13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 2 May 2025
Resolved
A flammable vapor detection system required by 46 CFR 182.410(c) must be located in the lowest part of a space containing a fuel tank above the expected bilge water level.
46 CFR 182.480
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 May 2025
Resolved 29 April 2026
Resolution: Vapor detector was lowered; all sat.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 2 May 2025
Resolved
A vessel must carry a first-aid kit approved under ISO 18813:2006(e) paragraph 4.12. Update first aid kit.
46 CFR 184.710
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 May 2025
Resolved 29 April 2026
Resolution: Updated, verified with no expired medication; all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 2 May 2025
Resolved
At each inspection for certification, the operator shall be prepared to conduct test of its fire protection equipment, including testing of alarms and ventilation shutdowns.
46 CFR 176.810
Action required: 701 - Prior to carriage of passengers/cargo
Due 2 May 2025
Resolved 2 May 2025
Resolution: Bungie straps on closures replaced.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 2 May 2025
Resolved
The OCMI may require that a vessel and its equipment undergo any additional test or inspection deemed reasonable and necessary to determine that the vessel and its equipment are suitable for the service in which they are to be employed. Remove paint from fuel tank mounting brackets for annual visual inspections.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 29 April 2026
Resolution: Paint was removed from fuel tank brackets.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 2 May 2025
Resolved
Each distribution panel and switchboard must be in as dry a location as practicable, adequately ventilated, and protected from falling debris and dripping or splashing water. Install splash shield on distribution panel at stern.
46 CFR 183.330
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 May 2025
Resolved 25 November 2025
Resolution: Rectified
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 14 April 2024
Resolved
A submersible electric bilge pump may be used as a power bilge pump required by Table 182.520(a) only on a vessel of not more than 19.8 meters (65 feet) in length carrying not more than 49 passengers, other than a ferry, provided that: (1) The pump is listed by an independent laboratory as meeting the requirements in UL 1113. On-board bilge pumps are not UL1113 listed. 46CFR182.520
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2024
Resolution: UL listed pumps installed.
04 - Emergency Systems › N/A - No Subsystem › Man Overboard Drill (MOB)
Issued 14 April 2024
Resolved
The owner, charterer, master or managing operator shall instruct each crew member, upon first being
employed and prior to getting underway for the first time on a particular vessel and at least once every
three months, as to the duties that the crew member is expected to perform in an emergency... New crew members have not completed familiarization and drills. 46CFR185.420
***To be cleared by attending Marine Inspector***
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 13 May 2024
Resolution: Received video of MOB drill conducted on vessel.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 14 April 2024
Resolved
As appropriate for the intended voyage, a vessel must carry adequate and up-to-date: (1) Charts of large enough scale to make safe navigation possible. Onboard charts are not current. 46CFR184.420(a)(1)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 May 2024
Resolution: Updated charts provided.
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 14 April 2024
Resolved
Except on a vessel limited to daytime operations, the compass must be illuminated. Compass light on-board is not illuminated. Restricted to daytime operations. 46CFR184.402(c)
Action required: 705 - Other - as specified
Resolved 10 May 2024
Resolution: Compass light installed.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 14 April 2024
Resolved
The Certificate of Inspection and any SOLAS Certificates must be posted under glass or other suitable transparent
material, such that all pages are visible. All pages of the COI are not displayed. 46CFR176.302
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 May 2024
Resolution: COI displayed appropriately.
18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Other (Conditions of employment)
Issued 14 April 2024
Resolved
Marine employers shall establish programs for the chemical testing for dangerous drugs on a random basis of crewmembers on inspected vessels. Operator could not provide evidence of consortium enrollment. 46CFR 16.230(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 May 2024
Resolution: List of crew enrolled in consortium provided.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 14 April 2024
Resolved
The servicing facility must issue a certificate to the liferaft owner or owner's agent for each liferaft it services. Owner/operator did not have servicing certificate issued by the servicing facility. 46CFR176.302
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 May 2024
Resolution: Liferaft certificate porovided.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 14 April 2024
Resolved
For fixed-gas fire extinguishing systems...The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. O/O
could not provide servicing records for fixed gas
suppression system. 46CFR176.810(b)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 May 2024
Resolution: Servicing records provided.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 14 April 2024
Resolved
All escape hatches and other emergency exits used as means of escape must be marked on both sides in clearly
legible letters at least 50 millimeters (2 inches) high: “EMERGENCY EXIT, KEEP CLEAR”, unless such markings are
deemed unnecessary by the cognizant [name withheld] on-board is fading. 46CFR185.606
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 May 2024
Resolution: Emergency exit sign re-stenciled.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 24 April 2023
Resolved
A vessel must carry one floating waterlight, unless it is limited to daytime operation, in which case no floating waterlight is required. (1) Each floating waterlight must be approved in accordance with § 161.010 in subchapter Q of this chapter, or other standard specified by the Commandant, including, but not limited to, approval series 160.110. (2) Each ring life buoy with a floating waterlight must have a lanyard of at least 910 millimeters (3 feet) in length, but not more than 1,830 millimeters (6 feet), securing the waterlight around the body of the ring life buoy. (3) Each floating waterlight installed after March 11, 1997, on a vessel carrying only one ring buoy, must be attached to the lanyard with a corrosion-resistant clip. The clip must have a strength of at least 22.7 kilograms (50 pounds), and allow the waterlight to be quickly disconnected from the ring life buoy. Vessel float light bracket is broken so the float light is not supported / protected while the vessel is underway. Properly repair or replace the float light bracket. 46 CFR 180.70
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 May 2023
Resolution: Operator replaced the float light bracket with a new one - all sat.
