PVT SOLANA is a 2008 tank ship. The Coast Guard has recorded 13 inspections since 2016, most recently in August 2024, along with 34 deficiencies — 2 with no resolution recorded — and 3 operational controls.

Records from 2016 to 2024. Most recent: inspection, 2 August 2024.

Built
2008
Last inspected
2 August 2024
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 2 August 2024
…with no type recorded2
Operational controls None recorded without a removal date
Years with a record 5 calendar years (2016–2024)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9391531
3E6050
1278403
Flag
PANAMA
Maury page id
psix-1278403

Documentation record

Tonnage as PSIX records it50129 - Dead Weight, Metric Ton
60971 - Displacement, Metric Ton
29995 - Convention (Subpart B), Gross Ton
13358 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 13

2 August 2024 Appeal
Administrative · Commandant (CG-CVC) · Activity 7973042
28 June 2024 PSC B
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7942795
28 June 2024 Appeal
Administrative · Commandant (CG-CVC) · Activity 7949809
12 May 2024 Deficiency Check · PSC A · COC-CHEM & TVE Renew
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7909347
31 August 2023 VRP Review
Administrative · U.S. COAST GUARD FORCES MICRONESIA/SECTOR GUAM · USCG Oceania District (CGD-O) · Activity 7786629
29 January 2023 PSC B · COC-CHEM & TVE Renew
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7628582
15 May 2019 In-Service Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6686547
13 May 2019 Administrative Inspection
Administrative · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6683726
26 April 2019 ISPS II Exam · COC-CHEM & TVE Annual · Ballast Water Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6664920
26 April 2019 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6683438
29 March 2018 Type not recorded
No type recorded · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6381310
29 March 2018 ISPS II Exam · Ballast Water Examination · COC-CHEM & TVE Renew
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6381345
1 August 2016 ISPS II Exam · COC-CHEM & TVE Renew · Ballast Water Examination
Physical examination · Marine Safety Unit Brownsville · USCG Heartland District (CGD-H) · Activity 5952256

Deficiency record · 34

14 - Pollution Prevention › 148 - Ballast Water › Ballast water report
Issued 28 June 2024 Resolved
The Master, Owner, Operator, Agent or person in charge of any vessel subject to this part bound for ports or places of the United States must provide the information required by 151.2070 of this subpart in electronic or written form to the Coast Guard through the National Ballast Information Clearinghouse's website, Vessel has not submitted a ballast report since new management. 33CFR151.2060 10c
Condition: Invalid
Action required: 10 - Deficiency Rectified
Resolved 28 June 2024
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 7 June 2024 Resolved
Firefighting systems and appliances shall be kept in good working order and readily available for immediate use. PSCO observed hyper mist system set to manual. Fresh water supply valve to the system was also found in the closed position. 74 SOLAS (2004) II-2/14.2.1.2 30ac
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Due 7 July 2024
Resolved 14 June 2024
Resolution: System was observed in "remote" setting and main supply valve was found open. Found one clogged sprinkler head above framo power packs, crew cleared clog. hyper mist was successfully tested above power packs and purifier room in presence of MI's.
