MAURY USCG vessel records
← All vessels

SOPHISTICATED LADY

Built
1973
Last inspected
8 December 2025
Documentation
Valid · NVDC file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 8 December 2025
Operational controls None recorded without a removal date
Years with a record 10 calendar years (2016–2025)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDA9662
120733
Flag
UNITED STATES
Maury page id
psix-120733

Documentation record

Registered dimensions (L × B × D)62.1 ft × 17.1 ft × 9.8 ft
Registered tonnagegross 90 / net 61
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderCHRIS CRAFT CORPORATION · HOLLAND, MI, UNITED STATES · built 1973
Hull materialAluminum
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portCHICAGO, IL
Endorsements, as the file codes themcw_un
DocumentationValid · issued 14 January 2026 · expires 28 February 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it61 - Regulatory (Subpart C or D), Net Ton
90 - Regulatory (Subpart C or D), Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel

Behind this panel: 23 inspections, each with its date, unit and type; 87 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; no tow-unit appearances recorded; no other recorded names; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 23

8 December 2025 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 8279114
22 September 2025 Annual Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 8238779
11 July 2024 Deficiency Check · Plan Review "T" Boat
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7956193
20 May 2024 Deficiency Check · Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7915720
3 November 2023 Deficiency Check · Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7819970
21 July 2023 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7757254
28 June 2023 Annual Inspection · Deficiency Check · Administrative Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7725833
22 September 2022 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7564483
28 July 2022 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7518026
13 July 2021 DAPI Audit · Annual Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7254568
28 July 2020 Deficiency Check · Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 7043891
11 May 2020 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6977211
17 March 2020 In-Service Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6928087
19 August 2019 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6787833
29 July 2019 DAPI Audit · Annual Inspection · Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6766484
2 November 2018 Plan Review "T" Boat · Administrative Inspection · Internal Structural Exam · Examination of Repairs · Drydock Exam
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6573387
5 June 2018 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6435177
24 April 2018 COI Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6398675
2 January 2018 Administrative Inspection
Administrative · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6331306
9 November 2017 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6304298
18 October 2017 Annual Inspection · DAPI Audit · In-Service Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6290455
30 November 2016 Deficiency Check
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6050573
21 October 2016 DAPI Audit · Annual Inspection
Physical examination · Marine Safety Unit Chicago · USCG Great Lakes District (CGD-GL) · Activity 6029404

Deficiency record · 87

07 - Fire Safety › N/A - No Subsystem › Evaluation of crew performance (fire drills)
Issued 22 September 2025 Resolved
Fire fighting drills and training shall be logged or otherwise documented for review by the Coast Guard upon request. Last fire drill recorded was June 2024.
Action required: 10 - Deficiency Rectified
Resolved 22 September 2025
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 22 September 2025 Resolved
All cable and wire must: (4) Be installed with metal supports spaced not more than 610 millimeters (24 inches) apart, and in such a manner as to avoid chafing and other damage. Cables found hanging on starboard side of engine room outboard of engine.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 6 October 2025
Resolved 8 December 2025
Resolution: -Wires on starboard side of engine room are secured with metal banding.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 22 September 2025 Resolved
Electrical equipment on a vessel must be installed and maintained to: (b) Protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Receptacles in port side of salon and on port side of flying bridge are damaged.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 6 October 2025
Resolved 8 December 2025
Resolution: -Replaced electrical receptacles in port side salon and flying bridge.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Windows, sidescuttles and deadlights
Issued 22 September 2025 Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected and all required guards and protective devices must be in satisfactory condition. Starboard side window in main cabin is cracked.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 October 2025
Resolved 8 December 2025
Resolution: -Replaced window on starboard side of main cabin.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 20 May 2024 Resolved
Firefighting drills and training shall be logged or otherwise documented. Create a drill log that includes the items required by 46 CFR 185.524 (date, description of topic/scenario).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC sent picture of drill log which includes all topics required by 46 CFR 185.524.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 20 May 2024 Resolved
A vessel must carry adequate and up to date Coast Pilot and Light List. Provide the same.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided electronic copies of the Light List and Coast Pilot 6.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 20 May 2024 Resolved
Portable fire extinguishers must be inspected IAW NFPA 10. Conduct monthly inspectio of the protable fire extinguishers.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 20 June 2024
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 20 May 2024 Resolved
All electrical installations must be to the satisfaction of the OCMI. The wires beneath the operating station are no properly mounted. Mount the same.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided pictures of proper mounting and securing of wires beneath the second deck op station.
