Records from 2016 to 2019. Most recent: inspection, 16 June 2019.
04 - Emergency Systems › N/A - No Subsystem › Functionality of Safety Systems
Issued 16 June 2019
Resolved
The EEP must be submitted to the OCMI having jurisdiction over the facility in operation. The current EEP was submitted 29MAY2019 and vessel began operations on 13JUN20-19. Vessel must provide an approved EEP.
33CFR 146.140(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 July 2019
Resolved 16 July 2019
Resolution: (Cleared by correspondence from OIM) EEP Provided as well as Operator being contacted about early submission in the future.
04 - Emergency Systems › N/A - No Subsystem › Water level indicator
Issued 16 June 2019
Resolved
Propulsion rooms and pump rooms in lower hulls should be provided with two independent systems for high bilge water detection. Bilge alarm in the mud room is inoperable. Repair and verify operation of all bilge alarms.
89 MODU Code 4.8.8.3
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 July 2019
Resolved 16 July 2019
Resolution: (Cleared by correspondence from OIM) Please see attached evidence to clear deficiency 02. Attachment: Mud pump room bilge alarm repaired and verified. Attachment: Verified operation of all bilge alarms.
12 - Dangerous Goods › N/A - No Subsystem › Instrumentation
Issued 16 June 2019
Resolved
At least two portable gas monitoring devices should be provided, each capable of accurately measuring a concentration of flammable gas. Provided gas calibration bottles were expired. Replace expired calibration gas.
89 MODU Code 9.8.2
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 July 2019
Resolved 16 July 2019
Resolution: (Cleared by correspondence from OIM) Please see the attached is photos of the new test gas bottle installed in the gas meter test rack for Deficiency # 3 with an expiration date of Dec 2019. We have also ordered new gas as well.
01 - Certificates & Documentation › 013 - Documents › Energy Efficiency Design Index File
Issued 16 June 2019
Resolved
Every marine diesel engine shall be provided with a technical file and shall contain the information in 2.4.1 of NOx Code. The current technical files do not contain the items required in 2.4.1.7. The parts change out list was not in a hard copy and the electronic file was corrupted and could not be opened.
MARPOL Annex VI
NOx Code 2.4.1.7, 6.2.2.7
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 July 2019
Resolved 16 July 2019
Resolution: (Cleared by correspondence from OIM) The EIAPP log was recovered and is attached.
The Chief has printed off each engine log and has placed hard copies in the engine technical manuals and they will be updated as needed moving forward.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 16 June 2019
Resolved
Provisions should be made such that the unit can comply with the pollution prevention requirements of international conventions in force. The piping on the starboard OWS was cracked and leaking, making the OWS inoperable.
89 MODU Code 14.3
MARPOL Annex I
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 July 2019
Resolved 16 July 2019
Resolution: Cleared onboard although deficient when originally inspected.
Lifesaving › Lifeboat › Fire Protection (water spray system)
Issued 18 September 2017
Resolved
#4 L/B was missing sprinkler pump.
Action required: 66 - Prior to drilling or production operations
Resolved 26 September 2017
Resolution: Recieved email notification from OIM stating that def has been corrected.
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 18 September 2017
Resolved
There was an insufficient number of lifejackets readily available for persons on duty.
Action required: 66 - Prior to drilling or production operations
Resolved 26 September 2017
Resolution: REcieved email from OIM stating that they have installed lifejacket in all the 3rd party building, cranes and on the drill
floor. We have an order in to provide 100% capacity at all 4 life boats that should arrive
the first week of October.
Fire Fighting › Structural Fire Protection - General › Deckhouse Construction
Issued 18 September 2017
Resolved
Multiple fire doors throughout the rig have structural issues jeopardizing their A class fire boundary.
Action required: 705 - Other - as specified
Due 18 October 2017
Resolved 26 September 2017
Resolution: Recieved Email from OIM that fire doors will arrive on rig on 09/26/2017 and be ready for install.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 18 September 2017
Resolved
Multiple battery ballasts were in the red.
Action required: 705 - Other - as specified
Due 18 October 2017
Resolved 26 September 2017
Resolution: They have changed out 30 batteries in the emergency lights last week and have a
hotshot in for 200 more batteries along with 40 complete 4’ emg lights and 10 complete 2’ emg
light. This will complete the lighting survey that we did onboard for closure.
Lifesaving › Buoyant Apparatus › Painter
Issued 18 September 2017
Resolved
Lines on ring buoys are dry rotted.
Action required: 705 - Other - as specified
Due 2 October 2017
Resolved 20 September 2017
Resolution: Recieved email from OIM stating that def has been rectified.
Accommodation/Occupational Safety › Occupational Safety › Welding/Hot Work
Issued 18 September 2017
Resolved
Welding/grinding shack did not have eye wash station nearby.
Action required: 705 - Other - as specified
Due 18 October 2017
Resolved 20 September 2017
Resolution: Recieved email from OIM stating Eyewash has been placed in various locations.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 14 March 2016
Resolved
Port Forward Tank Top Stair Tower Door doesn't self close, repair door to self closing.
Condition: Improper/Lack of Maintenance
Due 14 April 2016
Resolved 15 March 2016
Resolution: [name withheld] from West Capricorn sent in a video showing the fire door self closing as required.