05 - Radio Communications › N/A - No Subsystem › VHF EPIRB
Issued 18 April 2022
Resolved
IAW with D17 Instruction 16714.1A dtd 5 Mar 2007. Vessel must have on board a FCC Type Accepted Cat 1, 406 MHz EPIRB, installed to automatically float free and activate. Vessel's EPIRB's hydrostatic release is expired. Renew expired hydrostatic release. 46 CFR 180.64
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 April 2022
Resolved 19 April 2022
Resolution: Owner replaced the expired EPIRB hydrostatic release with a new one - all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 18 April 2022
Resolved
Vessel is required to have onboard bilge pump arrangements iaw 46 CFR 182.520(a). Vessel is using submersible electric bilge pumps to meet the requirement. Vessel's aft bilge pump was not working when tested. Repair aft bilge pump. 46 CFR 182.520
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Due 2 May 2022
Resolved 19 April 2022
Resolution: Owner replaced faulty aft bilge pump operational test - all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 18 April 2022
Resolved
Each survival craft must be secured to the vessel by a painter with a float free link permanently attached to the vessel. Vessels painter was not connected to the wink link. Connect IBA painter line to the weak link on the hydrostatic release. 46 CFR 180.130(a)
Condition: Placed in Improper Service
Action required: 701 - Prior to carriage of passengers/cargo
Due 2 May 2022
Resolved 19 April 2022
Resolution: Owner installed the IBA painter line to the hydrostatic release weak link - all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 28 June 2020
Resolved
Replace expired hydrostatic release on IBA.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 June 2020
Resolution: IBA hydrostatic release replaced.
Communications › Radio Communications › EPIRB
Issued 30 April 2018
Resolved
Replace expired EPIRB batteries.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2018
Resolution: New EPIRB provided.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 30 April 2018
Resolved
Provide proof of enrollment in a drug and alcohol testing program, including a list of covered employees.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 May 2018
Resolved 9 May 2018
Resolution: Proof of enrollment with list of covered employees received.
Lifesaving › Lifejacket/PFD (Type I) › Storage
Issued 26 April 2017
Resolved
Properly label all ADULT and CHILD PFD storage locations with type and quantity.
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 25 May 2017
Resolution: Owner labeled PFD storage locations.
Navigation › Piloting/Steering › Marine Charts
Issued 26 April 2017
Resolved
Provide onboard updated marine charts.
Action required: 705 - Other - as specified
Due 10 May 2017
Resolved 25 May 2017
Resolution: Owner properly updated nav charts and placed them onboard.
Construction/Loadline › Markings › Vessel Name/Home Port
Issued 25 April 2016
Resolved
Properly stencil vessel's name and hailing port onto the vessels stern.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Construction/Loadline › Structures › Door
Issued 25 April 2016
Resolved
Properly repair minor hairline cracks at the base of the cabin side doors. Aprox 2" - 3" inches in length. Monitor until repaired and notify the local OCMI if the condition worsens. Due by the vessels 2017 hull/ise exam.
Action required: 705 - Other - as specified
Due 30 April 2017
Resolved 26 April 2017
Resolution: Professional welder drill stopped, gouged, and welded cracks. Visual inspection SAT.
Operations/Management › Drug and Alcohol Testing › Employee Coverage
Issued 25 April 2016
Resolved
Ensure all employees are pre-employment drug screened and enrolled in company's DAPI program.
Action required: 701 - Prior to carriage of passengers/cargo
Due 2 May 2016
Resolved 27 April 2016
Resolution: Owner provided list of company employees pre tested and enrolled in their third party consortium.
Engineering › Bilge Water Management System › Valve
Issued 25 April 2016
Resolved
Properly install a marine grade valve in the fwd void electrical submersible bilge overboard piping.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Fire Fighting › Fixed Fire Detection System › Alarms
Issued 25 April 2016
Resolved
Properly repair the audible alarm located at the helm station on the vessels fire boy system. All other aspects of the system are functional/working properly.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Fire Fighting › Fire Bucket › Capacity
Issued 25 April 2016
Resolved
Replace vsl's 2 gallon fire buckets with 2.5 gallon fire buckets.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Lifesaving › Lifejacket/PFD (Type I) › Quantity
Issued 25 April 2016
Resolved
Vessel reduced to 26 total persons due to missing two type I PFD's.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 27 April 2016
Resolution: Owner purchased two additional Type I PFD's, stenciled vsl's name onto them and stowed onboard the vessel.
Communications › Radio Communications › EPIRB
Issued 25 April 2016
Resolved
Properly renew vsl's expired EPIRB hydrostatic release.
Action required: 701 - Prior to carriage of passengers/cargo
Due 25 May 2016
Resolved 27 April 2016
Resolution: Vessels crew renewed the expired hydro static release with a new one.
Construction/Loadline › Structures › Cofferdam
Issued 25 April 2016
Resolved
Properly repair broken hinges for vessels anchor line and chain stowage void hatch cover.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Personnel › Certificates/Documents/Licenses › License, Radio Officer
Issued 25 April 2016
Resolved
Vessel restricted to 1000' fm shore unless master has a valid FCC Marine Radio Operators Permit.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Resolution: Master obtained a valid FCC Marine Radio Operators Permit.
Operations/Management › Drug and Alcohol Testing › Testing, Equipment
Issued 25 April 2016
Resolved
Have onboard non expired alcohol test strips due to remote ops.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 27 April 2016
Resolution: Owner obtained two alcohol test strips and placed them onboard the vessel.
Fire Fighting › Means of Escape › Blocked
Issued 25 April 2016
Resolved
Properly label emerbency exits.
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 25 April 2016
Resolved
Provide 3'-5' line for vsl's float light.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 25 May 2016
Resolved 7 May 2016