09 - Working and Living Conditions › 091 - Living Conditions › Water, pipes, tanks
Issued 20 May 2024 Resolved
All observed unsafe practices must be corrected. The water heater outer shell is cracked and shows signs of over pressurization. Replace or remove the same. The water heater may not be operated pending replacement or removal.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided pictures of replacement water heater properly installed on vessel.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 20 May 2024 Resolved
A vessel of less than 65ft may provide a portable battery powered bull horn in lieu of a public address system. The vessel is missing a public address system. Provide a PA system or battery powered bull horn.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided statement of purchase of bullhorn and batteries.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 20 May 2024 Resolved
A vessel of 12 meters or more in length, but less than 50 meters in length, must have a stern light visible for a minimum of 2 miles. The stern light is not visible for 2 miles. Replace the same.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided statement of replacement of stern light w/ LED.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 20 May 2024 Resolved
A vessel must carry a first aid kit that meets 46 CFR 199.175(b)(10). First aid kit aspirin was expired. Provide the same.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided statement of purchase of aspirin for first aid kit.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 20 May 2024 Resolved
At each initial and subsequent inspection for certification of a vessel the owner shall be prepared and have the vessel ready for inspection. Four transverse stiffeners have fractured welds. Make repairs to the satisfaction of the marine inspector.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 July 2024
Resolved 22 July 2024
Resolution: POC provided pictures of repairs to stiffeners.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 November 2023 Resolved
The stern ladder is missing several pieces of hardware. Replace all hardware.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 20 June 2024
Resolution: Stern ladder hardware was replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 28 June 2023 Resolved
Provide four additional distress signals (either 4 orange smoke or 4 day/night).
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 July 2023
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 28 June 2023 Resolved
Provide Marine Radio Operator permit for [name withheld].
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 28 July 2023
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 June 2023 Resolved
Post EAP information (i.e. phone numbers) in an area accessible by the crew.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 August 2023
Resolved 7 July 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 June 2023 Resolved
The battery selector switch on the starboard side of the engine compartment is cracked. Repair or replace the same.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 28 July 2023
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 28 June 2023 Resolved
Provide eye wash for first aid kit.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 August 2023
Resolved 7 July 2023
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 28 June 2023 Resolved
Provide all around white anchor light.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 July 2023
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 28 June 2023 Resolved
Monthly fire extinguisher checks have not been conducted as required by NFPA 10 (incorporated by reference). Complete monthly fire extinguisher checks and log as appropriate.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 5 July 2023
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 28 June 2023 Resolved
Label interior and exterior of emergency escape hatche "Emergency Escape - Keep Clear" (2" letters).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 August 2023
Resolved 6 July 2023
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 1 August 2022 Resolved
Crew was unable to test the Fire boy shutdown and override. Conduct operational test of Fire boy in presence of Marine Inspector prior to carrying passengers.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 August 2022
Resolution: Witnessed test and override.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for master and officers
Issued 28 July 2022 Resolved
Master did not have a radio operator permit. Provide a crewmember holding a valid radio operator permit. 47 CFR 80
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: Master completed course online.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2022 Resolved
Vessel could not provide evidence of DAPI program. Provide random drug testing results in the form of a MIS report for crewmembers.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: Testing and MIS rcvd
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 28 July 2022 Resolved
First aid kit is missing items. Ensure the kit has all items required by 46 CFR 160.041
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: Items have been replaced.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2022 Resolved
A power cable for a camera on the stern of the vessel had been temporarily put in place. Properly route power cable and support wit metal at least every 24". 46 CFR 183.01-15
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 August 2022
Resolved 22 September 2022
Resolution: Video camera and power cords have been removed from stern of vessel.
99 - Other › N/A - No Subsystem › Other (MARPOL operational)
Issued 28 July 2022 Resolved
Foward head and cabin outlet power breaker is dislodged from panel faceplate. Properly reinstall the breaker. 46 CFR 183.01-15
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 August 2022
Resolved 1 August 2022
Resolution: Repaired
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 July 2022 Resolved
Upper deck rail wooden baseplate is rotten around vessel perimeter causing hazard as the entirely of the deck rail is not sturdily connected to the vessel.
