MISS VIRGINIA

Built
1971
Last inspected
13 November 2025
Documentation
Valid · NVDC file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 13 November 2025
Operational controls None recorded without a removal date
Years with a record 10 calendar years (2016–2025)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDF2104
111508
Flag
UNITED STATES
Maury page id
psix-111508

Documentation record

Registered dimensions (L × B × D)49.9 ft × 16.4 ft × 5.2 ft
Registered tonnagegross 51 / net 34
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderCLEARWATER BAY MARINE WAY · CLEARWATER, FL, UNITED STATES · built 1971
Hull materialWood
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portTARPON SPRINGS, FL
Endorsements, as the file codes themcw_un, fi
DocumentationValid · issued 2 June 2026 · expires 30 June 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it51 - Regulatory (Subpart C or D), Gross Ton
34 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel

Behind this panel: 17 inspections, each with its date, unit and type; 38 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; no tow-unit appearances recorded; no other recorded names; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 17

13 November 2025 Administrative Inspection · Deficiency Check · COI Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8228037
1 May 2025 Hull Examination · Internal Structural Exam · Deficiency Check
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8082203
6 January 2025 Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8058614
9 February 2024 Annual Inspection · Deficiency Check
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7856172
2 May 2023 Deficiency Check · Examination of Repairs · Internal Structural Exam · Hull Examination
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7644995
8 February 2023 Deficiency Check · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7622577
15 July 2022 In-Service Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7457990
2 February 2022 Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7384295
12 May 2021 Deficiency Check · In-Service Inspection · Drydock Exam · Internal Structural Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7184141
5 November 2020 In-Service Inspection · Deficiency Check · COI Inspection · Plan Review "T" Boat
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7078479
14 November 2019 Administrative Inspection · Drydock Exam · Internal Structural Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6853597
17 October 2019 In-Service Inspection · Administrative Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6835689
2 October 2018 Deficiency Check · Annual Inspection · DAPI Audit · Administrative Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6517814
1 May 2018 Internal Structural Exam · Drydock Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6386057
7 November 2017 Annual Inspection · DAPI Audit
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6303258
21 November 2016 Deficiency Check · DAPI Audit · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6028480
26 April 2016 Drydock Exam · Internal Structural Exam · Deficiency Check
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 5858414

