Records in 2020. Most recent: inspection, 23 August 2020.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 23 August 2020
Resolved
Fire protection systems and fire fighting systems and appliances shall be maintained and ready for use. (74 SOLAS (14) II-2/14.1.1)
During fire hose test, a varying type nozzle was stuck on straight stream. During deck walk, found 03 additional nozzles siezed, not alloing for varying function.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 August 2020
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of Lifeboats
Issued 23 August 2020
Resolved
All life saving appliances and arrangements shall comply with the applicable requirements of the code. (74 SOLAS (14) III/34)
During lifeboat inspection, found over 12 food rations open or not properly sealed in accordance with LSA 4.4.1.12.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 August 2020
09 - Working and Living Conditions › 092 - Working Conditions › Steam pipes and pressure pipes
Issued 23 August 2020
Resolved
The machinery, boilers, and other pressure vesssels, associated piping systems and fittings, shall be of a design and construction adequate for the service for which they are intended. (74 SOLAS (14) II-2/26.1)
During engine room inspection, found steam leak near Number 3 generators and oil accumulation under Number 4 generator and under aft section of main engine.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 August 2020
14 - Pollution Prevention › 145 - MARPOL Annex V › Garbage
Issued 23 August 2020
Resolved
Every ship of 100 gross tonnage and aboce shall carry a garbage management plan, which the crew shall follow. (MARPOL ANNEX V/10.2)
Found excessive accumulation of trash at receptacle stations on deck.
Action required: 10 - Deficiency Rectified
Resolved 23 August 2020
Resolution: Vessels captain showed exam crew documents and verification of trash services being ordered. Arrival for trash services was 1900 aug 23rd
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 23 August 2020
Resolved
The machinery, boilers, and other perssure vessel associated poping systems and fitting shall be of a dsign and construction adequate for the service for which they are intended. (74 SOLAS (14) II-2/26.1)
During emergency steering test, found accumulation of hydraulic fluid on top and around the emergency steering gear.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 23 August 2020
Resolution: Vessels crew cleaned all oil accumlated under steering gear system. No further leaks detected.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Company verification, review and evaluation
Issued 23 August 2020
Resolved
The company and the ship shall comply with the requirements of the international safety management code. The requirements of this code shall be treated as mandatory. (74 SOLAS (14) IX/3.1)
Verify compliance of the ship's safety management system with regard to lifesaving, firefighting, and engine room maintainence and procedures for nonconformities.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 August 2020
09 - Working and Living Conditions › 091 - Living Conditions › Sanitary Facilities
Issued 23 August 2020
Resolved
There is reasonable cause to believe this vessel does not comply with any regulation listed under this chapter or any other applicable law or treaty. (33 USC 1223(b)1)
Head on stern of the vessel (S.05) has substantial amount of water on the deck, potential mold throughout the space.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 August 2020