Records from 2016 to 2025. Most recent: inspection, 28 January 2025.
04 - Emergency Systems › N/A - No Subsystem › Water level indicator
Issued 28 January 2025
Resolved
The condition of the ship and it's equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons onboard. PSCO observed fore peak water ingress alarm not functional.
74 SOLAS 20 I/II(a)
Action required: 60 - Rectify deficiencies prior to movement
Resolved 29 January 2025
Resolution: Received satisfactory class report attesting to repairs of the alarm.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 28 January 2025
Resolved
A fixed fire-extinguishing system required by paragraph 5 below may be any of the following systems: a fixed pressure water-spraying fire-extinguishing system. PSCO observed water mist local fire pump starter actively leaking. Vessel crew replaced o-ring, tested zone, leaking stopped.
Action required: 10 - Deficiency Rectified
Resolved 28 January 2025
Resolution: PSCO observed that the vessel crew replaced o-ring, tested zone, leaking stopped.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Shipboard operations
Issued 6 November 2023
Resolved
The company and the ship shall comply with the requirements of the International Safety Management Code. For the purpose of this regulation, the requirements of the Code shall be treated as mandatory. The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations and with any additional requirements which may be established by the company. Objective evidence indicates a lack of compliance with vessel SMS to include proper operation, ready availability and maintenance of fixed fire-fighting systems and appliances, lack of compliance with garbage management plan, insufficient control of oil leaks, and general housekeeping. An external audit is required.
74 SOLAS(20) IX/3.1
ISM Code Part A/10.1
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 10 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, all sat.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 6 November 2023
Resolved
Machinery spaces of category A above 500m3 in volume shall, in addition to the fixed fire-extinguishing system required in paragraph 5.1.1, be protected by an approved type of fixed water- based or equivalent local application fire extinguishing system... In the case of periodically unattended machinery spaces, the fire-extinguishing system shall have both automatic and manual release capabilities... PSCOs discovered an unattended machinery space with the LP water mist system set to "local" preventing the system from operating automatically.
74 SOLAS (20 CONS) II-2/10.5.6.2
Condition: Placed in Improper Service
Action required: 30 - Ship detained
Resolved 9 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, confirmed water mist system was in remote.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 6 November 2023
Resolved
In a ship in which oil fuel is used, the arrangements for the storage, distribution and utilization of the fuel oil shall be such as to ensure the safety of the ship and persons onboard... PSCOs discovered an MGO fuel leak on the distribution system in the fuel supply line for the vessel's boiler and observed fuel dripping onto lagging and pooling on the deck below.
74 SOLAS (20) II-2 / 4.2.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 9 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, MGO leak appeared to be repaired, and new lagging had been placed on associated piping.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 6 November 2023
Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Portable extinguishers which have been discharged shall be immediately recharged or replaced... PSCOs discovered 02 CO2 nozzles in engine room covered with duct tape and plastic and 03 labeled extinguisher brackets in the engine room missing portable fire extinguishers.
74 SOLAS (20 CONS) II-2 / 14.2.1.2
Condition: Improper Installation
Action required: 30 - Ship detained
Resolved 9 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, plastic had been removed from CO2 nozzles and CO2 extinguishers had been replaced.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 6 November 2023
Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids… Means shall be provided to limit the accumulation of flammable liquids. PSCOs observed oil-soaked rags and active oil leaks on M/E.
74 SOLAS (20 CONS) II-2 / 4.1.1
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 10 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, all oil-soaked rags had been removed and no active oil leaks were observed on M/E.
14 - Pollution Prevention › 145 - MARPOL Annex V › Garbage management plan
Issued 6 November 2023
Resolved
Every ship of 100 gross tonnage and above...shall carry a garbage management plan which the crew shall follow... PSCOs observed inadequate containers and improper storage of garbage to include oily rags and domestic waste mixed with large batteries in the same wooden container. Additionally, oily rags, oil-soaked cardboard, and flammable liquid containers were found stored behind a lube oil tank, and throughout engine room.
