OPTI-EX

OPTI-EX is a 2011 industrial vessel. The Coast Guard has recorded 37 inspections since 2010, most recently in January 2026, along with 20 deficiencies and 2 casualty investigations between 2012 and 2019.

Records from 2010 to 2026. Most recent: inspection, 23 January 2026.

Built
2011
Last inspected
23 January 2026
Documentation
Case Pending · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

8770364 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
WQJS419
1052777
Flag
UNITED STATES
—
Maury page id
psix-1052777

Inspections, by type

…with no type recorded7
Years with a record 14 calendar years (2010–2026)
The 37 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Offshore class in Maury's sources begin in 1978.

Documentation record

Registered dimensions (L × B × D)252.0 ft × 252.0 ft × 137.8 ft
Registered tonnagegross 10,917 / net 3,275
ITC dimensions (L × B × D)252.0 ft × 252.0 ft × 137.8 ft
ITC tonnagegross 10,917 / net 3,275
BuilderSAMSUNG HEAVY INDUSTRIES · GEOJE ISLAND, KOREA, REPUBLIC OF · built 2011
Hull materialSteel
PropulsionNot recorded
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portCOVINGTON, LA
Trade endorsementsRegistry
DocumentationCase Pending · issued 4 February 2026 · expires 31 March 2027
Service, as the file records itIndustrial Vessel
Hull formbarge (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it3275 - Convention (Subpart B), Net Ton
10917 - Convention (Subpart B), Gross Ton
25 - Displacement, Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

Inspection history · 37

23 January 2026 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8300592
12 September 2025 Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8236766
31 July 2025 Administrative Inspection
Administrative · Outer Continental Shelf National Center of Expertise · Activity 8199183
4 November 2024 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8029491
14 August 2024 Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7982988
18 November 2022 Damage Survey · Administrative Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7671902
15 September 2022 Administrative Inspection · Damage Survey
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7671863
29 August 2022 Administrative Inspection · Damage Survey
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7577431
20 June 2022 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7482247
15 March 2022 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7424930
13 December 2021 Deficiency Check · COI Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7367259
11 October 2021 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7337791
9 September 2021 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7309030
16 March 2021 Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7157574
18 January 2021 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7142857
9 November 2020 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7104900
27 May 2020 Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6962022
21 March 2020 Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6937613
11 February 2020 Annual Inspection · MTSA Verification
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6904375
1 August 2019 Spot Check
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6773512
15 July 2019 Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6809461
6 May 2019 Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6685721
7 February 2019 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6621550
7 February 2019 Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 6650404
23 January 2019 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6614190
22 January 2019 Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6613925
29 January 2018 COI Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6613952
5 December 2017 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6322639
29 September 2016 Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6012575
15 August 2016 COI Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5956960
12 July 2016 Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5938297
14 October 2015 Deficiency Check
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 5753833
18 August 2015 Annual Inspection · Administrative Inspection
Physical examination · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 5220051
4 May 2014 Type not recorded
No type recorded · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4852420
25 February 2011 COI Inspection · Construction Oversight
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4183991
21 January 2010 Type not recorded
No type recorded · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 3667357
15 January 2010 Type not recorded
No type recorded · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 3664770