14 - Pollution Prevention › 141 - MARPOL Annex I › Other (MARPOL Annex I)
Issued 7 June 2024 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present convention to ensure that the ship in all respects will remain fit to proceed to sea without presenting an unreasonable threat of harm to the marine environment. Vessel’s sewage holding tank is full. Crew is transferring sewage to bilge holding tank. MARPOL ANNEX I REG 6.4.1 17ac
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 7 July 2024
Resolved 14 June 2024
Resolution: Sewage is being offloaded to truck shoreside from the sewage holding tank and bilge holding tank.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 7 June 2024 Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids for this purpose, functional requirements shall be met: means shall be provided to control leaks of flammable liquids. PSCO observed port side MGO settling tank leaking from a fitting near the deck into an open catch pan with about one gallon of fuel in the pan. Additionally, PSCO observed FO #2 circulating pump leaking. 74 SOLAS (20) II-2/4.1.1 30ac
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Due 7 July 2024
Resolved 14 June 2024
Resolution: Leak on the settling tank was corrected and the fuel oil properly stored.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 7 June 2024 Resolved
The purpose of this regulation is to contain a fire in the space of origin. For this purpose, the following functional requirements shall be met: Thermal insulation of boundaries shall have due regard to the fire risk of the space and adjacent spaces. PSCO observed missing insulation on overhead by port MGO settling tank. This boundary is identified as “A-60”. 74 SOLAS (20) II-2/9.1.2 17ac
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 7 July 2024
Resolved 14 June 2024
Resolution: New insulation was installed in the area of concern.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 7 June 2024 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations. PSCO observed hose clamps and other evidence of temporary repair on fresh water line feeding hyper-mist system, as well as on an unknown pipe above MGO settling tank (port) in the engine room. 74 SOLAS (20) 1/11a 17ac
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 7 July 2024
Resolved 14 June 2024
Resolution: Hose clamps were removed, pipe appeared in good condition.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 7 June 2024 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the code to ensure that the ship will remain fit to proceed to see without danger to the ship or persons on board or without presenting an unwarranted threat of harm to the marine environment. PSCO observed multiple faults on the hydraulic power unit remote controller for all cargo and ballast valves. 74 SOLAS (20) VII /10.1 IBC CODE 1.5.3.1 17 AC
Action required: 17 - Rectify deficiencies prior to departure
Due 7 July 2024
Resolved 14 June 2024
Resolution: Faults were corrected, new def issued for remote controller console showing incorrect valve position on multiple cargo tank valves.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 7 June 2024 Resolved
Each tank ship with a vapor collection system must be fitted with a pressure sensing device located as close as practicable to the vessels vapor connection, that measures the pressure in the main vapor collection line, which has a high pressure and a low-pressure alarm that gives an audible and visible warning on the vessel where the cargo transfer is controlled. Vessel does not have a hand pump for testing, PSCO was unable to verify operation of high and low pressure alarms on the VECS. 46 CFR 39.2013(b)(1) 17 AC
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 7 July 2024
Resolved 14 June 2024
Resolution: Crew purchased a new hand pump to test pressure sensors in cargo system.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 June 2024 Resolved
Electrical equipment cables and wiring shall not be installed in the hazardous locations unless it conforms with the standards not inferior to those acceptable to the organization. PSCO observed grounding wire to the tank radar for the 1 port cargo tank disconnected. 74 SOLAS (20) VII/10.1 IBC CODE 10.1.4 10C
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 8 June 2024
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 21 May 2024 Resolved
The conditions of the ship and its equipment shall be maintained to conform with the provisions of theCode to ensure that the ship will remain fit to proceed to sea without danger to the ship or persons onboard or without presenting an unreasonable threat of harm to the marine environment. PSCO observed active alarm on power pack #4 due to low start battery voltage. Additionally, PSCO observed inoperable drive pressure gauge for #4 starboard Framo pump. 74 SOLAS (20) VII/10.1 IBC Code 1.5.3.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 14 June 2024
Resolution: Observed drive pressure gauge fuctioning properly on all cargo pumps. Alarm was corrected on #4 power pack-low start battery voltage. Calss attested to the same.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 May 2024 Resolved