MARPOL ANNEX V / 10.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 10 November 2023
Resolution: Received confirmation that vessel will discharge garbage at anchorage.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 6 November 2023
Resolved
For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (11) below... Table 9.5 requires an A-60 boundary between machinery spaces of category A and spaces for the storage of flammable liquids. PSCOs observed placarded flammable liquid containers in various locations throughout engine room and not in spaces categorized for their storage.
74 SOLAS (20 CONS) II-2 / 9.2.3.3.2.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 9 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, all containers had been removed from E/R and stored in accordance with garbage management.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 6 November 2023
Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Pump marked “fire G/S pump is inoperable”. Vessel has a general service pump and emergency fire pump for firefighting purposes.
74 SOLAS (20 CONS) II-2 / 14.2.1.2
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 November 2023
Resolved 28 January 2025
Resolution: Reviewed provided class report onboard and PSCO observed satisfactory operation.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 6 November 2023
Resolved
The fire resistance of doors shall be equivalent to that of the division in which they are fitted, this being determined in accordance with the Fire Test Procedures Code... PSCOs observed an A-15 Fire door on Deck C is being kept open due to loud whistling noise caused by ventilation pushing air through the door frame when door is closed.
74 SOLAS (20 CONS) II-2/ 9.4.2.1
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 November 2023
Resolved 9 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, door appeared to be repaired.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 6 November 2023
Resolved
Satisfactory means for safe passage required by 25-1 (in the form of guard rails, lifelines, gangways or underdeck passages, etc.) shall be provided for the protection of the crew getting to and from their quarters, the machinery space and any other spaces used in the essential operation of the ship. PSCOs observed multiple railings in engine room have missing/broken rails.
ICLL 25.4
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 November 2023
Resolved 9 November 2023
Resolution: Received Class report attesting to the rectification of all Code 30 deficiencies and the required external audit had been completed. PSC conducted deficiency check, railings had been repaired.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 26 October 2023
Resolved
07108-FIRE FIGHTING SYSTEMS AND APPLIANCES SHALL BE KEPT IN GOOD WORKING ORDER AND READILY AVAILABLE FOR IMMEDIATE USE. PSCO OBSERVED EXCESSIVE CORROSION ON THE LINES WHICH SUPPLY THE HYPER MIST NOZZLES WITH WATER TO THE VESSEL'S SEPARATOR ROOM.THE CREW WAS REQUESTED TO DEMONSTRATE THE OPERATION OF THE HYPER MIST SYSTEM IN THIS SPACE. THE CREW ATTEMPTED TO ACTIVATE THE SYSTEM THROUGH THE FIXED FIRE DETECTION AND LOCAL OPERATION FOR OVER 15 MINUTES WITHOUT SUCCESS.
74 SOLAS (20) II-2/14.2.1.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 26 October 2023
Resolved 31 October 2023
Resolution: Received Class Report attesting to rectification of this deficiency.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 26 October 2023
Resolved
07126-MEANS SHALL BE PROVIDED TO CONTROL LEAKS OF FLAMMABLE LIQUIDS. PSCO OBSERVED EXCESSIVE OIL LEAKS ON THE #1 AND #2 MDG'S AND UNDER THE MAIN ENGINE.
74 SOLAS (20) II-2/4.1.1
Action required: 17 - Rectify deficiencies prior to departure
Due 26 October 2023
Resolved 31 October 2023
Resolution: Received Class Report attesting to rectification of this deficiency.