Deficiency record · 20

07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 5 January 2022 Resolved
Each space protected by a CO2 system must hav ethe following means for closing the openings to the space from outside the space: (1) doors... The latch on the door to the generator 9200 enclosure is broken, preventing positive closure. Fix to the satisfaction of attending marine inspector. 46 CFR 108.455
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 February 2022
Resolved 10 January 2022
Resolution: Received photographs of satisfactory repairs carried out to door latch.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 5 January 2022 Resolved
All power actuated valves required in an emergency to operate the vessel's machinery to maintain stability and operate bilge and firemain systems must have a manual means of operation. MOV SE-13 in the SE column is positioned in such a way as to prevent manual operation. Repair to the satisfaction of the attending marine inspector. 46 CFR 56.501(g)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 February 2022
Resolved 24 January 2022
Resolution: Received photographs showing the valve was rotate to allow access for local manual operation.
01 - Certificates & Documentation › 013 - Documents › Fire control plan - all
Issued 16 March 2021 Resolved
A review of the floating installation's fire control plan revealed inaccurate total and type of fire doors installed. Illustrates on the fire control plan must reflect the type of fire doors installed and fire equipment on board. Provide documentation of a revised plan for Coast Guard verification to attest fire boundaries and equipment on board.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 April 2021
Resolved 5 January 2022
Resolution: Satisfactorily reveiwed revised fire control plan that was signed and stamped by ABS.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 1 August 2019 Resolved
Fire and Gas detection system panel located along the back wall of the control room was observed inoperable. The system monitors the flash gass compressors located in the northeast quadrant of the facility. The system is emergency equipment that must be maintained and serviceable per manufacturer's requirements. Provide documentation that the sustem is operational and serviceable per manufacturer's requirements.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 August 2019
Resolved 28 August 2019
Resolution: Unaproved system removed from facility.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 1 August 2019 Resolved
"A" class boundaries not being met. At least 04 "A" class doors were permanently held back by installed devices. Remove devices and keep doors closed except for transit.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 August 2019
Resolved 28 August 2019
Resolution: Removed all hold back devices.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 29 January 2018 Resolved
Lifeboat #2 is missing data plate. 46 CFR 160.133-17
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 March 2018
Resolved 5 February 2018
Resolution: Proof of data plate provided.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 29 January 2018 Resolved
Regulator relief valve on #2 Lifeboat suppled air system is blowing by. 46 CFR 108.520
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 March 2018
Resolved 5 February 2018
Resolution: Relief valve was replaced.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 29 January 2018 Resolved
Cable run penetrations in control room were improperly installed. 46 CFR 180.133
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 March 2018
Resolved 5 February 2018
Resolution: Equipment was reinstalled.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 29 January 2018 Resolved
Distribution panels throughout the facility were missing index with amperage. 46 CFR 108.133
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 March 2018
Resolved 5 February 2018
Resolution: All panels were labeled.
Lifesaving › Lifeboat › Self-contained Air Support System
Issued 15 August 2016 Resolved
Air system has pin hole leak.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 August 2016
Resolved 22 August 2016
Resolution: Line replaced and tested sat.
Electrical › Electric Supply System (service) › Cable
Issued 15 August 2016 Resolved
Cable transit missing blocks.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 15 September 2016
Resolved 15 September 2016
Resolution: Blocks replaced.
Lifesaving › Lifeboat › Hull
Issued 18 August 2015 Resolved
Lifeboats are fadded to a whiteish color, replace/repair to original condition. 46CFR160.137-7(b)(24)
Action required: 705 - Other - as specified
Due 1 October 2015
Resolved 1 October 2015
Resolution: Hull Refurbished
Operations/Management › Drills/Instruction › Activating General Alarm
Issued 18 August 2015 Resolved
Several general alarm signals and flashing red lights around facility are inop, replace/restore to original conditon. 46CFR113.25(c)(2)
Action required: 705 - Other - as specified
Due 1 October 2015
Resolved 1 October 2015
Resolution: General Alarms Replaced
Documentation › Certificates/Documents › Certificate of Financial Responsibility
Issued 19 July 2011 Resolved
Provide BOEMRE Oil Spill Financial Responsibility Certificate
Action required: 705 - Other - as specified
Resolved 20 July 2011
Resolution: rcvd email with supporting document
Communications › Alarms/Indicators › Bilge Alarm
Issued 19 July 2011 Resolved
Prove all column bilge alarms
Action required: 705 - Other - as specified
Resolved 8 September 2011
Documentation › Markings/Placards › Lifejacket Placard
Issued 19 July 2011 Resolved
Label lifesaving appliances with IMO labels
Action required: 705 - Other - as specified
Resolved 23 July 2011
Resolution: rcvd supporting documentation validating completion
Lifesaving › Lifeboat Equipment › Anti-seasickness Medicine
Issued 19 July 2011 Resolved
Provide first aid kit and seasick pills in both lifeboats
Action required: 705 - Other - as specified
Resolved 23 July 2011
Resolution: rcvd email validating completion
Lifesaving › Lifeboat › Lamp (outside)
Issued 19 July 2011 Resolved
Repair running lights in both lifeboats
Action required: 705 - Other - as specified
Resolved 8 September 2011
Fire Fighting › Fixed Fire Detection System › Indicator Light
Issued 19 July 2011 Resolved
Replace missing gas detector in the galley.
Action required: 705 - Other - as specified
Resolved 20 July 2011
Resolution: Rcvd email with picture supporting replacement of gas detector
Communications › Alarms/Indicators › Fire Alarm
Issued 19 July 2011 Resolved
Make repairs to emergeny signals
Action required: 705 - Other - as specified
Resolved 8 September 2011

Casualty record · 2

14 August 2012Routine · role: Involved in a Marine Casualty · activity 4413671
15 July 2019Routine · role: Involved in a Marine Casualty · activity 6809461
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.