07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 17 February 2023
Resolved
07122 - Fire control plan - A fixed fire detection and fire alarm system shall be installed in: periodically unattended machinery spaces. PSCO discovered a missing fire detector in the purifier room. A space protected by an automatic water mist system.
-74 SOLAS (04) II-2/7.4.1.1
-17ac
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 February 2023
Resolution: Recevied condition of class, which was endorsed for a period of one month. Deficiency cleared.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 17 February 2023
Resolved
07124-Maintenance of Fire protection systems- The function of the fixed fire detection and fire alarm systems shall be periodically tested to the satisfaction of the Administration by means of equipment producing hot air at the appropriate temperature. PSCO was informed the proper heat detection testing equipment is not on board.
-74 SOLAS (04) II-2/7.3.2
-17ac
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 February 2023
Resolution: Received condition of class stating that fire detection equipment was ordered.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 February 2023
Resolved
07199 - Fire Safety - Waste receptacles shall be constructed of non combustible material. PSCO observed plastic receptacle with oil soaked rags in the engine room workshop.
-74SOLAS(04)II-2/4.4.2
-17ac
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 February 2023
Resolution: Received class report stating: plastic receptacles were removed from the engine workshop.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 17 February 2023
Resolved
07126- Oil accumulation in engine room- Means shall be provided to control leaks of flammable liquids. PSCO discovered active diesel leak on transfer pump system in the purifier room. Additionally PSCO discovered an active diesel leak on the emergency generator fuel tank strainer and electrical fuel pump.
-74 SOLAS (04) II-2/4.1.1
-17ac
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 February 2023
Resolution: Recevied class report stating the following: crew cleaned oil separator ventilaiotn system, re-tightened bolts on the crankcase and replaced the oil. Upon completion of the repair the EDG was operationally tested and considered satisfactory.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 17 February 2023
No resolution recorded
15109- Maintenance of the ship and equipment- The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations. Deficiency 1-3 are direct effect on the lack of continuous maintenance, resulting in high risk of fire in engine room and other critical areas. Require external audit to ensure crew maintains engine room to reduce risks of fire as per SOLAS II-2.
-74 SOLAS (20) IX/5, ISM Code Part A reg 10
-16abc
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 March 2023 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 February 2023
Resolved
07199- Fire safety- Surfaces with temperatures above 220 degrees Celsius which may be impinged as a result of fuel system failure shall be properly insulated. PSCO observed oil soaked lagging made out of polypropylene rope wrapped around high temperature lines leading to the main engine.
-74SOLAS(04)II-2/4.2.2.6.1
-17ac
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 February 2023
Resolution: Recevied class report stating the following: improper lagging was removed. Fire retardent lagging materials were placed around ME return drain line, class allowed one month for original lagging material to be sourced and installed.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Reports of non-conf., accidents & hazardous occur.
Issued 17 February 2023
No resolution recorded
15108- Reports of non-conf., accidents & hazardous occur.- The Safety Management System should include procedures ensuring the non-conformities, accidents, and hazardous situations are reported to the company. PSCO discovered multiple systems in the engine room (tied to deficiency 1-3) that did not have requisition ordered or requisitions were over 3 months old and no critical parts delivered to ensure vessel and crew safety. require external audit to ensure crew report non-conformities in a timely manner to and company provide equipment and parts in a timely manner.
-74 SOLAS (20) IX/5, ISM Code Part A reg 9
-16abc
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 March 2023 — due date passed with no resolution recorded