Records from 2020 to 2024. Most recent: inspection, 8 August 2024.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 8 August 2024
Resolved
Firefighting systems and appliances shall be kept in good working order and readily available for immediate use. PSCO observed in the fire control room that the plastic box containing the CO2 pilot bottle was broken on the bottom.
74SOLAS(14)II-2/14.2.1.2
Condition: Damaged By Earlier Event
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 August 2024
Resolution: PSCO received email of proper repairs of the CO2 pilot bottle box. Deficiency rectified.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 8 August 2024
Resolved
The following functional requirements shall be met: the fire integrity of the divisions shall be maintained at all openings and penetrations. PSCO observed a fire door in the engine room failed to close properly.
74 SOLAS(14)II-2/45.5.5
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 August 2024
Resolution: PSCO received email of proper repairs of the fire door in the engine room. Deficiency rectified.
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 24 February 2023
Resolved
ALL STEERING COMPONENTS AND THE RUDDER STOCKSHALL BE OF SOUND AND RELIABLE CONSTRUCTION.PSCO OBSERVED HYDRAULIC PIPING FROM NO.1 STEERING PUMP TO STEERING GEAR VIBRATE EXCESSIVELY. SOLAS 74(20) II-1 REG 29.2.1 CODE 40ac
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 June 2024
Resolution: Received Class Report attesting to repairs.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 24 February 2023
Resolved
MEANS SHALL BE PROVIDED TO CONTROL LEAKS OF FLAMMABLE LIQUIDS. PSCO OBSERVED MULTIPLE FUEL INJECTORS ON M/E CYLINDERS LEAKING FUEL OIL. 74SOLAS(09) II-2 REG 4.1.1 CODE 40AC
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 June 2024
Resolution: Received Class Report attesting to repairs.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 24 February 2023
Resolved
ACCUMULATOR BATTERIES SHALL BE SUITABLY HOUSED AND COMPARTMENTS USED PRIMARILY FOR THEIR ACCOMODATION SHALL BE PROPERLY CONSTRUCTED AND EFFICIENTLY VENTILATED. PSCO OBSERVED BATTERIES HOUSED WITHOUT PROPER VENTILATION. 74SOLAS(20) II-1 REG 45.9.1 CODE 40ac
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 June 2024
Resolution: Received Class Report attesting to repairs.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 15 February 2023
Resolved
The maintenance plan shall include at least the following fire protection systems and fire-fighting systems and appliances, where installed: fire mains, fire pumps and hydrants. Vessel's maintenance plan did not address maintenance, testing, or inspection of the fire main or hydrants.
74SOLAS(04) II-2/14.2.2.3.1
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: PSCDO received and reviewed documents and accepted Class report attesting to addition of the aforementioned items into the maintenance plan.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 February 2023
Resolved
Oil fuel pipes, which, if damaged, would allow oil to escape ... from a tank ... shall be fitted with a cock or valve directly on the tank capable of being closed from a safe position outside of the space concealed.
Shut off valve on the emergency generator fuel tank did not close when operated remotely.
74 SOLAS (20) II-2/2.2.5.1, 17ac
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: received and reviewed class report, PSCO's verified operation of quick close valve
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 10 February 2023
Resolved
The following functional requirements shall be met: .1) means shall be provided to control leaks of flammable liquids.
Excessive oil leaks were observered on all four auxilliary generators and on oil piping throughout engine room.
74 SOLAS (20) II-1/4.1.1, 17ac
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: PSCDO received and reviewed documents and accepted Class report attesting to teh repairs of the sources of oil leaks.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 February 2023
Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Numerous flame detectors in the engine room were observed with oil and with material obscuring sensors.
74 SOLAS (20) II-2/14.2.1.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: received and reviewed class report, PSCO's verified flame detectors had been satisfactorily cleaned.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 February 2023
Resolved
The condition of the ship and its equipment shall be maintained to confrom with provision of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board.
The ship's boiler was observed with active steam and water leaks from ruptured piping. Also observed various alarms.
74 SOLAS (20) I/11(a), 17ac
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: Received condition of class giving vessel until May 023 to effect permanent repairs to boiler.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 10 February 2023
Resolved
Doors required to be self closing shall not be fitted with hold back hooks.
Several self closing fire doors in the engine room were observed to have hold backs without remote release.
74 SOLAS (20) II-2/4.2.1, 17ac
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: received and reviewed class report, PSCO's verified all holdbacks had been removed.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Reports of non-conf., accidents & hazardous occur.
Issued 10 February 2023
Resolved
The company and the ship shall comply with the requirements of the ISM Code. The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations and with any additional requirements which may be established by the company. Objective evidence collected by PSCOs throughout the course of both attendances (10FEB23/15FEB23) has called into question the adequacy/implementation of this vessel's SMS. This evidence includes excessive oil leaks throughout engine room, significant leaks on the fire main, leaking fire hose connections at fire stations, an inop fuel shut-off valve, lack of maintenance on fire detection systems, hold back hooks installed on self closing fire doors, boiler wastage & steam leaks, portable fire extinguishers w/o brackets, a wasted gasket on the sewage tank, inop emergency lighting, improper storage/excessive accumulation of chemical/oil containers. Additionally, crew painted over previously ID'ed soaked lagging rather than effect permanent repairs. based on the overall material condition of the vessel, as substantiated by the objective evidence cited above, an external audit is required.
74SOLAS(20) IX/3.1 ISM CODE 10.1
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 22 February 2023
Resolution: PSCDO received and reviewed Flag report, Chief of SSO accepted report as external ISM audit.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 10 February 2023
Resolved
Fire-fighting systems and appliances shall be kept in good working order. The fire main was gushing fire-fighting water from two separate expansion joints and flooding the surrounding space
74SOLAS(04) II-2/14.2.1.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 22 February 2023
Resolution: PSCDO received and reviewed Class report attesting to the repairs to the fire main.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 February 2023
Resolved
Where the contents and use of a space is such that there is doubt as to its classification for the purpose of this regulation, or where it is possible to assign two or more classifications to a space, it shall be treated as a space within the relevant category having the most stringent requirements. Containers of chemicals (some marked as corrosive or otherwise hazardous) and containers of various oils were stored inappropriately categories in numerous locations including in corridors directly adjacent to inadequately insulated steam piping.
74SOLAS(04) II-2/9.2.3.3.2.2
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: PSCDO received and reviewed documents and accepted Class report attesting to rectification of the deficiency
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 February 2023
Resolved
The boilers and associated piping systems and fittings shall be of design and construction adequate for the service for which they are intended and shall be so installed and protected as to reduce to a minimum any danger to persons on board, due regard being paid to... hot surfaces and other hazards. Steam lines in corridor were exposed without insulation presenting a hazard to persons onboard.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 February 2023
Resolution: PSCDO received and reviewed documents and accepted Class report attesting to rectification of the deficiency