11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 28 August 2019
Resolved
Rescue boat shall be in a fully inflated condition at all times. PSCO observed a deflated sponson on a rescue boat in way of transom on starboard side aft.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 September 2019
Resolution: Rec'd class report attesting to proper operation.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 28 August 2019
Resolved
Maintenance, testing and inspections shall be carried out in accordance with guidelines developed by the organization. PSCO noted that both the fixed firefighting system and portable firefighting appliances have not undergone annual inspection as last servicing was conducted in July 2018.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 September 2019
Resolution: Rec'd class report attesting to servicing and proper operation.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 28 August 2019
Resolved
Machinery spaces of category A shall be ventilated so as to ensure an adequate supply of air is maintained for the operation of machinery. PSCO noted temporary ventillation on all three ship service generators in way of turbo charger intakes.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 September 2019
Resolution: Rec'd class report attesting to proper operation.
14 - Pollution Prevention › 141 - MARPOL Annex I › Other (MARPOL Annex I)
Issued 28 August 2019
Resolved
Each operation shall be recoreded without delay in Oil Record Book, Part 1, so that entries in the book appropriate to that operation are completed. PSCO observed a bunkering entry incorrectly dated in ORB.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 September 2019
Resolution: Rec'd class report attesting to proper operation.
Engineering › Fuel Oil Service System › Filter
Issued 1 September 2016
Resolved
1499 - Other (Prop & Aux. Machinery)- In a ship in which oil fuel is used, the arrangements for the storage, distribution and utilization of the oil fuel shall be such as to ensure the safety of the ship and persons on board. PSCO observed an active leak from the fuel oil strainer, on the number 3 prime mover. 74 SOLAS (14) II-2/4.2.2 17a
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 September 2016
Resolution: Received class report stating deficiency was rectified.
Engineering › Fuel Oil Service System › Piping
Issued 1 September 2016
Resolved
1470 - Insulation wetted through (oil) - In a ship in which oil fuel is used, the arrangements for the storage, distribution and utilization of the oil fuel shall be such as to ensure the safety of the ship and persons on board. PSCO observed oil dripping onto the lagging underneath the FO strainer, on the number 3 prime mover. 74 SOLAS (14) II-2/4.2.2 17a
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 September 2016
Resolution: Received class report stating deficiency was rectified.
Lifesaving › Lifeboat › Lamp (outside)
Issued 1 September 2016
Resolved
0699 - Other (Life Saving Appliances) - During preparation and launching, the survival craft, its launching appliance, and the area of water into which it is to be launched shall be adequately illuminated by lighting supplied from the emergency source of electrical power. PSCO observed several emergency light fixtures not functioning. 74 SOLAS (14) III/16.7 10c
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 September 2016
Resolved 1 September 2016
Resolution: Crew replaced nonfunctioning light fixtures.