Electrical equipment, cables and wiring shall not be installed in the hazardous locations unless itconforms with the standards not inferior to those acceptable to the Organization. PSCO observed holes in the electrical run to 4S Framo pump sensor (discharge). Addtionally, PSCO observed gland for explosion proof light aft of tank slop S not properly packed. 74 SOLAS (20) VII/10.1 IBC Code 10.1.4
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 June 2024
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 21 May 2024 Resolved
Each tankship with a vapor collection system must be fitted with a pressure-sensing device, located as close as practicable to the vessel vapor connection. PSCO observed fitting for starboard aft VCS pressure sensor severely corroded. 46 CFR 39.2013
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 June 2024
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 12 May 2024 Resolved
Firefighting systems and appliances shall be kept in good working order and readily available for immediate use. PSCO observed vessels hyper-mist system set to manual. Additionally, PSC observed multiple hyper-mist nozzles blocked with rust and saltwater buildup, preventing any flowto the nozzle above the incinerator and restricting flow above boiler. 74SOLAS(2004) II-2/14.2.1.2
Action required: 30 - Ship detained
Resolved 21 May 2024
Resolution: Crew demonstrated full operation of the hyper mist system above the incinorator with appropriate smoke and flame testing EQ.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 12 May 2024 Resolved
Firefighting systems and appliances shall be kept in good working order and readily available for immediate use. PSCO observed local controls and pilot cylinder for the emergency diesel generator fixed CO2 system seized shut. Additionally, PSCO observed, activator valve handles painted and seized in the closed position. 74SOLAS(2004) II-2/14.2.1.2
Action required: 30 - Ship detained
Resolved 21 May 2024
Resolution: During follow-on inspection crew remove seized actuation handles and freed them up allowing for proper operation. Key lock to activation station box was renewed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 May 2024 Resolved
Electrical equipment, cables, and wiring shall not be installed in the hazardous locations unless it conforms with the standards not inferior to those acceptable to the organization. PSCO observed severe wastage to electrical runs, including flexible conduit within the hazardous area indicated in the vessels approved hazardous location plan specifically, -Temp sensor (discharge) to slop port Framo pump, starboard slop junction box, two starboard tank radar, one starboard temperature sensor. -bolts missing on Ballast Water tank six starboard tank level sensor, bolt missing on temperature sensor three port, bolt missing ballast wing tank two port tank level sensor. -bonding strap above tank one starboard, ground wires disconnected to forward, starboard explosion proof light, and to deck crane motor controller -Finally, PSCO observed cracked explosion proof light on the forward port side forecastle bulkhead. PSCO traced to the intrinsically safe circuits back to the electrical panel, located in cargo control room, and observed faults on four isolation devices compromising the circuit. 74SOLAS(2020) VII/10.1 IBC 10.1.4
Action required: 30 - Ship detained
Resolved 14 June 2024
Resolution: Crew resolved all outstanding electrical issues noted in deficiency, Class attested to the same.
07 - Fire Safety › N/A - No Subsystem › Inert gas system
Issued 12 May 2024 Resolved
For tankers of 20,000 tons deadweight and upwards the protection of the cargo tank shall be achieved by fixed inert gas system in accordance with the requirements of the Fire Safety Systems Code. PSC observed vessel's inert gas generator inoperable. The crew identified the gas regulating valve was not functioning properly on 24 January 2024, rendering system unable to provide inert gas at or below 5% oxygen. Crew notified Company without rectification. 74SOLAS(2004) II-2/4.5.5.1.1
Action required: 30 - Ship detained
Resolved 14 June 2024
Resolution: IGG still inoperable, condition of class issued with requirement for repair to be complete by 06JUL2024. New def issued as 40ac for the same.
08 - Alarms › N/A - No Subsystem › UMS - alarms
Issued 12 May 2024 Resolved
Bilge Wells in periodically unattended machinery spaces shall be located and monitored in such a way that the accumulation of liquids is detected at normal angles of trim and heel. PSCO observed crew unable to activate bilge alarms. 74SOLAS(2004) II-1/48.1
Action required: 30 - Ship detained
Resolved 21 May 2024
Resolution: Crew satifactorily tested all bilge alarms in the engine room.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 12 May 2024 Resolved
The function of the fixed fire detection and fire alarm system shall be periodically tested to the satisfaction of the administration by means of equipment producing hot air at the appropriate temperature, or smoke or aerosol particulates having the appropriate range of density or particle size, or other phenomena associated with incipient fires to which the detector is designed to respond. PSCO observed crew does not have required testing equipment on board to test flame detectors or manually operated call points. 74SOLAS(2004) II-2/7.3.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Crew obtained the correct equipment on board.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Atmosphere testing instruments