14 - Pollution Prevention › 141 - MARPOL Annex I › 15 PPM Alarm arrangements
Issued 26 October 2023
Resolved
14108-OIL FILTERING EQUIPMENT REFFERED TO IN PARAGRAPH 2 OF THIS REGULATION SHALL COMPLY WITH PARAGRAPH 6 OF THIS REGULATION. IN ADDITION, IT SHALL BE PROVIDED WITH ALARM ARRANGEMENTS TO INDICATE WHEN THIS LEVEL CANNOT BE MAINTAINED. THE SYSTEM SHALL ALSO BE PROVIDED WITH ARRANGEMENTS TO ENSURE THAT ANY DISCHARGE OF OIL MIXTURES IS AUTOMATICALLY STOPPED WHEN THE OIL CONTENT METER OF THE EFFLUENT EXCEEDS 15 PARTS PER MILLION. IN CONSIDERING THE DESIGN OF SUCH EQUIPMENT AND APPROVALS, THE ADMINISTRATION SHALL HAVE REGARDS TO THE SPECIFICATION RECOMMENDED BY THE ORGANIZATION. THE 15 PARTS PER MILLION BILGE ALARM SHOULD RECORD DATE, TIME AND ALARM STATUS, AND OPERATING STATUS OF THE 15 PART PER MILLION BILGE SEPARATOR. PSCO OBSERVED THE OIL CONTENT METER, OMD-2005, DID NOT PROPERLY INDICATED THE SEPARATOR'S OPERATION STATUS.
MARPOL (73/78) I/14.7 MEPC 107(49) 4.2.9
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 26 October 2023
Resolved 28 January 2025
Resolution: Received Class Report extending the due date for this deficiency.
11 - Life Saving Appliances › N/A - No Subsystem › Embarkation arrangement survival craft
Issued 26 October 2023
Resolved
11124-BEFORE THE SHIP LEAVES PORT AND AT ALL TIMES DURING THE VOYAGE, ALL LIFE SAVING APPLIANCES SHALL BE IN WORKING ORDER AND READY FOR IMMEDIATE USE. PSCO OBSERVED SEVERAL DAMAGED STEPS DAMAGED STEPS ON THE FWD EMBARKATION LADDER. ADDITIONALLY, THE CREW WAS NOT ABLE TO PROVIDE ANY CERTIFICATE OR WEIGH TEST DOCUMENTATION FOR THE FWD EMBARKATION LADDER.
74 SOLAS (20) III/20.2
Action required: 17 - Rectify deficiencies prior to departure
Due 26 October 2023
Resolved 31 October 2023
Resolution: Received Class Report attesting to the rectification of this deficiency.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 26 October 2023
Resolved
09208-MACHINERY ASSOCIATED PIPING SYSTEMS SHALL BE SO INSTALLED AND PROTECTED AS TO REDUCE TO A MINIMUM ANY DANGER TO PERSONS ONBOARD, DUE REGARDS BEING PAID TO MOVING PARTS AND HOT SURFACES. PSCO OBSERVED MISSING LAGGING ON THE HOT SIDE OF THE TURBO ON #1 MDG.
74SOLAS(20)
II-1/26.1
Action required: 17 - Rectify deficiencies prior to departure
Due 26 October 2023
Resolved 31 October 2023
Resolution: Received Class Report attesting to the rectification of this deficiency.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 26 October 2023
Resolved
09210-THE CONDITION OF THE SHIP AND ITS EQUIPMENT SHALL BE MAINTAINED TO CONFORM WITH THE PROVISIONS OF THE PRESENT REGULATIONS TO ENSURE THAT THE SHIP IN ALL RESPECTS WILL REMAIN FIT TO PROCEED TO SEA WITHOUT DANGER TO THE SHIP OR PERSONS ON BOARD. PSCO OBSERVED HYDRAULIC LEAKS ON CARGO HOLDS HATCH COVER RAMS #1 AFT STBD, #2FWD STBD, #2 AFT PORT AND #3 FWD PORT.
