MARIA FAITH is a 2008 tank ship. The Coast Guard has recorded 6 inspections since 2016, most recently in May 2026, along with 14 deficiencies — 2 with no resolution recorded — and 3 operational controls.
Records from 2016 to 2026. Most recent: inspection, 22 May 2026.
Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
Tonnage as PSIX records it47125 - Dead Weight, Metric Ton 29266 - Convention (Subpart B), Gross Ton 12026 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 2016 to
2026 for this class, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
Inspection history · 6
22 May 2026PSC B
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 8376511
15 May 2026Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8373826
27 April 2026PSC A · COC-CHEM & TVE Renew
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8352233
15 May 2024PSC A · COC-CHEM & TVE Renew
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7912250
15 April 2016Ballast Water Examination · ISPS II Exam · COC-CHEM & TVE Annual · COE-Offshore
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 5854844
11 April 2016Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 5851367
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 22 May 2026No resolution recorded
In tankers, electrical equipment , cables and wiring shall not be installed in hazardous locations unless it conforms with the standards not inferior to those acceptable to the organization. PSCO found exposed wiring and wastage on high level and overfill alarms/ radar domes electrical conduit manifold on all cargo tanks. Deficiency must be rectified prior to cargo operations.
Solas 11-1/ 45.11
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 23 May 2026 — due date passed with no resolution recorded
Resolution: Reviewed and accepted class report from ABS. The report stated temporary repairs have been completed, but extended for permanent repairs.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 22 May 2026Resolved
The machinery… associated piping systems and fittings shall be of a design and construction adequate for the service for which they are intended and shall be so installed and protected as to reduce to a minimum any danger to persons on board. PSCO found disconnected valve actuator, hanging from a towel, on #5 stbd fill valve. Deficiency must be rectified prior to cargo operations.
Solas 11-1/26.1
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 23 May 2026
Resolution: Reviewed and accepted class report from ABS. The report stated butterfly valve was reconnected and tested satisfactorily.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 22 May 2026Resolved
Means shall be provided to control leaks of flammable liquids. PSCO found fuel leak on the fuel line of the #3 cylinder on the main engine and fuel oil leak from the fuel pump filter assembly in the fuel oil purifier room.
Solas 11-2/ 4.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 May 2026
Resolution: Reviewed and accepted class report from ABS. The report stated bolts have been retightened with no leaks observed.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 22 May 2026Resolved
Ignition sources shall be separated from combustible materials and flammable liquids. PSCO observed the stowage of 55 gallon drums of oil and other materials throughout the cargo block area.
Solas 11-2/ 4.1.5
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 May 2026
Resolution: Reviewed and accepted class report from ABS. The report stated 55 gallon drum was properly stowed.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 22 May 2026No resolution recorded
The company should establish procedures to ensure that the ship is maintained in conforming with the provisions of the relevant rules and regulations and additional company requirements . The technical and operational nature of deficiencies 1,2,3,4 provide objective evidence of a failure to implement ISM code. An internal audit, satisfactory to OCMI, must be submitted in 90 days
Solas IX/ 5
ISM 10
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 August 2026 — due date passed with no resolution recorded
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Company responsibility and authority
Issued 27 April 2026Resolved
The company should establish procedures to ensure that the ship is maintained inconformity with the provisions of the relevant rules and regulations and with additional requirements which may be established by the company. The technical and operational nature of deficiencies two, three, four, five, six, seven, and eight provide objective evidence of a serious failure of implementation of the ISM code. An external audit report satisfactory to the OCMI must be submitted prior to clearance of this deficiency.
74SOLAS (20) IX/ 3.1
ISM Code 10.1
Action required: 30 - Ship detained
Resolved 4 May 2026
Resolution: Received Vessels ISM Audit Report.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 27 April 2026Resolved
Sufficient foam concentration shall be supplied to ensure at least 30 minutes of foam generation when using the highest of the solution rates.
PSCO observed foam quantity of 7.2 m3 when system requires 7.5 m3 for necessary amount.
74SOLAS(20) VII/10.1
IBC 11.3.6
Action required: 30 - Ship detained
Resolved 4 May 2026
Resolution: Crew addressed vacuum on foam tank. Foam settled to 7.5m3. Foam analysis was conducted and test results were found satisfactory.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 27 April 2026Resolved
Such monitoring equipment shall also provide an alarm facility which is activated by detection of over pressure or under pressure conditions within a tank.
Crew had disabled audible alarm for pressure alarms by taping over speaker, redering alarms inaudible in CCR.
74SOLAS(20) VII/ 10.1
IBC 8.3.3
Action required: 30 - Ship detained
Resolved 27 April 2026
Resolution: Crew removed tape and alarms tested SAT
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 27 April 2026Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board.
PSCO observed 03 category A fire doors that shall be self-closing that did not self-close and numerous hold backs were present on self-closing doors. 01 fire door from galley to passage way, 01 fire door from galley to crew mess, and 01 fire door from engine room to crew locker room not self-closing.
74SOLAS (20) I/11a
Action required: 30 - Ship detained
Resolved 4 May 2026
Resolution: All doors found out of regulation, in earlier exam, were fixed and all hold back devices were removed from all doors examined.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 27 April 2026Resolved
Independent cargo tanks shall be electrically bonded to the hull. All gasketed cargo-pipe joints and hose connections shall be electrically bonded. PSCO observed numerous bonding wires twisted, missing and not connected throughout the cargo piping on deck.
74SOLAS(20) VII/ 10.1
IBC 10.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 May 2026
Resolution: Rectified inadequate bonding.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 27 April 2026Resolved
Life buoys shall be stowed as to be capable of being rapidly cast loose.
PSCO observed life buoys on bridge wing not stowed for rapid release. Connection to smoke/light signal interfered with release.
74SOLAS(20) III/ 7.1.1.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 27 April 2026
Resolution: Rectified while onboard, fixed the line that was keeping lifebuoys from being rapidly released.
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board.
74SOLAS(20) I/11a
PSCO observed number 35 ballast water tank vent on deck had a hole rusted in the top that had been taped and painted over.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 May 2026
Resolution: The vent cover was replaced with a new one. See class report.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 27 April 2026Resolved
Emergency towing arrangements at both ends shall be of adequate strength taking into account the size and deadweight of the ship, and the expected forces during bad weather conditions. The design and construction and prototype testing of emergency towing arrangements shall be approved by the Administration.
The PSCO observed the aft emergency towing light to be extinguished.
74SOLAS(20)II-1/3.1.1.2.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 27 April 2026
Resolution: Crew replaced batteries. Light tested SAT
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo operation
Issued 27 April 2026Resolved
Each vessel vapor connection flange face must have a permanent stud projecting outward that has a 12.7 millimeter (0.5 inch) diameter and is at least 25.4 millimeters (1 inch) long.
PSCO observed the bolt on flange face to be deteriorated and not correct size.
46CFR39.2001(j)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 May 2026
Resolution: The bolts on both the port and starboard sides of the vapor return connection flange were replaced with correctly sized bolts. See Class Report.