Issued 12 May 2024 Resolved
A chemical tanker shall comply with the requirements of the international bulk chemical code and shall, in addition to the requirements of regulation I/8, I/9, and I/10, as a applicable, be surveyed and certified as provided for the code. Ships carrying toxic or flammable products or both shall be equipped with at least two instruments designed and calibrated for testing for the specific vapors in question. PSC observed fixed gas detection system inoperable, portable detectors for toxic cargo on board were not available for toluene or xylenes. 74SOLAS(2020) VII/10.1 IBC 13.2.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 June 2024
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 12 May 2024 Resolved
Doors required to be self closing shall not be fitted with holdback hooks. PSCO observed both A-class self closing doors to galley as indicated on vessels approved fire control plan, fitted with holdback hooks. Additionally, PSCO observed self closing mechanism removed from officer recreation room, and A-class self closing fire door to "B" deck cable duct, unable to latch as intended. 74SOLAS(2004) II-2/9.4.2.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Crew removed all above mentioned hold backs and adjusted self closing mechanism.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 12 May 2024 Resolved
Where A-Class divisions are penetrated… penetrations shall be suitably insulated by extension of the insulation at the same level of the division. PSCO observed insulation in A-class division separating "A" deck and "B" deck cable ducts, completely missing in two cable runs and partly missing in one cable run. 74SOLAS(2004) II-2/9.3.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 June 2024
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 12 May 2024 Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. For this purpose, the following functional requirements shall be met: means shall be provided to control leaks of flammable liquids. PSC observed oil accumulation below the flywheel of all the generators, fuel oil pooling in the catch tray of the number two generator fuel filters, and on top of the boiler. 74SOLAS(2004) II-2/4.1.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Leaks arrested and cleaned by crew.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 12 May 2024 Resolved
The conditions of the ship and its equipment shall be maintained to conform with the provisions of the Code to ensure that the ship will remain fit to proceed to sea without danger to the ship or persons onboard or without presenting an unreasonable threat of harm to the marine environment. PSCO observed vessels electronic tank radar displaying inaccurate readings, particularly tank six starboard containing mixed xylene, a type two cargo, containing over 3000 m³ of product. Crew confirmed via UTI, Actual level is 2998 m³. Additionally, PSO observed temperature sensors displaying inaccurate readings, particularly tank one starboard was 89°C and tank six starboard was reading -67°C. 74SOLAS(2020) VII/10.1 IBC 1.5.3.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 June 2024
07 - Fire Safety › N/A - No Subsystem › Inert gas system
Issued 12 May 2024 Resolved
The inert gas supply main shall be fitted with branch piping leading to each cargo tank. Branch piping for inert gas shall be fitted with either stop valves or equivalent means of control for isolating each tank. PSCO observed the isolation valve to one port cargo tank taken apart at the valve gearbox. The valve is inoperable, and cannot be determined to be open or closed. 74SOLAS(2020) II-2/4.5.5.1.1 FSS CODE (07) 15.2.3.2.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Crew replaced with a new valve.
01 - Certificates & Documentation › 011 - Ships Certificates › Load Lines (including Exemption)
Issued 12 May 2024 Resolved
After any survey of the ship under Article 14 has been completed, no change shall be made in the structure, equipment, arrangements, material or scantlings covered by the survey, without the sanction of the Administration. PSC observed load line painted with a tropical fresh, fresh, tropical, summer, and winter load line as indicated on certificate number 2223778/LL1 with a deadweight 50,129 metric tons, however, the last activity and correspondence from class indicates the vessel should be operating with a load line with just a freshwater mark and a deadweight of 34,999 metric tons as indicated on certificate number 2223778/LL4. ILLC 66 Article 15
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: The correct Load Line certificate is being used now, others are stowed in safe on board
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 12 May 2024 Resolved
Every ship to which this Annex applies shall be provided with a Cargo Record Book, whether as a part of the ship's official logbook, or otherwise, in the form specified in appendix II to this Annex. PSCO observed the cargo record book being in another format, not matching appendix II. MARPOL II/15.1
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Correctly formatted Cargo Record Book was found on board with appropriate entires.