Deficiency record · 38

11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for rescue boats
Issued 13 November 2025 Resolved
Each item of survival craft equipment must be stored in a way that does not interfere with launching. Life floats tethered together using improperly sized line. Tether must be replaced utilizing a length of line that will reach the waterline from the stowage position.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 November 2025
Resolved 13 November 2025
Resolution: Operator provided pictures indicating the corrected length of line and life floats individually tethered.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 13 November 2025 Resolved
Rotating machinery must be properly protected by a cover, guard, or rail. Both main engines must have the belt guards installed to the satisfaction of the MI. 46 CFR 177.960
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 November 2025
Resolved 13 November 2025
Resolution: Operator replaced machinery guards and provided photos.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 6 February 2025 Resolved
The intent of this part is to insure that all machinery be installed and maintained in such a manner as to afford adequate protection against fire, explosion, machinery failure and personnel injury. MI observed missing insulation/lagging from the port side main engine turbo. Repair to satisfaction of CG inspectors. 46 CFR 182.01-5(a) 701c
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 6 February 2025
Resolution: Received picture of new lagging installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 6 February 2025 Resolved
All vessels except non-self-propelled vessels shall be provided with suitable steering apparatus. MI observed leaking hydraulic lines connected to main steering ram. Repair to satisfaction of CG inspectors. 46 CFR 182.30-1(a) 701c
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 6 February 2025
Resolution: Received picture fittings being tightened.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 6 February 2025 Resolved
The intent of this part is to insure that all machinery be installed and maintained in such a manner as to afford adequate protection against fire, explosion, machinery failure and personnel injury. MI observed missing double hose clamps on nonmetallic fuel lines connected to main engines and generator. Repair to satisfaction of CG inspectors. 46 CFR 182.01-5(a) 701c
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 6 February 2025
Resolution: Received pictures of all fuel hose having double hose clamps on each end.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 6 February 2025 Resolved
46 CFR 181.420(a)(3) A pre-engineered fixed gas fire extinguishing system must automatically shut down all power ventilation systems and all engines that draw intake air from within the protected space. Installed system does not shutdown generator. Repair to satisfaction of CG inspectors. CODE 705: Vessel is restricted from operating the generator while passengers are on board.
Action required: 705 - Other - as specified
Resolved 6 February 2025
Resolution: Received video of system shutting down the generator.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 6 February 2025 Resolved
46 CFR 182.01-5 "Old T" All machinery be installed and maintained in such a manner as to afford adequate protection against fire, explosion, machinery failure and personnel injury. MI observed deteriorated generator fuel supply line. Repair to the satisfaction of CG inspectors. CODE 705: Generator can't be operated until fuel line is replaced.
Action required: 705 - Other - as specified
Resolved 6 February 2025
Resolution: Received picture of new fuel line.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 6 February 2025 Resolved
46 CFR 182.01-5(a) "Old T" The intent of this part is to insure that all machinery be installed and maintained in such a manner as to afford adequate protection against personnel injury. MI observed missing belt guards covering rotating machinery on port and stbd main engines. Repair to satisfaction of CG inspectors. CODE 705: Make repairs within 7 days of inspection (NLT 13FEB2025).
Action required: 705 - Other - as specified
Due 13 February 2025
Resolved 6 February 2025
Resolution: Received picture of guards installed.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 6 February 2025 Resolved
46 CFR 176.810(b)(1)(iv) The required fire extinguisher maintenance shall be logged. Monthly maintenance was being performed. Update maintenance logs to the satisfaction of CG inspectors.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 February 2025
Resolved 20 February 2025
Resolution: Monthly maintenance log established and updated.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 6 February 2025 Resolved
46 CFR 185.364 On vessels described by 46 CFR 175.110(c), flammable items not otherwise covered by the regulations of this subchapter, such as rechargeable batteries, including lithium ion batteries utilized for commercial purposes, must be handled, stored, and operated in a way that mitigates the risk of hazardous conditions. MI observed lack of crew and passenger instruction for the handling, storage, and operation of rechargeable batteries contained in cell phones.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 February 2025
Resolved 20 February 2025
Resolution: Safety brief restricts crew/passenger use of one plug and one outlet while onboard. CAPT says vessel only has one outlet.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Sewage discharge connection
Issued 6 February 2025 Resolved
33 CFR 159.7 (C) When operating a vessel on a body of water where the discharge of untreated sewage is prohibited by the Environmental Protection Agency under 40 CFR 140.3, the operator must secure each Type III device in a manner which prevents discharge of sewage. MI observed sewage overboard valves in the open position.
Action required: 10 - Deficiency Rectified
Resolved 6 February 2025
Resolution: Valves were secured.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 9 February 2024 Resolved
