Records from 2024 to 2025. Most recent: inspection, 18 February 2025.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 8 February 2024
Resolved
The purpose of this regulation is to contain fire... the integrity of the division shall be maintained at openings and penetrations. In battery room, class A boundary, PSCE observed missing packing in electrical penetration.
74SOLAS(20)II-2/9.1.3 40ac
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 26 April 2024
Resolution: Received class report of survey and corrective reports with pictures. Deficiencies rectified.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 8 February 2024
Resolved
Terminations and joints in all conductors shall be so made as to retain the original electrical, mechanical, flame-retarding and, where necessary, fire-resisting properties of the cable. Wiring in boatswain (FWD) was spliced together.
74SOLAS(20)II-1/45.5.6 40ac
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 26 April 2024
Resolution: Received class report of survey and corrective reports with pictures. Deficiencies rectified.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 8 February 2024
Resolved
Electrical installation shall be such that... The safety of passengers, crew, and ship from electrical hazards will be ensured. Frayed wires were found throughout the ship. Def Rectified.
74SOLAS(20)II-1/40.1.3 40ac
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 February 2024
Resolved 8 February 2024
Resolution: Deficiency was rectified on the spot, verified by the PSCO.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 8 February 2024
Resolved
Fire extinguishers shall... in such a way that their serviceability is not impaired by the weather, vibration, or other external factors. Portable fire extinguishers were not bracketed properly throughout the ship.
74SOLAS(20)II-2/10.3.2.4 40ac
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 22 February 2024
Resolution: Received satisfactory class report.