MAURY USCG vessel records Sign in
← All vessels

CSC CYANITE

CSC CYANITE is a 2009 tank ship. The Coast Guard has recorded 3 inspections since 2011, most recently in May 2016, along with 3 deficiencies and 1 operational control.

Records from 2011 to 2016. Most recent: inspection, 4 May 2016.

Built
2009
Last inspected
4 May 2016
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

9483736 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
1155654
Flag
HONG KONG
—
Maury page id
psix-1155654

Inspections, by type

…with no type recorded1
Years with a record 2 calendar years (2011–2016)
The 3 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

This record may be incomplete: the most recent inspection recorded for this vessel was 10 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 1980.

Documentation record

Tonnage as PSIX records it49982 - Dead Weight, Ton
31534 - Convention (Subpart B), Gross Ton
13395 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.

Inspection history · 3

4 May 2016 Deficiency Check
Physical examination · U.S. COAST GUARD FORCES MICRONESIA/SECTOR GUAM · USCG Oceania District (CGD-O) · Activity 5868623
8 April 2016 ISPS II Exam · COC-TVE Renew · Ballast Water Examination
Physical examination · U.S. COAST GUARD FORCES MICRONESIA/SECTOR GUAM · USCG Oceania District (CGD-O) · Activity 5846483
29 September 2011 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 4157544

Deficiency record · 3

Deck/Cargo › Inert Gas System › Gas Regulating Valve
Issued 8 April 2016 Resolved
The IGS System shall be designed, constructed, and tested to the satisfaction of administration. Suitable means shall be provided for the zero and span calibration of 2.4.2.1 Fixed IGS gas analyzer. Ship could not provide technical drawing of IGS analyzer. PSC Officer undable to verify that IGS oxygen analyzer was installed IAW manufacturer guidelines. 74 SOLAS (04) II-2/4.5.5.3.2 FSS 15.2.1.2
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 8 May 2016
Resolved 4 May 2016
Resolution: Vessel provided proof that vessel has necessary plans and guidelines.
Electrical › Lighting (service) › Lighting Fixture
Issued 8 April 2016 Resolved
Electrical equipment of a type which will not ignite flammable mixtures on board tankers shall be installed in a spae where flammable mixtures are libale to collect. Light fixtures within the deck storage locker missing a cap fixture, light is no longer explosion proof. 74SOLAS(04)II-1/45.10 Rectify deficiency within 30 days.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 8 May 2016
Resolved 4 May 2016
Resolution: Vessel provided class approval of installation of correct light fixture.
Accommodation/Occupational Safety › Occupational Safety › Rubbish/Waste Materials
Issued 8 April 2016 Resolved
Batteries shall be suitably housed and compartments used for their accomodation shall be properly constructed and efficiently ventilated. PSC Officers discovered batteries being stored improperly in a poorly ventilated compartment. 74 SOLAS (04) II-1/45.4.2
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 8 April 2016
Resolved 8 April 2016
Resolution: Vessel's crew moved batteries to appropriate storage.