Records from 2017 to 2019. Most recent: inspection, 22 May 2019.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 22 January 2019
Resolved
Means shall be provided to control leaks of flammable liquids. Observed oil drain line wrapped with several rags. Rags were soaked through with oil and dripping into the provided bucket which was in contact with the main engine, representing a fire hazard. 74 SOLAS (14) II-2/4.1.1
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 February 2019
Resolved 22 January 2019
Resolution: PSCO verified deficiency rectified.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 15 January 2019
Resolved
The machinery, boilers and other pressure vessels, associated piping system and fittings shall be of a design and construction adequate for the service for which they are intended. The design shall have regard to materials used in construction, the purpose for which the equipment is intended, and conditions on board. A temporary repair consisting of a rubber patch was observed on the discharge side of the fire/general service pump. The repair leaked significantly when the system was pressurized. The Responsible Organization did not authorize the repair. - 74SOLAS(04) II-1/26.1 30ABC
Action required: 30 - Ship detained
Due 15 January 2019
Resolved 22 January 2019
Resolution: See attached Class report.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 15 January 2019
Resolved
Fire-extinguishing appliances shall be readily available. All three fire pumps have a manual valve closed on the suction side making remote starting and immediate water delivery unavailable. - 74SOLAS(14) II-2/10.1.1.2 30ABC
Action required: 30 - Ship detained
Due 15 January 2019
Resolved 22 January 2019
Resolution: See attached Class report.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 15 January 2019
Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. For this purpose, the following shall be met: means shall be provided to control leaks of flammable liquids. Observed excessive oil leaks on the fuel oil and lube oil purifying units and associated piping. Crew attempted to reduce these leaks using rags that were hidden by cardboard which had been painted to match the purifiers and associated piping. Additional significant oil leaks were found on the main engine and emergency generator. - 74SOLAS (14) II-2/4.1.1 30ABC
Action required: 30 - Ship detained
Due 15 January 2019
Resolved 22 January 2019
Resolution: See attached Class report.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 15 January 2019
Resolved
The company should establish procedures to ensure that the ship is maintained in accordance with the provisions of the relevant rules and regulations and with any additional requirements which may be established by the company. In meeting these requirements, the company should ensure that: any non-conformity is reported, with its possible causes, if known; and ensure appropriate corrective action is taken. An unauthorized temporary repair was made to the discharge side of the fire and general service pump and was not reported to the Responsible Organization. Excessive oil leaks were observed on the oil purifier pumps and on the emergency generator, representing a significant fire hazard. Cardboard was painted and placed on the piping and oil purifier pumps which concealed rags and leaks. The crew made unsatisfactory repairs to the oily water supply piping that were not reported to the Responsible Organization. Operational-related deficiencies collectively provide objective evidence of a serious failure, or lack of effectiveness, of the implementation of the ISM Code. No evidence of required reporting to the designated person was observed. An external audit is recommended to be conducted within 30 days by the flag state or RO to determine whether the ship is operating in accordance with the ISM Code. Provide decision to USCG prior to departing port. - 74SOLAS(14) IX/3.1 & ISM Code Part A 10 30ABC
Action required: 30 - Ship detained
Due 15 January 2019
Resolved 22 January 2019
Resolution: See attached Class report.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 15 January 2019
Resolved
Any ship of 10,000 gross tonnage and above shall be fitted with oil filtering equipment complying with paragraph 7 of this regulation. PSCO observed excessive leaks on the oily water supply piping. - MARPOL 1/14.2 17AC
Action required: 15 - Rectify deficiencies by next port
Due 15 January 2019
Resolved 25 January 2019
Resolution: Resolved per attached class report.
09 - Working and Living Conditions › 092 - Working Conditions › Steam pipes and pressure pipes
Issued 15 January 2019
Resolved
Every steam pipe and fitting connected thereto shall be so designed, constructed, and installed as to withstand the maximum stresses to which it may be subject. PSCO observed three steam leaks coming from piping near the main boiler that pose a significant hazard to personnel. - 74SOLAS(04) II-1/33.1 17AC
Action required: 17 - Rectify deficiencies prior to departure
Due 15 January 2019
Resolved 22 January 2019
Resolution: See attached Class report.
