Records from 2015 to 2026. Most recent: inspection, 12 August 2026.
Inspection history · 15
12 August 2026
Annual Inspection
Physical examination · Marine Safety Unit Savannah · USCG Southeast District (CGD-SE) · Activity 8462525
24 February 2025
COI Inspection · Deficiency Check
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 8083554
3 September 2024
Drydock Exam · Internal Structural Exam
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7995177
7 June 2024
Annual Inspection · Administrative Inspection
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7929833
13 June 2023
MTSA Verification · Annual Inspection · Administrative Inspection · Deficiency Check
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7714120
4 August 2022
Internal Structural Exam · Administrative Inspection · Deficiency Check · Periodic Inspection · Drydock Exam
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7524930
20 July 2021
MTSA Verification · Administrative Inspection · Annual Inspection
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7261955
22 March 2021
Type not recorded
No type recorded · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7162066
2 April 2020
Annual Inspection · MTSA Verification · Examination of Repairs
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6941450
19 August 2019
Internal Structural Exam · Drydock Exam · Administrative Inspection · MTSA Verification · Hull Examination · Examination of Repairs · Annual Inspection
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6797928
15 August 2018
Deficiency Check · Annual Inspection · Plan Review (Other than "T") · Administrative Inspection · MTSA Verification
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6513882
4 May 2018
Administrative Inspection
Administrative · Navigation Center · Activity 6405624
16 November 2017
Administrative Inspection · Hull Examination · Internal Structural Exam · Drydock Exam
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6310678
21 April 2017
Annual Inspection · MTSA Verification
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6146710
18 August 2016
MTSA Verification · Annual Inspection · DAPI Audit
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 5975023
09 - Working and Living Conditions › 092 - Working Conditions › Steam pipes and pressure pipes
Issued 19 March 2025
Resolved
Relief valves not tested with in required interval.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 April 2025
Resolved 3 April 2025
Resolution: Recieved notification that relief valve were tested 1 failed and was replaced with new valve.
11 - Life Saving Appliances › N/A - No Subsystem › Operation of Life Saving Appliances
Issued 7 June 2024
Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Hydrostatic release unit on EPIRB was expired.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 June 2024
Resolved 25 June 2024
Resolution: HRU replaced with a new one
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 2 November 2023
Resolved
Where natural ventilation is provided for spaces protected by a carbon dioxide extinguishing system, provisions shall be made for easily and effectively closing off the ventilation. above the port side high speed engine there is a 10 in penetration that is open the the atmosphere with no means of closure. 46 CFR 95.15-35
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 December 2023
Resolved 13 November 2023
Resolution: A rubber cover was added to the access pipe for when not used as an MPT
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 14 June 2023
Resolved
Each firehose on each hydrant must have a combination solid stream and water spray firehose nozzle approved under subpart 162.027 of this chapter.
Nozzles not of approved type.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 July 2023
Resolved 2 November 2023
Resolution: Verified approved type of hose nozzles. deficiency rectified.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 14 June 2023
Resolved
life line at least as long as twice the height where it is stowed above the waterline with the vessel in its lightest seagoing condition, or 30 meters (100 feet) in length, whichever is the greater; (B) Non-kinking; (C) Not less than 8 millimeters (5/16 inch) in diameter; (D) Of a breaking strength which is not less than 5 kiloNewtons (1,124 pounds-force); and (E) Is, if synthetic, a dark color or certified by the manufacturer to be resistant to deterioration from ultraviolet light.
life line of incorrect type
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 July 2023
Resolved 17 July 2023
Resolution: Replaced life line
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 14 June 2023
Resolved
Each cable installation must meet— (1) Sections 6, of IEEE 45.8–2016.
Extension cord providing power to equipment mounted on the dredge ladder.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 July 2023
Resolved 17 July 2023
Resolution: removed extension cord and added an outlet
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 14 June 2023
Resolved
Each outlet and junction box must be suitable for the environment in which it is installed and be constructed to the appropriate NEMA or IEC standard.
water maker pump controller missing cover/plugs
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 July 2023
Resolved 17 July 2023
Resolution: removed controller and associated wiring.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 14 June 2023
Resolved
All general alarm bells shall be identified by red lettering at least 1/2 inch high: “GENERAL ALARM—WHEN BELL RINGS GO TO YOUR STATION.”
markings missing or in wrong location.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 July 2023
Resolved 17 July 2023
Resolution: remarked GE markings
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 14 June 2023
Resolved
Exhaust pipe installations must conform to the requirements of ABYC P–1 and part 1, section 23 of NFPA 302 (both incorporated by reference;
STBD dredge engine exhaust expansion joint is cracked.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 July 2023
Resolution: Replaced cracked section of exhaust
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 13 June 2023
Resolved
Top of STBD side E/R WTD was found to have a wasted flange.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2023
Resolution: Approx 12" of flat bar scarfed into upper door flange, tested with fire hose for tightness.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 13 June 2023
Resolved
Stbd side hydrant drop identified by O/O for replacement between valve and main pipe coupling.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2023
Resolution: New section of pipe replaced between valve and "T" from the main line. Operational test with fire main conducted sat.
