Records from 2017 to 2019. Most recent: inspection, 16 October 2019.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 15 October 2019
Resolved
Fire Protection systems and fire-fighting systems and appliances shall be maintained ready for use. Observed safety pins inserted into 02 high pressure CO2 bottles preventing the required amount of CO2 to be discharged into the protected spaces during an emergency. Additionally, several valves in the vicinity of the air vents were rusted out. 74 SOLAS(09) II-2/14.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 October 2019
Resolved 19 October 2019
Resolution: Received, reviewed, and accepted ABS class report attesting all safety pins were removed and valves were cleaned.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 15 October 2019
Resolved
Emergency Generator shall be capable of being automatically started and supplying the required load as quickly as is safe and practicable subject to a maximum of 45s. Primary source of power unable to start emergency generator. 74 SOLAS(14) II-1/43.3.1.3
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 October 2019
Resolved 19 October 2019
Resolution: Received, reviewed, and accepted ABS class report attesting to the proper operation of the emergency generator.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 15 October 2019
Resolved
Means shall be provided to control leaks of flammable liquid. Observed excessive leaks from booster pump and secondary fuel oil filter in the purifier room. 74 SOLAS(09) II-2/4.1.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 October 2019
Resolved 19 October 2019
Resolution: Received, reviewed, and accepted ABS class report attesting that leaks in the purifier room had been rectified.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 15 October 2019
Resolved
In a ship in which fuel oil is used, the arrangements for storage, distribution, and utilization of oil fuel shall be such to ensure the safety of the ship. All three ships service diesel generators are leaking fuel and were found with disconnected oil leak alarms. 74 SOLAS(09) II-2/4.2.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 October 2019
Resolved 19 October 2019
Resolution: Received, reviewed, and accepted ABS class reporting stating leaks were resolved and leak alarms were reconnected.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 15 October 2019
Resolved
All life saving appliances shall be in working order and ready for immediate use. Observed 04 self igniting lights for life buoys inoperable. 74 SOLAS(14) III/20.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 October 2019
Resolved 19 October 2019
Resolution: Received, reviewed, and accepted ABS class report stating vessel received new self-igniting lights.