12 - Dangerous Goods › N/A - No Subsystem › Other (tankers)
Issued 12 May 2024 Resolved
Stowage of cargo samples. The stowage space shall be: - cell-divided in order to avoid shifting of the bottles at sea. PSCO observed cargo sample storage locker full with additional samples stowed above the cell enclosure. 74SOLAS(2004) VII/10.1 IBC 16.5.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Crew added proper stowage baskets and organized samples with cell division.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 12 May 2024 Resolved
Cylinders must always be secured and, when not in use, they must be stowed in a rack in an upright position, with the valve protection cap in place. PSCO observed 80 nitrogen bottles to the deck in the cargo area. Some bottles were missing the protective caps. 46CFR 147.60(b)(1)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Nitrogen bottles were moved to steel baskets stored on top of the external framing of the cargo tank tops in the upright position and secured in place. Crew stated that after cargo discharge/inerting the bottles would be removed.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Maintenance of the ship and equipment
Issued 12 May 2024 Resolved
The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations and with any additional requirements which may be established by the company. The technical and or operational nature of deficiencies 02, 03, 04, 05, 06, 07, 08, 09, 10, 11, 12, 13,16 and 17 provide objective evidence of a serious failure of the implementation of the ISM code. An external audit report satisfactory to the OCMI must be submitted prior to the clearance of this deficiency. 74SOLAS(20) IX/3.1 ISM Code 10.1
Action required: 30 - Ship detained
Resolved 21 May 2024
Resolution: Class NKK provided external audit noting company and vessel shortfalls to address.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 12 May 2024 Resolved
Each vessel vapor connection flange face must have a permanent stud projecting outward that has a 12.7 millimeter (0.5 inch) diameter and is at least 25.4 millimeters (1 inch) long. It must be located at the top of the flange face, midway between boltholes, and in line with the bolthole pattern. PSCO observed no flange stud on the starboard forward vapor connection. 46 CFR 39.2001(j)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2024
Resolution: Flange was removed and a permanent stud was installed in on board workshop, flange reinstalled.
07 - Fire Safety › N/A - No Subsystem › Inert gas system
Issued 12 May 2024 Resolved
For tankers of 20,000 tons deadweight and upwards the protection of the cargo tank shall be achieved by fixed inert gas system in accordance with the requirements of the Fire Safety Systems Code. PSC observed vessel's inert gas generator inoperable. The crew identified the gas regulating valve was not functioning properly on 24 January 2024, rendering system unable to provide inert gas at or below 5% oxygen. Condition of class issued requiring rectification by 06 JULY 2024. 74 SOLAS (04) II-2/4.5.5.1.1
Action required: 705 - Other - as specified
Due 6 July 2024
Resolved 20 June 2024
Resolution: Class report issued attesting to satisfactory reapir of the IGG.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 12 May 2024 No resolution recorded
The conditions of the ship and its equipment shall be maintained to conform with the provisions of theCode to ensure that the ship will remain fit to proceed to sea without danger to the ship or persons onboard or without presenting an unreasonable threat of harm to the marine environment. PSCO observed valve position indicator for 2 port, 3 port, 4 port and stbd, 5 stbd, and stbd slop cargo tank valves on the hydraulic power unit remote controller console in CCR. 74 SOLAS (20) VII/10.1 IBC Code 1.5.3.1
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 May 2024 No resolution recorded
Electrical installations shall be such that: the safety of passengers, crew and ship from electrical hazards will be ensured. PSCO observed disconnected ground wires on explosion proof light aft of stbd slop tank, stbd embarkation deck emergency light, and light on port side of upper funnel. Additionally, PSCO observed multiple wire runs in the engine room with compromised glands exposing the conductors to include motors on sewage treatment plant and HFO/LO purifiers and most tank level sensors for storage tanks within the engine room. 74 SOLAS (04) II-1/40.1.3
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 15 May 2019 Resolved
The machinery, boilers, and other pressure vessels associated piping systems and fittings shall be of a design and construction adequate for the servie for which they are intended and shall be so installed and protected as to reduce to a minimum any danger to persons on board due regard being paid to moving parts, hot surfaces and other hazards. Vessel suffered a reduction in propulsion due to issue with steam bypass valve on main engine fuel oil heaters. 74 SOLAS (04) II-1/26.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 15 May 2019
Resolution: Class provided inspection report recommending the steam bypass valves be replaced and confimring that blanks were installed to prevent further propulsion interruptions.