Records from 2017 to 2019. Most recent: inspection, 14 November 2019.
Inspection history · 4
14 November 2019
COC-CHEM & TVE Renew · ISPS II Exam · Ballast Water Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6850474
28 November 2017
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6314400
7 June 2017
ISPS II Exam · Ballast Water Examination · COC-CHEM & TVE Renew
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6154370
6 June 2017
Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6167201
07 - Fire Safety › N/A - No Subsystem › Inert gas system
Issued 14 November 2019
Resolved
07102 - Inert Gas System - For tankers of 20,000 tonnes deadweight and upwards, the protection of the cargo tanks shall be achieved by a fixed inert gas system in accordance with the requirements of the Fire Safety Systems Code. PSCO observed Inert Gas Generator system inoperable. Complete repairs to class satisfaction prior to cargo operations.
SOLAS 74(a)2004 (cons) II-2/4.5.5.1.1 a
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 20 November 2019
Resolution: Received, reviewed and accepted class report from BV stating the deficiency was rectified. The limit flow switch for the cooling was stuck. Overhauled and tested. Test SAT.
08 - Alarms › N/A - No Subsystem › UMS - alarms
Issued 14 November 2019
Resolved
08108 - UMS Alarms - An alarm system shall be provided indicated any fault requiring attention and shall be capable of sounding an audible alarm in the main machinery control room or at the propulsion machinery control position and indicate visually each separate alarm function at a suitable position. PSCO observed multiple visual and audible alarms not working properly throughout the engine room.
SOLAS 74(a) 2004 (cons) II-1/51.1.1 16ac
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 November 2019
Resolved 20 November 2019
Resolution: Received, reviewed and accepted class report fro BV stating the deficiency was rectified. The alram panal had a blown fuse. It was changed and tested. Test SAT.
Lifesaving › Lifeboat Equipment › Food Ration
Issued 7 June 2017
Resolved
Survival Craft shall be stowed fully equipped as required by this chapter and the code. 15 out of 26 food rations were found to have lost vacuum seal.
74 Solas (2014 Cons.) III/ 13.1.4
LSA Code IV 4.4.8.12
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 9 June 2017
Resolution: Received Class Survey resolving deficiency.
Deck/Cargo › Inert Gas System › Inert Gas Generator (IGG)
Issued 7 June 2017
Resolved
The protection of the cargo tanks shall be achieved by a fixed inert gas system in accordance with the requirements of the FSS Code. Installed nitrogen system currently inoperable and installed IGG unable to have calibration and operation demonstrated by the crew.
74 Solas (04 Cons.) II-2/ 5.5
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 9 June 2017
Resolution: Received Class Survey resolving deficiency.
Documentation › Logs/Records › Cargo Record Book (NLS)
Issued 7 June 2017
Resolved
After completion of any operation specified in Appendix II to the Annex, the operation shall be promtly recorded in the Cargo Record Book. Missing entry for the last cargo load of Methyl Tert-Butyl Ether at Odfjell Terminal, Rotterdam on 26 April 2017.
Marpol Annex II/ Reg 15.2
Condition: Improper/Lack of Maintenance
Action required: 15 - Rectify deficiencies by next port
Resolved 9 June 2017
Resolution: Received Class Survey resolving deficiency.
Documentation › Certificates/Documents › IOPP Certificate
Issued 7 June 2017
Resolved
The IOPP Certificate shall be drawn up in the form corresponding to the model given in Appendix II. Maximum throughput of the Oily Water Separator is not entered on the Form B.
Marpol Annex I/ Reg 9
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 7 July 2017
Resolved 9 June 2017
Resolution: Received Class Survey resolving deficiency.