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 13 June 2023
Resolved
Self-closing dampers were painted and in need of grease to enable closing.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2023
Resolution: Port dampers were greased and demonstrated to completely close as designed.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 26 August 2022
Resolved
The boundary bulkheads and decks separating the accommodations and control stations from cargo and machinery spaces, galleys, main pantries and storerooms, other than small service lockers, shall be of “A” Class construction.
Control room A class door is broken and missing latch assembly
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 24 September 2022
Resolution: Received photo that a patch and latch assembly was installed, notified O/O that repair must be approved by MFG or door has to be replaced. O/O stated there has been issues in getting a replacement door sourced.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 26 August 2022
Resolved
Where natural ventilation is provided for spaces protected by a carbon dioxide extinguishing system, provisions shall be made for easily and effectively closing off the ventilation.
Self closing vent for port stack and stbd E/R vent were inoperable.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 September 2022
Resolved 29 August 2022
Resolution: Observed satisfactory test of the ventilation shutdown for the port engine.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 26 August 2022
Resolved
During preparation and launching, the survival craft, its launching appliance, and the area of water into which it is to be launched are illuminated by lighting supplied from the vessel's emergency source of electrical power.
Missing embarkation lighting.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 September 2022
Resolved 29 August 2022
Resolution: Two lights were installed and tested on each side of the embarkation area, sat.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 26 August 2022
Resolved
Each battery-operated, relay-controlled lantern used in accordance with Table 112.05-5(a).
Port E/R and pump room e-light inoperable.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 29 August 2022
Resolution: The lights were installed and tested, sat.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 26 August 2022
Resolved
Electric installations on vessels must ensure: (1) Maintenance of services necessary for safety under normal and emergency conditions.
Power strip installed in break room powering fridge and ice machine.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 29 August 2022
Resolution: The power strip was removed.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Sewage treatment plant
Issued 26 August 2022
Resolved
No person may operate any vessel equipped with installed toilet facilities unless it is equipped with: (1) An operable Type II or III device that has a label on it under § 159.16 or that is certified under § 159.12 or § 159.12a.
FWD type II MSD feed tank is loose, system needs to be repaired to original MFG specification.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 24 September 2022
Resolution: MSD's serviced and returned to MFG specifications.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 26 August 2022
Resolved
Each fire hydrant shall be identified in red letters and figures at least two inches high “FIRE STATION NO. 1,” “2,” “3,” etc. Where the hose is not stowed in the open or behind glass so as to be readily seen, this identification shall be so placed as to be readily seen from a distance.
Markings missing
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 29 August 2022
Resolution: The markings were placed on the fire hydrants.
01 - Certificates & Documentation › 011 - Ships Certificates › Load Lines (including Exemption)
Issued 26 August 2022
Resolved
All U.S.-flag vessels which engage in domestic voyages by sea (coastwise and intercoastal voyages) shall be subject to the applicable provisions of load lines.
Vessel is still completing load line survey and has conditions of the survey outstanding, limited to operation with in the boundary line.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 10 November 2022
Resolution: The Load Line Annual survey was completed by attending Lloyds surveyor and cert signed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 4 August 2022
Resolved
If your vessel's Certificate of Inspection is renewed less often than annually, the marine inspector must check the settings of the safety or relief valves on all pressure vessels, except cargo tanks, twice every 5 years. No more than 3 years may elapse between any check and its immediate predecessor.
Relief valve need to be tested
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 24 September 2022
Resolution: Relief valves have been serviced and tested.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 4 August 2022
Resolved
Each hand portable fire extinguisher shall be marked with a number and the location where stowed shall be marked with a corresponding number at least 1/2 inch high. Where only one type and size of hand portable fire extinguisher is carried, the numbering may be omitted.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 September 2022
Resolved 29 August 2022
Resolution: The portable extinguishers were marked per 46CFR 97.37.23.
14 - Pollution Prevention › 141 - MARPOL Annex I › Other (MARPOL Annex I)
Issued 20 July 2021
Resolved
Must have a placard of at least 5x8" made of durable material fixed in a conspicuous place in each machinery space, or at the bilge and ballast pump control station stating: Discharge of Oil Prohibited.
Placard was faded and not legible; replace.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 20 July 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 July 2021
Resolved
The operating gear for the shutoff valves at the tanks shall be accessible at all times and shall be suitably marked.
Shutoff Valve placard faded and not legible; replace.
46CFR56.50-10(c)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 20 July 2021
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 21 April 2017
Resolved
Port running light bulb not working and starboard running light stanchion bent over ; corrected both
Condition: Improper/Lack of Maintenance
Due 28 April 2017
Resolved 24 April 2017
Engineering › Fuel Oil Service System › Piping
Issued 21 April 2017
Resolved
drain line for emergency generator goose neck containment plug with debris; cleared line
Condition: Improper/Lack of Maintenance
Due 28 April 2017
Resolved 24 April 2017
Communications › Radio Communications › EPIRB
Issued 21 April 2017
Resolved
EPIRB hydrostatic release out of date; renewed
Condition: Improper/Lack of Maintenance
Due 28 April 2017
Resolved 24 April 2017