A vessel must carry one floating waterlight, unless it is limited to daytime operation, in which case no floating waterlight is required. Floating waterlight is inoperative. Repair or replace light. Operations restricted to daylight only. 46 CFR 180.70(d)(1)
Action required: 705 - Other - as specified
Due 9 February 2024
Resolved 23 February 2024
Resolution: Light replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 9 February 2024 Resolved
Each ring life buoy with a floating waterlight must have a lanyard of at least 910 millimeters (3 feet) in length, but not more than 1,830 millimeters (6 feet), securing the waterlight around the body of the ring life buoy. Floating waterlight lanyard is not at least 3 feet in length. 46 CFR 180.70(d)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: Lanyard at approved length.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 9 February 2024 Resolved
On a vessel carrying only one ring buoy, the floating waterlight must be attached to the lanyard with a corrosion-resistant clip. The clip must have a strength of at least 22.7 kilograms (50 pounds), and allow the waterlight to be quickly disconnected from the ring life buoy. Clip found to be deteriorated. 46 CFR 180.70(d)(3)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: Clip attached to lanyard.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 9 February 2024 Resolved
Machinery and equipment installed on each vessel must be suitable for the vessel and its operation and for the purpose intended. All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from causing fire, explosion, machinery failure, and personnel injury. Forward emergency fuel shut-off valve's packing is no longer sufficient to ensure no fuel leaks out of the valve stem. Valve to be repacked or replaced. 46 CFR 182.100
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: Valve re-sealed.
09 - Working and Living Conditions › 092 - Working Conditions › Guards - fencing around dangerous machinery parts
Issued 9 February 2024 Resolved
An exposed hazard, such as gears or rotating machinery, must be properly protected by a cover, guard, or rail. Both main diesel engine accessory drive and belts do not have guards around them. Install guards around belts. 46 CFR 177.960
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: Guards installed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 9 February 2024 Resolved
Each battery must be located as high above the bilge as practicable, secured to protect against shifting with the roll and pitch of the vessel, and free from exposure to water splash or spray. Generator battery found to be unsecured and not covered. Battery to be firmly secured and covered to prevent water splash. 46 CFR 183.350(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: Battery placed in battery box and secured.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 9 February 2024 Resolved
First aid kit is expired. Replace first aid kit with an approved type kit. 46 CFR 160.041
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: First aid kit replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 9 February 2024 Resolved
Each life jacket carried on a vessel on a oceans route must have a life jacket light. 11 adult life jackets lights found inoperable. 46 CFR 180.75
Action required: 10 - Deficiency Rectified
Due 9 February 2024
Resolved 9 February 2024
Resolution: Lights replaced on the spot.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 9 February 2024 Resolved
The Certificate of Inspection and any SOLAS Certificates must be posted under glass or other suitable transparent material, such that all pages are visible, in a conspicuous place on the vessel where observation by passengers is likely. If posting is impracticable, such as in an open boat, the certificates must be kept on board in a weathertight container readily available for use by the crew and display to passengers and others on request. COI not posted; post COI as indicated above. 46 CFR 176.302
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: COI posted.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 9 February 2024 Resolved
When, in accordance with § 178.210 of this chapter, a vessel must be provided with a stability letter, the stability letter must be posted under glass or other suitable transparent material, such that all pages are visible, at the operating station of the vessel. If posting is impracticable, the stability letter must be kept on board in a weathertight container readily available for use by the crew and display to passengers and others on request. Stability letter not posted; post stability letter as indicated above. 46 CFR 176.306
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 February 2024
Resolved 23 February 2024
Resolution: Stability letter posted.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 8 February 2023 Resolved
Each life preserver carried on a vessel engaged in ocean, coastwise, or Great Lakes service after June 30, 1980, must have a personal flotation device light that is approved under subpart 161.012 of this chapter. MI observed 05 child life preservers were outfitted with inoperable lights. Vessel route is restricted to limited coastwise. 46 CFR 180.25-20
Action required: 705 - Other - as specified
Due 8 February 2023
Resolved 14 February 2023
Resolution: Purchased 6 new chemical lights.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 8 February 2023 Resolved
The marine employer must have a sufficient number of alcohol testing devices readily accessible on board the vessel to determine the presence of alcohol in the system of each individual who was directly involved in the SMI. MI observed vessel was only outfitted with 02 alcohol testing devices. When underway for overnight voyages, vessel sails with 04 crewmembers. Vessel route is restricted to limited coastwise. 46 CFR 4.06-15(a)(1)
Action required: 705 - Other - as specified
Due 8 February 2023
Resolved 3 March 2023
Resolution: New drug/alcohol test kits received onboard.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 8 February 2023 Resolved
