This record may be incomplete: the most recent inspection recorded for this vessel was 10 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
Tonnage as PSIX records it3430 - Convention (Subpart B), Gross Ton 3811 - Dead Weight, Metric Ton 1029 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
A report is not offered for this hull. Its Coast Guard record spans fewer than two calendar years. That is a statement about the record, not about the vessel. What a sparse-record report looks like.
Inspection history · 1
14 October 2016ISPS II Exam · COC-GAS Renew · Deficiency Check · Ballast Water Examination
Emergency shut down valves in liquid piping should fully close under all service conditions within 30 s of activation. The vessels ESD was unable to close the ESD valves from multiple locations over the course of 2 hours.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 October 2016
Resolved 21 October 2016
Resolution: Attended vessel and witness proper operation of ESD system.
Deck/Cargo › Holds/Tanks › Tank Pressure Monitoring Device
Issued 19 October 2016Resolved
A high pressure alarm should be provided for each cargo tank. The crew was unable to show a high level alarm for cargo tank 2, and was unfamiliar with the equipment used to test the system.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 October 2016
Resolved 21 October 2016
Fire Fighting › Structural - A Class Divisions › Doors
Issued 19 October 2016Resolved
Fire resistance of doors shall be equivalent to that of the division in which they are fitted. All of the vessels Class A doors have had the gaskets removed, compromising the ability of the door to stop the passage of smoke.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 21 October 2016
Resolved 21 October 2016
Resolution: Received documentaion from door manufacturer that the door was designed and approved to meet Class A standards without a gasket.