14 - Pollution Prevention › 146 - MARPOL Annex VI › Incinerator incl. operations and operating manual
Issued 15 January 2019
Resolved
Each incinerator shall be approved by the administration taking into account standard specifications for shipboard incinerators. An interlock should be installed to prevent the charging door from opening while the incinerator is in operation. PSCO observed the interlock on the door inoperable allowing access to inside the incinerator during operation. The incinerator cannot be operated until the condition is rectified. - MARPOL VI/16.6.1 17AC
Action required: 17 - Rectify deficiencies prior to departure
Due 15 January 2019
Resolved 22 January 2019
Resolution: See attached Class report.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 15 January 2019
Resolved
All shell fittings and valves required by this regulation shall be of steel, bronze, or other approved ductile material. All pipes to which this regulation refers shall be of steel or other equivalent material to the satisfaction of the administration. Extensive temporary repairs found on the sewage system at the treatment tank and air conditioning system in the air conditioning space and in the associated piping to the galley were not made of steel or equivalent material. - ICLL I/22.6 50AC
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 February 2019
Resolved 22 January 2019
Resolution: See attached Class report.
01 - Certificates & Documentation › 013 - Documents › Oil record book
Issued 15 January 2019
Resolved
Any failure of the oil filtering equipment shall be recorded in the Oil Record Book Part I. The engineers told PSCO’s that the Oily Water Separator was taken out of service to conduct repair of piping. This was not logged in the Oil Record Book. - MARPOL I/17.5 10C
Action required: 10 - Deficiency Rectified
Due 15 January 2019
Resolved 15 January 2019
Engineering › Fuel Oil Storage/Transfer System › Valve
Issued 6 December 2017
Resolved
1499–Other (Prop. & Aux. Machinery)- Means shall be provided to control leaks of flammable liquids. PSCO observed active FO leaks: IWO relief valve on SSGs FO delivery line, and mechanical seal failure IWO main engine FO circulation pump. 74 SOLAS(09) II-2/4.1.1 60a
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 12 December 2017
Resolution: Received class report documentation from NKK stating deficiency has been rectified. The class report stated: Relief valve on SSGs delivery line was overhauled and flange connection on main engine circulation pump re-tightened. SSGs delivery line and main
Pollution Prevention/Response › Prevention Equipment › Oily Water Separator (15 ppm)
Issued 6 December 2017
Resolved
1730-Oily-water separating equipment-Oil filtering equipment referred to in paragraph 2 of this regulation shall comply with paragraph 6 of this regulation. PSCO observed the crew for approximately 20 minutes were unable to run the ships oily water separator, and oil content monitor is missing tamper proof seal. Further investigation found 3-way valve frozen in the closed position. MARPOL I/14.7 40a
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 12 December 2017
Resolution: Received class report documentation from NKK stating deficiency has been rectified. The class report stated: 3-way valve was overhauled; separator tested and confirmed SAT operations, tamper proof seal in place.
Fire Fighting › Automatic Sprinkler System › Testing Switches (Alarm/Sprinklers)
Issued 6 December 2017
Resolved
1099- Other (alarm-signals)-The condition of the ship and its equipment shall be maintained after survey to conform with the provisions of the present regulations to ensure the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. PSCO observed INOP low water alarm to fresh water tank servicing hyper mist system. 74 SOLAS(14) I/11a 40a
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 12 December 2017
Resolution: Received class report documentation from NKK stating deficiency has been rectified. The class report stated: low water alarm to fresh water tank sensor was repaired, tested and confirm operable.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 6 December 2017
Resolved
0899- Other (accid. prevent.)- Steering gear compartments shall be provided with suitable arrangements to ensure working access to steering gear machinery and controls. These arrangements shall include handrails and gratings or other nonslip surfaces to ensure suitable working conditions in the event of hydraulic fluid leakage. PSCO observed no non-slip surface exists between the access point and the control station. 74SOLAS (09) II-1/29.13.2 50a
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 5 January 2018
Resolved 12 December 2017
Resolution: Received class report documentation from NKK stating deficiency has been rectified. The class report stated: Suitable non-slip surface has been provided in steering gear compartment between the access point and the control station.