Tonnage as PSIX records it81944 - Dead Weight, Metric Ton 94361 - Displacement, Metric Ton 42995 - Convention (Subpart B), Gross Ton 27444 - Convention (Subpart B), Net Ton 42995 - Simplified, Gross Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 21 November 2024Resolved
74 SOLAS 20 II-2/10.1.1.1
... THE FOLLOWING FUNCTIONAL REQUIREMENTS SHALL BE MET: FIXED FIRE-FIGHTING SYSTEMS SHALL BE INSTALLED HAVING DUE REGARD TO THE FIRE GROWTH POTENTIAL OF THE PROTECTED SPACES. PSCO OBSERVED MISSING AGENT CYLINDER FROM INSTALLED GALLEY GAYLORD SYSTEM.
10C
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 21 November 2024
Resolved 21 November 2024
Resolution: ORDERED NEW AGENT CYLINDER AND CORRESPONDING HOSE.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 21 November 2024Resolved
74 SOLAS 20 II-2/9.4.1.1.1
... OPENINGS SHALL BE PROVIDED WITH PERMANENTLY ATTACHED MEANS OF CLOSING WHICH SHALL BE AT LEAST AS EFFECTIVE FOR RESISTING FIRES AS THE DIVISIONS IN WHICH THEY ARE FITTED. PSCO OBSERVED A-15 FIRE DOOR FOR THE FIRE CONTROL STATION INCAPABLE OF FULLY CLOSING.
50C
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2024
Resolved 16 January 2025
Resolution: Door was taken off faulty hinges and made true to frame. Deficiency effectively rectified and pictures and class report attached in Documents.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 21 November 2024Resolved
74 SOLAS 20 II-2/4.1.1
MEANS SHALL BE PROVIDED TO CONTROL LEAKS OF FLAMMABLE LIQUIDS. PSCO OBSERVED FUEL OIL LEAKS IN PURIFIER SPACE AND MULTIPLE FUEL FILTERS THROUGHOUT THE MACHINERY SPACE.
40AC
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 21 January 2025
Resolved 16 January 2025
Resolution: Crew rectified deficiency by fixing leaks from pumps and replacing diesel oil filter lagging.