The marine employer must have a sufficient number of urine-specimen collection and shipping kits meeting the requirements of 49 CFR Part 40 that are readily accessible for use following SMIs. MI observed no acceptable urine-specimen collection and shipping kits onboard. Vessel route is restricted to limited coastwise. 46 CFR 4.06-15(b)(1)
Action required: 705 - Other - as specified
Due 8 February 2023
Resolved 3 March 2023
Resolution: New drug/alcohol test kits received onboard.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 8 February 2023 Resolved
All vessels shall be provided with bilge pumps in accordance with Table 182.25-10(a). Per the table, vessel is required to have 1 fixed power pump and 1 portable hand pump. MI observed that vessel did not have a portable hand pump onboard. Rectify within 7 days. 46 CFR 182.25-10(a)
Action required: 705 - Other - as specified
Due 15 February 2023
Resolved 14 February 2023
Resolution: New portable bilge pump placed onboard.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 8 February 2023 Resolved
Each survival craft on a vessel must be in good working order and ready for immediate use before the vessel leaves port and at all times when the vessel is underway. MI observed strength and general condition of painter for life floats was significantly deteriorated due to exposure. 46 CFR 185.700(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2023
Resolved 2 March 2023
Resolution: New painter installed.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 8 February 2023 Resolved
Paddles shall be lashed on the sides of the life floats to which they belong. MI observed paddles were not secured to life floats. 46 CFR 180.15-10
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2023
Resolved 2 March 2023
Resolution: Paddles lashed to life floats.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 8 February 2023 Resolved
An EAP training program must be conducted for the employer's crewmembers and supervisory personnel. MI observed that EAP training had not been conducted for any of the crewmembers. 46 CFR 16.401(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2023
Resolved 1 March 2023
Resolution: Training was conducted for all crewmembers.
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 8 February 2023 Resolved
The master of the vessel shall ensure that: Each EPIRB...must be tested monthly, using the integrated test circuit and output indicator, to determine that it is operative. MI observed that log entries did not indicate EPIRB testing monthly and vessel rep confirmed testing was not completed on a monthly basis. 46 CFR 185.728(a)
Action required: 10 - Deficiency Rectified
Due 8 February 2023
Resolved 8 February 2023
Resolution: EPIRB tested sat during inspection and was properly logged. Educated master on testing/logging requirements.
09 - Working and Living Conditions › 091 - Living Conditions › Berth dimensions, etc.
Issued 17 October 2019 Resolved
Vessel is restricted from carrying overnight passengers until plans from owner are approved and completed repairs and maintenance are inspected by an attending marine inspector. Cited under 46 CFR 177.202 Plans and information required / 46 CFR 177.810 Overnight accommodations.
Action required: 705 - Other - as specified
Resolved 20 February 2020
Resolution: Deactivated COI.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 2 October 2018 Resolved
Vessel must be in compliance with this subpart. Wood keel forward of fuel tank has considerable rot. Renew wasted and rotted material. - 46CFR176.25-1
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 October 2018
Resolved 17 October 2018
Resolution: Owner/operator scarfed out 1'x6" section of rotted wood in the affected area. Repaired section with wood and epoxy.
11 - Life Saving Appliances › N/A - No Subsystem › Buoyant apparatus
Issued 2 October 2018 Resolved
Each Buoyant Apparatus must be fitted with a life line. Life line on buoyant apparatus wasted. Replace life line. - 46CFR180.175(e)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 October 2018
Resolved 17 October 2018
Resolution: Life line's were repaired and reinspected by MI.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Windows, sidescuttles and deadlights
Issued 2 October 2018 Resolved
Each port light with sill located below margin line must have hinged, inside dead cover. Port side missing cover and bolts. Replace dead cover and bolts. - 46CFR171.117
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 October 2018
Resolved 17 October 2018
Resolution: Bolts were replaced and MI witnessed presence of all dead covers.
Construction/Loadline › Hull › Keel
Issued 1 May 2018 Resolved
0983 - Proposed alterations shall be approved by the OCMI before work is started. Submit a repair proposal for the rotted section of wood on the aft keel. - 46CFR176.20-1(b)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 May 2018
Resolution: Repaired IAW with approved repair proposal.
Communications › Radio Communications › VHF Radiotelephone
Issued 21 November 2016 Resolved
Place MMSI in VHF-DSC Radio and ensure GPS is also hooked into the VHF-DSC Radio and have FCC Certified Tech verify proper instalation.
Action required: 705 - Other - as specified
Due 5 December 2016
Resolved 22 December 2016
Resolution: Vessel rep shown proof of placed MMSI in VHF-DSC Radio and GPS is also hooked into the VHF-DSC Radio and a FCC Certified Tech verified proper installation.
Engineering › Steering Gear System › Bracket/Clamp
Issued 26 April 2016 Resolved
Repair flexible clamps on port and starboard stuffing boxes.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 April 2016
Resolution: Flexible clamps present on port and starboard stuffing boxes.
Electrical › Electric Generation Source (service) › Ground Indicator
Issued 26 April 2016 Resolved
Replace Transducer mounts on port side.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 April 2016
Resolution: New transducer mounts present on port side.
Construction/Loadline › Hull › Hull Plating
Issued 26 April 2016 Resolved
Repair port side splash rail to satisfaction of Marine Inspector.
Action required: 705 - Other - as specified
Resolved 29 April 2016
Resolution: Port side splash rail inspected and repaired to satisfaction of Marine Inspector.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.