Action required: 705 - Other - as specified
Due 30 November 2023
Resolved 16 November 2023
Resolution: Requirement re-issued as a worklist item for completion prior to credit dry dock.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 July 2022 Resolved
Forward boiw railing does not meetin rail courses requirements of 46 CFR 177.35-1. Provide means to restrict passenger access to foward bow or provide rail courses.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: Chain and sign added to box.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 July 2022 Resolved
Passenger access on port side diagonal rail course is missing rail hardward.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 August 2022
Resolved 1 August 2022
Resolution: hardware added.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 28 July 2022 Resolved
Forward crew space/quarters has an outlet that is brown/singed around the ground plug. 46 CFR 183.01-15
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: outlet repaired
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 28 July 2022 Resolved
Forward crew space/quarters has a 220V cable outlet with the ground wire disconnected. Remove if deadended or reconnect ground wire to 220V outlet box. 46 CFR 183.01-15
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: removed un-used wire.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 28 July 2022 Resolved
Galley area has a surge protector that is covered in grease. Remove from vessel and hard install equipment temporarily connected to the surge protector. 46 CFR 183.01-15
Action required: 10 - Deficiency Rectified
Resolved 1 August 2022
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 28 July 2022 Resolved
Throughout the vessel, there are multiple dead end wire/cable rune. Remove all the satisfaction of the OCMI. 46 CFR 183-01-15
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 July 2022 Resolved
Overboard discharge pipe in the engine room is not properly protected from flowing overboard. Properly cap overboard discharge in starboard engine space behind the battery box.
Action required: 30 - Ship detained
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 28 July 2022 Resolved
Engine space starboard side over head light is missing light fixture cover. 46 CFR 183.01-15
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
Resolution: replaced.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 July 2022 Resolved
Replace cable from battery charger to batters with proper boat cable. 46 CFR 183.01-15
Action required: 17 - Rectify deficiencies prior to departure
Resolved 2 August 2022
Resolution: New 14ga conductor run UL boat cable 105 c rated.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 July 2022 Resolved
Engine space port forward side has an electric motor that is not mouted to the deck. Properly mount mount to the deck.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 September 2022
Resolution: Electric motor has been secured to the deck.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 28 July 2022 Resolved
Secure fuel oil lek on propulsion engine suction line and remove fuel oil from the bilge area under the dining room.
Action required: 10 - Deficiency Rectified
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 28 July 2022 Resolved
Secure the four refrigerator in the foward compartment for sea.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 28 July 2022 Resolved
Secure all alochol and misc items in the aft storage compartment to allow access to bilge systems/pumps.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 28 July 2022 Resolved
Remove all temporary A/C system installation throughout the vessel.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 28 July 2022 Resolved
Improve general cleaniness thrughout the below deck compartments for crew accessibility and safety.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Cleanliness of engine room
Issued 28 July 2022 Resolved
Properly secure or remove all tools and maintenance items from engine space.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2022 Resolved
Prove vessel operation and safety by getting the vessel underway and conducting drills in the presence of attendig Coast Guard marine inspections.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 August 2022
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 July 2021 Resolved
Power panel in cabinet has open slots with no circuit breakers or covers present. Provide cover protection for exposed slots to the satisfaction of Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 August 2021
Resolved 15 July 2021
Resolution: Received evidence that exposed slots/circuit breakers have been filled with 1/2" filler plates.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 13 July 2021 Resolved
Starboard shaft seal is leaking heavily compared to drips on port side. Investigate cause and make repairs. Pump down/clean engine space bilge when shaft seal rectified to satisfaction of Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 July 2021
Resolved 5 August 2021
Resolution: Vessel has repaired starboard shaft seal leak and cleaned engine space bilges.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Windows, sidescuttles and deadlights
Issued 13 July 2021 Resolved
Window in galley port side is cracked/broken. Replace glass to satisfaction of Marine Inspector. 46 CFR 177.1020
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 August 2021
Resolved 5 August 2021
Resolution: Galley window glass has been replaced.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2020 Resolved
