Records from 2012 to 2017. Most recent: inspection, 5 September 2017.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Inspection history · 8
5 September 2017
COC-MODU Renew
Type not classified · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6259881
11 April 2016
COC-MODU Renew
Type not classified · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 5851466
28 March 2016
Type not recorded
No type recorded · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 5843121
19 December 2015
In-Service Inspection
Physical examination · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 5784883
20 November 2015
Type not recorded
No type recorded · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 5769508
8 August 2014
Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4948429
26 March 2014
Administrative Inspection · Deficiency Check · ISPS III Exam · COC-MODU Renew
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4823381
9 July 2012
Deficiency Check
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4373627
Fire Fighting › Structural Fire Protection - General › Hull Construction
Issued 12 August 2014
Resolved
Class surveyor to review the type approvals, installation & repair procedures & ensure that all MCT's that have been disturbed since new construction/vessel delivery have been restored per manufacturer's instructions & type approvals to maintain the appropriate boundary integrity. Class Report documenting the findings & any necessary corrections to be provided. 89 MODU 3.6.1 & 9.1.3. Action 50a,c.
Action required: 705 - Other - as specified
Due 12 September 2015
Resolved 29 August 2015
Resolution: Class review/inspection completed with report provided.
Engineering › Bilge Water Management System › Valve
Issued 24 April 2014
Resolved
Installed emergency bilge suction valves in all three of the lower machinery spaces were found to be in an inoperable condition. Conduct maintenance on all emergency bilge valves and prove proper operation of the same. Put preventive maintenance procedures in place to ensure that these valves are maintained in an operable condition at all times. Cite 88 SOLAS 1/11(a). Action 40a,b,c.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2014
Resolved 9 May 2014
Resolution: Received an email from [name withheld] attesting that all valves are now working properly and a weekly PM has been created to function all of these valves.
Engineering › Fuel Oil Storage/Transfer System › Filter/Strainer
Issued 24 April 2014
Resolved
Fuel leaks were present and the fuel strainer selector valve and the relief valve housing in the Port Purifier Room. Correct both leaks. Cite 89 MODU 4.7.4. Action 40a,c.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2014
Resolved 29 April 2014
Resolution: Received an email from [name withheld] on 04/29/14 attesting that the O-Ring on the strainer basket was changed out and the relief valve leak was repaired.
Electrical › Electric Generation Source (service) › Power Requirement
Issued 24 April 2014
Resolved
EDG had insufficient capacity to power the radiator/exhaust vent closures and exhibited an alarm condition on the control panel while operating with the battery charger isolated for hydraulic/back-up starting system. Prove that the batteries are in serviceable condition with adequate run time with the battery charger input secured IAW operating procedures. Cite 89 MODU 5.4.3. Action 16a,b,c.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 8 May 2014
Resolved 9 May 2014
Resolution: Received an email from [name withheld] on 05/09/14 attesting that E-Gen batteries were replaced and system is operating as designed.
Engineering › Fuel Oil Service System › Tank
Issued 24 April 2014
Resolved
EDG fuel day tank had insufficient fuel contained within the tank to sustain 18-hour minimum run time IAW minimum quantity placard posted on the day tank. Fill tank and ensure that the proper fuel level is maintained at all times. Cite 89 MODU 5.3.6. Action 40a,b,c.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2014
Resolved 29 April 2014
Resolution: Received an email from [name withheld] on 04/29/14 attesting that the day tank was filled to the required level.
Engineering › Diesel Engine (auxiliary) › Emergency shutdown
Issued 24 April 2014
Resolved
Tested EDG Low Oil Pressure Shut-Down but was unable to verify the actual set-point of the switch (actual pressure at which the engine is triggered to shut-down). The shut-down also exhibited sporadic results during testing. Provide equipment/arrangement for proper testing. Prove operation and set-point of the Low Oil Pressure shut-down. Cite 89 MODU 4.2.7, 81 SOLAS II-1/27.5. Action 16a,c.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 8 May 2014
Resolved 9 May 2014
Resolution: Received an email from [name withheld] attesting that an improper test proceedure was performed during the inspection. The correct test proceedure provides the needed information requested and the engine trips at 40 PSI.
Engineering › Diesel Engine (propulsion-electric) › Emergency shutdown
Issued 24 April 2014
Resolved
Proper test arrangement or procedure was not available to prove proper operation of the Oil Mist Detectors (OMD's) on the Main Diesel Generators. Provide test equipment/procedure and prove full functionality of the installed OMD's. Cite 89 MODU 8.3.7, 81 SOLAS II-1/47.2, IMO MSC.1/Circ. 1345. Action 50a,b,c.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 May 2014
Resolved 18 June 2014
Resolution: Proper test equipment has been ordered/received and OMD''''''''''''''''s tested.
Electrical › Electrical Distribution System (service) › Wiring
Issued 24 April 2014
Resolved
Temporary power cords were found to be tapped into the ECR console for the speed log computer in the ECR. Extension cords for permanent equipment present both electrical and personnel (trip) hazards. Install permanent power supply for this system and ensure that the ECR console access panels are properly sealed. Cite 89 MODU 5.1.1.1.3. Action 50a,b,c.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 24 May 2014
Resolved 29 April 2014
Resolution: Received an email from [name withheld] on 04/29/14 attesting that electricians ran permanent power supply and video feed for this computer and all temp cords were removed.
Engineering › Steam Boiler (auxiliary/waste heat) › Combustion Air System
Issued 24 April 2014
Resolved
The Low Combustion Air Shut-Down did not function properly during the tests witnessed for #2 Boiler. Verify proper test procedures and prove proper operation of the shut-down. Cite 89 MODU 4.3.2. Action 40a,b,c.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2014
Resolved 9 May 2014
Resolution: Correct procedure has been created and unit tested sat.
Pollution Prevention/Response › Prevention Equipment › Oily Water Separator (15 ppm)
Issued 24 April 2014
Resolved
IMO approval was not present on the Oil Content Meter for the forward Oily Water Separator. Provide approval for the Oil Content Meter and have OEM affix approval to the unit. Cite 2004 MARPOL, Annex I, Ch III Reg 14.6 & 14.7. Action 50a,b,c.
Action required: 705 - Other - as specified
Due 24 May 2014
Resolved 21 May 2014
Resolution: Received an email from [name withheld] of the PSA attesting to the fact that the OCM is an IMO approved model. Pictures were provided as well.