DURANGO is a 2000 tank ship. The Coast Guard has recorded 15 inspections since 2017, most recently in October 2019, along with 14 deficiencies and 2 operational controls, 1 with no removal date recorded.
Records from 2017 to 2019. Most recent: operational control imposed, 13 October 2019.
This record may be incomplete: the most recent inspection recorded for this vessel was 7 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
Tonnage as PSIX records it12369 - Regulatory (Subpart C or D), Net Ton 28534 - Convention (Subpart B), Gross Ton 12369 - Convention (Subpart B), Net Ton 47131 - Dead Weight, Metric Ton 56474 - Displacement, Metric Ton 28534 - Regulatory (Subpart C or D), Gross Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 2016 to
2026 for this class, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
The Coast Guard recorded this vessel and the following in the same
inspection activity — normally a tug and the barges in its tow. A recreational or
unclassed hull in the same activity is held and not published, so it does not appear
here: these lists are a floor, not a complete manifest.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 19 June 2019Resolved
Oil tankers shall carry fire protected lifeboats complying with the requirements of section 4.9 of LSA Code. PSCO found that the piping and one of the securing brackets on the STBD side lifeboat water spary system were damaged by previous event. The piping was partially crushed and the PORT side bow bracket was broken. In addition, the system is missing one nozzle on the forward section.
74 SOLAS (2014) III/31.1.7
50ac
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 July 2019
Resolved 19 July 2019
Resolution: Representatives of the vessel submitted documentation attesting to correcting the noted deficiency.
Operations/Management › Pollution › Control of Discharge of Oil
Issued 25 May 2018Resolved
Subject to the provisions of regulation 4 of MARPOL ANNEX I and paragraphs 2,3, and 6 of regulation 15, any discharge into the sea of oil or oily mixtures from ships shall be prohibited. PSCOs attended vessel after report of heavy fuel oil spill received. PSCOs witnessed HFO leaking out through stbd side ballast overboard discharge into the sea. MARPOL Annex I Reg. 15.1 Action 17.a.c.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 1 June 2018
Resolved 27 May 2018
Resolution: See Class Report.Source of oil discharge controlled. Condition of Class imposed.
Operations/Management › Pollution › Discharge of Cargo Residue
Issued 25 May 2018Resolved
Instructions as to the operation of the ODME shall be IAW an operational manual approved by the administration. ODME manual is not approved by the administration. MARPOL Annex I Reg. 31.4. Action 50.b.c.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 June 2018
Resolved 19 July 2019
1410-Propulsion Main Engine- The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Vessel experienced a loss of propulsion while transiting outbound of Corpus Christi, TX. 74SOLAS(2014)Ch.1/Reg.11(a)
Action required: 60 - Rectify deficiencies prior to movement
Resolved 30 January 2018
Resolution: Class report provided attesting to repair.
Engineering › Compressed Air System (control) › Valve
Issued 25 July 2017Resolved
The #2 air start valve was stuck in the open position causing the reduction of propulsion, as noted on attached Class Report.
Condition: Invalid
Action required: 705 - Other - as specified
Due 18 August 2017
Resolved 26 July 2017
Resolution: Class issued a condition of class, set to expire on the 8/18/2017
1835 - The venting system shall be provided with devices to prevent passage of flame into the cargo tanks. All 16 flame screens on the vacuum side of the P/V valves are holed and rotted through and would not prevent the passage of flame into the cargo and slop tanks. 74 SOLAS (2001 Cons.) II-2/59.1.5, 46 CFR 39.2011(b) 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
Deck/Cargo › Holds/Tanks › Fixed Gas Detection
Issued 29 June 2017Resolved
1820 - The sampling points for the bottom of the cargo pump room were disconnected at the gas tight bulkhead penetration from the cargo pump room into the sampling unit in the accommodation space. Furthermore, crew did not have appropriate calibration gas on-board for testing of LEL concentration as per the manufacturer’s instructions. 74 SOLAS(14)II-2/1.6.7 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
Deck/Cargo › Holds/Tanks › Portable Gas Measuring Equipment
Issued 29 June 2017Resolved
1840 - Crew was unfamiliar with calibration procedures for all portable gas detectors on board. Crew was unable to provide sufficient calibration gas for the detectors. Only one bottle of non-expired calibration gas was produced. During calibration the bottle quickly emptied due to a leak in the tubes being used. 74 SOLAS (2001 Cons) II-2/59.5 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
1830 - The steam turbine for the #4 cargo pump has disconnected oil lines for the trip servo-motor. The overspeed, as well as local and remote emergency shutdowns, are potentially affected by this condition. Vessel is not to use the #4 cargo pump in US waters until emergency shutdowns are verified. 74 SOLAS (04) II-1/27.1, 33 CFR 155.780(a) 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
Deck/Cargo › Holds/Tanks › Tank Level Monitoring Device
Issued 29 June 2017Resolved
1840 - This shall be accomplished by high-level alarms or overflow control systems, together with gauging devices and cargo tank filling procedures. The port slop tank closed gauging and overfill devices are inoperable. Vessel is not to utilize the port slop tank in US waters until rectified. 74 SOLAS (2001 Cons.)II-2/59.1.6 46 CFR 39.2003(a) 17abc amended to 40abc on 2JUL17
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 2 August 2017
Resolved 6 October 2017
Resolution: Received appropriate documentation from class.
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Service
Issued 29 June 2017Resolved
0720 - The portable fire extinguishers in the cargo pump room have not been inspected by the crew since April 2017. Monthly inspections are required by the company. 74 SOLAS (14) II-2/14.2.2.1 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
Engineering › Lubricating Oil Service System › Piping
Issued 29 June 2017Resolved
0999 - The hydraulic delivery line on the starboard side main deck is wasted in multiple locations as evident by excessive amounts of tape and paint on the piping. In particular, the line appears to be corroded IWO the IG drop line for tanks 6S and 2S. 74 SOLAS (2004) II-1/26.5 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
Fire Fighting › Fire Hoses › Condition
Issued 29 June 2017Resolved
0720 - The fire hose box IWO #5 cargo tank is cracked and showed evidence of salt water corrosion on the hose nozzle inside the box. Crew was able to demonstrate functionality of the hose nozzle after conducting maintenance on the nozzle. 74 SOLAS (14) II-2/14.2.1.2 17abc
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 June 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.
Deck/Cargo › Vapor Control Systems › Piping/Hoses
Issued 29 June 2017Resolved
1899 - Each vessel vapor connection flange face must have a permanent stud projecting outward that has a 0.5 inch diameter and is at least 1 inch long. The vapor flange on the starboard side aft vapor connection is missing the permanent stud. 46 CFR 39.2001(j) 40c
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 29 July 2017
Resolved 2 July 2017
Resolution: Received class/flag reports attesting to repairs. See attached documents.