Propulsion machinery shall be suitable in its type and design. Remove all oil/water from bilge in engine room space, specifically underneath port and starboard engines. Clean within 7 days. 46 CFR 182.05-1
Action required: 705 - Other - as specified
Due 3 August 2020
Resolved 28 August 2020
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 28 July 2020 Resolved
Each exposed hatch must be watertight. Replace gasket and dogs to watertight hatch on bow. 46 CFR 117.13-1 46 CFR 171.124(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 August 2020
Resolved 28 August 2020
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2020 Resolved
Batteries should be secured against motion of the boat and connectors shall be of the permanent type. Battery located on port side of engine room were missing cover and connectors were loose. 46 CFR 183.05-20(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 August 2020
Resolved 28 August 2020
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 July 2020 Resolved
An exposed hazard, such as gears for rotating machinery, must be protected by a guard, cover, or rail. Rotating belt on port and starboard engine exposed. 46 CFR 177.960
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 August 2020
Resolved 28 August 2020
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2020 Resolved
A vessel must carry either a first aid approved under series 160.041 or a kit of equivalent contents and instructions. First aid kit expired. Replace in 7 days. 46 CFR 184.620(a)
Action required: 705 - Other - as specified
Due 4 August 2020
Resolved 28 August 2020
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 July 2020 Resolved
Placards containing instructions for the donning and use of life jackets must be posted. Vessel had no placards posted anywhere. 46 CFR 185.516(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 August 2020
Resolved 28 August 2020
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 July 2020 Resolved
Electrical accessories (fuses, switches, sockets) shall be standard NEC types of the loads to be carried. Missing fuse for hot water heater. 46 CFR 183.03-35(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 August 2020
Resolved 1 September 2020
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 March 2020 Resolved
Cutlass bearings are dry and cracking, water grooves are close to 50% wastage guidance. Further inspection and measurements are required to determine satisfactory material condition. Vessel shall have shafts pulled for further inspection and measurements for bearings. Additionally, provide manufacturer tolerance for measurements and deterioration of bearings. Complete instructions prior to the carriage of passengers.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 17 April 2020
Resolved 11 May 2020
09 - Working and Living Conditions › 092 - Working Conditions › Guards - fencing around dangerous machinery parts
Issued 30 July 2019 Resolved
Starboard propulsion engine needs rotating machinery guards placed in area where rotation, gears, and belts are present to satisfaction of Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2019
Resolved 19 August 2019
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 July 2019 Resolved
Repair lube oil strip pump electrical cord to satisfaction of Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2019
Resolved 19 August 2019
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 July 2019 Resolved
Replace electrical outlet cover in engine space.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2019
Resolved 19 August 2019
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Emergency preparedness
Issued 29 July 2019 Resolved
No vessel log or training log present showing emergency drills conducted. Provide logs and/or record of drill, conduct training prior to Inspector's return.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 30 July 2019
Resolution: Vessel is logging training and drills conducted to the satisfaction of Marine Inspector.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 29 July 2019 Resolved
Charts and publications are not current. Provide up to date charts and publications.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 30 July 2019
Resolution: Vessel has updated charts and publications to satisfaction of Marine Inspector.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 29 July 2019 Resolved
Life rings need SOLAS approved retro material. Install SOLAS approved retro material on all life rings.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 30 July 2019
Resolution: SOLAS approved retro material has been applied to all life rings to satisfaction of Marine Inspector.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 29 July 2019 Resolved
Remove or replace all receptacles for waste with ones made of non-combustible material.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 30 July 2019
Resolution: Waste receptacles are made of non-combustible material to satisfaction of Marine Inspector.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 July 2019 Resolved
Light switch in galley has missing switch opening. Replace switch or cover opening.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 30 July 2019
Resolution: Light switch has been replaced and opening covered to satisfaction of attending Marine Inspector.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 July 2019 Resolved
Outlet in engine room space is missing it's cover. Replace cover.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 30 July 2019
Resolution: Outlet cover has been replaced to satisfaction of attending Marine Inspector.