74SOLAS(20)
III/20.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 26 October 2023
Resolved 28 January 2025
Resolution: Received Class Report extending the Due Date for this deficiency.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 26 October 2023
Resolved
11104-BEFORE THE SHIP LEAVES PORT AND AT ALL TIMES DURING THE VOYAGE, ALL LIFESAVING APPLIANCES SHALL BE IN WORKING ORDER AND READY FOR IMMEDIATE USE. PSCO OBSERVED THE CREW WAS UNABLE TO START THE RESCUE BOAT FOR OVER 15 MINUTES WITHOUT USE OF TOOLS. THE CREW WAS ABLE TO GET THE RESCUE BOAT STARTED AFTER TROUBLESHOOTING.
74SOLAS(20)
III/20.2
Action required: 10 - Deficiency Rectified
Due 26 October 2023
Resolved 26 October 2023
Resolution: Deficiency was rectified on the spot to the satisfaction of Coast Guard PSCO.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 June 2023
Resolved
Doors in boundary bulkheads of machinery spaces of Category A shall be reasonably gastight and self closing. A class door between steering gear and engine room has a bent sill therefore no longer preventing the passage of smoke or flame nor being gas tight.
Condition: Damaged By Earlier Event
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 22 August 2023
Resolution: Vessel submitted documentation with photos attesting to repairs.
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 19 June 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. The STBD aft steering raim is leaking hydraulic oil.
Condition: Damaged By Earlier Event
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 22 August 2023
Resolution: Vessel submitted documentation with photos attesting to repairs.
14 - Pollution Prevention › 141 - MARPOL Annex I › Retention of oil on board
Issued 19 June 2023
Resolved
After any survey of the ship under regulations 7,8,9, or 10 has been completed, no change shall be made in the structural arrangement, machinery, equipment, or other items covered by the survey without the sanction of the Adminisitration. PSCO identified fabricated flexible hoses from the main engine fuel oil drains directly into the bilge holding tank. Additionally, vessel is stowing used oil from an oil change conducted on Generator 2 in steel drums in the S/G room.
Condition: Placed in Improper Service
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 25 August 2023
Resolution: Vessel submitted the Class Report attesting to the corrections.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 19 June 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Emergency fire pump priming tank is wasted and leaking.
Condition: Damaged By Earlier Event
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 25 August 2023
Resolution: Vessel submitted the Class Report attesting to the corrections made.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 12 May 2023
Resolved
The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations and with additional requirements which may be established by the company. Due to the objective evidence in the deficiencies noted below, the vessel is not being maintained and not in substantial compliance with relevant conventions, calling into question the adequacy and implementation of the vessel's SMS under the ISM code. An external audit conducted by the Flag or RO is required before the ship will be release from its detention to determine whether the ship is operating in accordance with the ISM code. Provide a copy of the completed audit report to the USCG prior to departure from port. 74 SOLAS 20 XI-1/4.1 ISM Code 10.2
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: ISM Audit carried out by ABS with noted non-conformities and applicable corrective action.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 12 May 2023
Resolved
Each emergency generating set arranged to be automatically started shall be equipped with starting devices approved by the administration with stored energy capability of at least three consecutive starts. A second source of energy shall be provided for an additional three starts within 30 minutes. When testing primary source of power for emergency generator, PSCO observed that the battery bank was not sufficient to start the engine. 74 SOLAS 20 II-1/44.2
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: Vessel installed new battery bank. PSCO witnessed satisfactory operation of the emergency generator by primary and secondary means.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 12 May 2023
Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. PSCO observed a fault on the fire detection panel in the engine control room. PSCO also observed and the Chief Engineer was aware that the flame and smoke detectors over the number three generator and incinerator space were not operational. 74 SOLAS 20 II-2/14.2.1.2
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: Vessel installed new detectors where applicable. PSCO witnessed satisfacory operation and testing of fire detection system.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 12 May 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or person on board. PSCO observed multiple instances of fresh air distribution vents in the engine room severely clogged.
