Records from 2020 to 2025. Most recent: inspection, 11 April 2025.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boat inventory
Issued 9 April 2025
Resolved
Before the ships leaves port and at all times during the vouage, all life-saving appliances shall be in working order and ready for immediate use. PSCO observed rescue boat without any required equip-ment inside.
74 SOLAS 09 ed. III/20.2
10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 April 2025
Resolved 9 April 2025
Resolution: Crew replaced all rescue boat inventory.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 9 April 2025
Resolved
Rescue craft should be stowed in such a way that they are kept in a state of continuous readiness and can be launched within 5 min. PSCO observed rescue baot engine required troubleshooting to remove air from line and took more than 5 min to start.
74 SOLAS 09 ed. III/34
LSA Code 2.1.10.1
10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 April 2025
Resolved 9 April 2025
Resolution: Crew primed fuel line and engine started.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 9 April 2025
Resolved
Electrical installations shall be such that: the safety of passengers, crew and ship from electrical hazards will be ensured. Operating panels for the latch covers and winch in the bos'n stores were open and held in place using rope creating electrical hazards for crew.
74 SOLAS 09 ed. II-1/40.1.3
10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 April 2025
Resolved 9 April 2025
Resolution: Crew repaired the operating panels.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 9 April 2025
Resolved
Stairways and lift trunks which penetrate more than a single deck shall be surrounded by at least 'A-0' class divisions and be protected by self-closing doors at all levels. PSCO observed main stairway foor unable to fully close on its own.
74 SOLAS (2009 ed.) II-2/9.2.3.4.1
10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 April 2025
Resolved 9 April 2025
Resolution: Crew repaired door.
02 - Structural Conditions › N/A - No Subsystem › Openings to cargo area, doors, ... scuttles
Issued 19 October 2022
Resolved
THE MEANS FOR SECURING AND MAINTAINING WEATHERTIGHTNESS SHALL BE TO THE SATISFACTION OF THE ADMINISTRATION. THE ARRANGEMENTS SHALL ENSURE THAT THE TIGHTNESS CAN BE MAINTAINED IN ANY SEA CONDITIONS. PSCO OBSERVED CARGO HATCH SECURING CLEATS INABILITY TO FUNCTION AS INTENDED.
ICLL 66 REG 16(4)
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 11 April 2025
Resolution: Cargo hatch securing cleat was renewed and tested through hose test to the satisfaction of RO.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Cargo & other hatchways
Issued 19 October 2022
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 11 April 2025
Resolution: Hatch operation/maintanence manual is kept on board and checklist for hatch covers is maintained to satisfaction of RO.