04 - Emergency Systems › N/A - No Subsystem › Water level indicator
Issued 29 July 2019 Resolved
FWD bilge alarm is inoperative. Restore FWD bilge alarm to proper working condition in Marine Inspector presence prior to carriage of passengers.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 July 2019
Resolution: All bilge alarms are working properly to satisfaction of attending Marine Inspector.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Freeboard marks
Issued 29 July 2019 Resolved
Vessel has no permanent draft marks or loading marks. Install proper marks.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 August 2019
Resolved 21 October 2019
Resolution: Owner stated he could use black paint on hull to determine loading. cleared CG-835.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 29 July 2019 Resolved
Installed and portable fire extinguishing systems/devices have not been serviced/maintenance since OCT 19, 2017. Provide inspection report for services fire fighting systems ,prior to the carriage of passengers, to Marine Inspectors.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 July 2019
Resolution: Installed and portable fire extinguishing systems/devices have been serviced to the satisfaction of attending Marine Inspector.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 29 July 2019 Resolved
Conduct man overboard and fire drills in presence of Marine Inspectors prior to the carriage of passengers.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 July 2019
Resolution: Drills have been conducted to the satisfaction of attending Marine Inspector.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 29 July 2019 Resolved
Conduct machinery, engines, generator, steering operations while underway with Marine Inspectors prior to carriage of passengers.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 July 2019
Resolution: Underway machinery operations have been conducted to the satisfaction of Marine Inspector.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 2 November 2018 Resolved
Crack on Keel in FWD void. Submit plan for approval for determining the size of the crack on the keel in the forward void. Coast Guard Inspector will attend for testing. 46 CFR 176.700
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 8 November 2018
Resolved 9 July 2019
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 2 November 2018 Resolved
After testing is completed, submit repair plan for approval, once approved, conduct repairs and have Coast Guard Inspector inspect and test repairs prior to carrying passengers. 46 CFR 176.700
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 8 November 2018
Resolved 9 July 2019
Operations/Management › Drug and Alcohol Testing › Recordkeeping
Issued 30 April 2018 Resolved
MIS report was not aboard the vessel. Provide copy of the report
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2018
Resolved 3 May 2018
Resolution: Report submitted
Electrical › Electric Generation Source (service) › Generator
Issued 24 April 2018 Resolved
port generator would not start. Demonstrate proper operation of the generator.Prove p
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 May 2018
Resolved 5 June 2018
Resolution: Operator submitted documentation that port engine was operating.
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 18 October 2017 Resolved
Provide documentation for annual fire fighting extinguishers servicing report. 46 CFR 176.810
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 18 October 2017 Resolved
life line dry rotted. Replace 46 CFR 180
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Resolution: Examined 02 new life buoys.
Documentation › Logs/Records › Drug Test Records
Issued 18 October 2017 Resolved
Missing current MIS report. (2015 and 2016) 46 CFR 16.260
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 3 December 2017
Resolved 9 November 2017
Resolution: Exammined MIS letter
Documentation › Markings/Placards › Warning Signs
Issued 18 October 2017 Resolved
replace fire extinguisher lable in forward main cabin. 46 CFR
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Resolution: Verified proper labeling
Electrical › Electric Generation Source (service) › Generator
Issued 18 October 2017 Resolved
STBD generator gauges at helm station not working. 46 CFR 182.410 and 182.155
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Resolution: witnessed operation of the port gauges.
Operations/Management › Navigation Safety › Navigation Underway, General
Issued 18 October 2017 Resolved
repair or replace broken window at main cabin helm station. 46 CFR 176.800
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Resolution: Glass had been renewed
Electrical › Lighting (service) › Switch
Issued 18 October 2017 Resolved
repair or remove A/C controls in forward compartment in crew quartors. 46 CFR 183.200
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 3 December 2017
Resolved 9 November 2017
Resolution: Verified cover installed
Pollution Prevention/Response › Prevention Equipment › Fixed Containment
Issued 18 October 2017 Resolved
remove all flammable containers from vessel or put in a approved flammable storage locker.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Resolution: Flammable containers removed from vessel.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 18 October 2017 Resolved
Conduct man overboard drill properly. 46 CFR
Condition: Invalid
Action required: 705 - Other - as specified
Due 3 December 2017
Resolved 9 November 2017
Resolution: Conducted man overboard and fire fighting drills
Navigation › Piloting/Steering › Marine Charts
Issued 18 October 2017 Resolved
provide updated charts for local area of operation. 46 CFR 184.420
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 May 2018
Resolved 30 April 2018
Resolution: Virified proper chart on board
Electrical › Lighting (service) › Outlet Box
Issued 21 October 2016 Resolved
Wiring from the electrical recptacle over the oven was operating as "open Neutral". Replace outlet box and ensure wiring is connected properly.
Action required: 705 - Other - as specified
Due 21 November 2016
Resolved 21 October 2016
Resolution: Corrected prior to end of inspection.
Fire Fighting › Portable CO2 Fire Extinguisher › Number
Issued 21 October 2016 Resolved
Missing one B-II fire extinguisher as per the COI. Purchase and add to accomandation space.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2016
Resolved 30 November 2016
Resolution: Received notification from vessel owner that a new fire extinguisher was purchased and added to the accommodation space per the COI.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.