74 SOLAS 20 I/11(a)
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: PSCO observed clean and operating ventilation outlets.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 12 May 2023
Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. For this purpose, the following functional requirements shall be met: Means shall be provide to control leaks of flammable liquids. PSCO observed oil-soaked lagging, pumps, and equipment in the engine purifier room and on electrical cables on the ship's main engine. 74 SOLAS 20 II-2/4.1
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: PSCO observed corrective action by way of cleaing in applicable spaces. Additionally, ISM audit mandated corrected cleaning/maintenance schedule of machinery spaces.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 12 May 2023
Resolved
After any survey of the ship under regulations 7, 8, 9, or 10 has been completed, no change shall be made in the structural arrangements, machinery, equipment and other items covered by the survey, without the sanction of the administration. PSCO observed multiple instances of modification to the ventilation ducts to redirect the flow of fresh air into the engine room and on specific machinery. 74 SOLAS 20 I/11(b)
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: PSCO observed all ventilation additions were removed and system was back to approved setup.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 12 May 2023
Resolved
Ships shall be designed, constructed, and maintained in compliance with the structural, mechanical, and electrical requirements of a classification society. PSCO observed one port side and two starboard side valves on deck for the fuel-oil overflow piping system were frozen and in a general state of disrepair. 74 SOLAS 20 II-1/3-1
Action required: 30 - Ship detained
Resolved 26 May 2023
Resolution: PSCO observed satisfactory condition and operation of applicable valves.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 12 May 2023
Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliance shall be in working order and ready for immediate use. PSCO observed the hydro-static release unit on both life rafts were installed incorrectly with the painter line attached at the raft release point.
74 SOLAS 20 III/20.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 May 2023
Resolution: PSCO observed correct installation of lifeboat painter in accordance with lifesaving manual and manufacturing instructions.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 12 May 2023
Resolved
Where a fixed gas fire-extinguishing system is used, openings which may admit air to, or allow gas to escape from, a protected space shall be capable of being closed from outside the protected space. PSCO observed the caps to close the non-return valves on the cargo hatch drains were missing from every non-return valve on all of the cargo holds.
74 SOLAS 20 II-2/10.4.2
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 28 January 2025
Resolution: Reviewed provided class report onboard and PSCO observed satisfactory operation.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 12 May 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. PSCO observed a significant leak on the general saltwater cooling pump for the generators.
74 SOLAS 20 I/11(a)
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 28 January 2025
Resolution: Reviewed provided class report onboard and PSCO observed satisfactory operation.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 12 May 2023
Resolved
The machinery and fittings shall be of a design and construction adequate for serve for which they are intended and shall be so installed and protected as to reduce to a minimum any danger to persons on board, due to regard being paid to moving parts, hot surfaces, and other hazards. PSCO observed evidence of a jacket water leak on at least 1 of the main engine cylinder heads. 74 SOLAS 20 II-1/26.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 May 2023
Resolution: PSCO witness operation of main engine with no observed leaks.
09 - Working and Living Conditions › 092 - Working Conditions › Guards - fencing around dangerous machinery parts
Issued 12 May 2023
Resolved
The machinery and fittings shall be of a design and construction adequate for service for which they are intended and shall be so installed and protected as to reduce to a minimum any danger to persons on board, due to regard being paid to moving parts, hot surfaces, and other hazards. PSCO observed exposed rotating machinery on number 1 & 2 service generators and evidence of a significant exhaust leak on the ship service generator combine exhaust manifold.
74 SOLAS 20 II-1/26.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 May 2023
Resolution: PSCO observed installation of machinery guards and cleaning of generator exhuast stack. PSCO observed all 3 generators online without exhaust leak.
04 - Emergency Systems › N/A - No Subsystem › Water level indicator
Issued 12 May 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons onboard. PSCO observed fore peak water ingress alarm not functional.
74 SOLAS 20 I/11(a)
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 28 January 2025
Resolution: PSCO observed spares onboard. Re-issuing deficiency as code 60ac.
10 - Safety of Navigation › N/A - No Subsystem › Voyage data recorder (VDR)/Simplified Voyage data recorder(S-VDR)
Issued 12 May 2023
Resolved
The condition of the ship and it's equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons onboard. PSCO observed fault on ship's VDR due to missing signal from watertight doors.
74 SOLAS 20 I/11(a)
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 28 January 2025
Resolution: Reviewed provided class report onboard and PSCO observed satisfactory operation.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 12 May 2023
Resolved
Ships shall be maintained in compliance with the regulations of a classification society which is recognized by the Administration. PSCO observed corrosion/wastage on starboard anchor windlass and both port and starboard anchor chains.
74 SOLAS 20 II-1/3-1
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 28 January 2025
Resolution: Reviewed provided class report onboard and PSCO observed satisfactory operation.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 5 May 2020
Resolved
Before ship leaves the port and at all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. PSCO observed 02 temporaty patches on the lower corner of the lifeboat. 74 Solas (14) III/20.2 AC 17
Action required: 17 - Rectify deficiencies prior to departure
Resolved 6 May 2020
Resolution: Class surveyor had vessel grind down epoxy repair and observed no cracks or fractures. The area was repatched and hose tested. DNV GL surveyer accepted the new patch as permanent repair.
Documentation › Safety Management System › Company Responsibility/Authority Documentation
Issued 28 March 2018
Resolved
The company shall comply with the requirements of the ISM code. Due to objective evidence, the PSCO questions the adequacy of the vessel's SMS and Company Procedures Manual. The Company is responsible for the purchase and arrangements of provisions. Provisions were found to be inadequate and not provided for after requested verbally and by email from the vessel's officers. An external audit is recommended to be conducted by the flag state or recognized organization.
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 9 April 2018
Resolved 29 March 2018
Resolution: Vessel's company obtained and distributed adequate provisions to the vessel.
Lifesaving › Lifeboat › Propulsion Transmission
Issued 5 February 2018
Resolved
0610: BEFORE THE SHIP LEAVES PORT AND AT ALL TIMES DURING THE VOYAGE, ALL LIFESAVING APPLIANCES SHALL BE IN WORKING ORDER AND READY FOR IMMEDIATE USE. FREE-FALL LIFEBOAT TRANSMISSION CLUTCH IS FAILING TO ENGAGE, RESULTING IN LACK OF PROPULSION AND INABILITY OF EQUIPMENT TO FUNCTION FOR IMMEDIATE USE. (74 SOLAS (14) III/2) CODE: 17(a)(c)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 10 February 2018
Resolution: Witnessed proper operation of Lifeboat. Entire transmission assembly was replaced. Reference Activity #63530941.
Engineering › Freshwater System (intermediary cooling) › Valve
Issued 5 February 2018
Resolved
1499: THE MACHINERY, ASSOCIATED PIPING SYSTEMS, AND FITTINGS SHALL BE OF A DESIGN AND CONSTRUCTION ADEQUATE FOR THE SERVICE FOR WHICH THEY ARE INTENTED. LEAKING AND CORROSION WERE FOUND ON SEALS IN THE FRESH WATER GENERATOR SYSTEM, GENERATOR COOLING WATER PUMP AND PIPING, AND LUBE OIL VENT LINE. (74 SOLAS (14) II-1/26.1) CODE: 40(a)(c)
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 10 February 2018
Resolution: Verified satisfactory repairs made to gaskets and seals for the fresh water generator system, generator cooling water pump, and lube oil vent line. Reference Activity #6353091.
Fire Fighting › Nozzles › Condition
Issued 5 February 2018
Resolved
0725:FIRE PROTECTION SYSTEMS AND APPLIANCES SHALL BE MAINTAINED AND READY FOR USE. TWO SPRINKLER HEADS FOR THE FIXED FIREFIGHTING SYSTEM IN THE ENGINE ROOM WERE FOUND COVERED AND THUS NOT READY FOR IMMEDIATE USE. (74SOLAS(14) II-2/14.1.1) CODE:10(c)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 10 February 2018