Records from 2018 to 2023. Most recent: inspection, 25 October 2023.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Masters responsibility and authority
Issued 21 March 2023
Resolved
The company should ensure that the safety management system operating on board the ship contains a clear statement emphasizing the master’s authority. The company should establish in the safety management system that the master has the overriding authority and the responsibility to make decisions with respect to safety and pollution prevention and to request the company’s assistance as may be necessary. Master failed to report to company continuous leaks and maintenance issues regarding the main diesel engine. Demonstrated systematic breakdown; require an external ISM audit.
74 SOLAS (20) IX/3.1 ISM Part A.5.2
Action required: 30 - Ship detained
Resolved 25 March 2023
Resolution: DNV conducted survey/safety audit
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 21 March 2023
Resolved
The purpose of this regulation is to prevent the ignition of combustible materials or flammable liquids. PSCOs identified excessive fuel leaks from the stbd main engine and the fuel supply line near injectors #4 and #5. PSCOs also observed excessive accumulation of oil in the bilge and soaked lagging.
74 SOLAS (04) II-2/4
Action required: 30 - Ship detained
Resolved 25 March 2023
Resolution: Vessel replaced fuel o rings/couplings and replaced and cleaned all lagging and bilges.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 21 March 2023
Resolved
All access openings in bulkheads at ends of enclosed superstructures shall be fitted with doors of steel or other equivalent material. Permanently and strongly attached to the bulkhead and weathertight when closed. PSCOs observed daylight through steel door to paint locker from a wasted gasket and a loose door handle located on the main deck.
ICLL 12(1)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 25 March 2023
Resolution: Gasket and door handle repair by crew.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 30 November 2022
Resolved
Def 01: The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. On 30NOV22, Biscayne Bay Pilots notified USCG Sector Miami that during departure checks the vessel's main engine overheated which resulted in loss of power. 74SOLAS(04 CON) 1/11(a) 17bc.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 December 2022
Resolution: Received RO attesting to repair & proper operation of M/E.
12 - Dangerous Goods › N/A - No Subsystem › Dangerous goods / harmful substances in pack. form
Issued 12 November 2022
Resolved
Cylinders must alwaays be secured and when not in use, they must be stowed in a rack in an upright position. Stowage of oxygen and aceteylene cylinders were stored directly on the deck and kept in multiple locations on open deck.
46 CFR 147.60 (b)(2)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 November 2022
Resolution: Received Class survey statement attesting to the adequate stowage of oxygen and acetylene cylinders.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 12 November 2022
Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be in working condition and ready for immediate use. Stbd side lifebouy found stowed in bracked tht was loose and not secured to bulkhead.
74 SOLAS (04) III/20.2
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 November 2022
Resolution: Temporary repairs conducted by crew. DNV approved temporary repairs, issued condition of class for permanent repairs due 31DEC2022.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 12 November 2022
Resolved
The purpose of this regulation is to prevent the ignition of combustible material or flammable liquids. For this pupose, the following functional requirements shall be met...means shall be provided for controlling leaks of flammable liquids. Leak of fuel oil was found coming from return line on main engine. Witness temp repair conducted by the crew at bilge deck plate level. Additionally, PSCO observed leaking flange from low pressure fuel pipe on stbd side bilge deck level.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 13 November 2022
Resolution: Attending DNV surveyor approved temporary repairs conducted by the crew.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Reports of non-conf., accidents & hazardous occur.
Issued 9 November 2022
Resolved
The company should establish procedures to ensure that the ship is maintained in conformity with the provisions of the relevant rules and regulations and with any additional requirements which may be established by the company. Due to the objective evidence in the below deficiencies, the vessel is not in substantial compliance with the relevant conventions, calling into question the adequacy and implementation of the vessel's SMS under the ISM code. PSCO's collected objective evidence that the vessel is not reporting all non-conformities or their causes to the company. This includes fuel leaks from the main engine, leaking fuel valve, fuel filters, and modification of remote quick closing valves. The vessel could not produce evidence that the company was made aware of the serious non-conformities discovered onboard. An ISM external audit is required.
74SOLAS(20)IX/3.1 ISM Code 10.2.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: DNV conducted ISM External Audit on 11&12 NOV 2022. 03 new non-conformities issued with 11FEB2023 due date. See attached Audit Report.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 9 November 2022
Resolved
Means shall be provided to control leaks of flammable liquids. PSCO's identified excessive fuel leaks from main engine crank case, fuel filters, and cylinders. Excessive fuel leaks were also observed from valves and piping on fuel oil system. Hydraulic oil was also observed inside the base of the BWTS control switchboard. Additionally, crew was found to be using buckets, plastic sheets, cardboard, and other unapproved means to capture leaks.
74SOLAS(04) II-2/4.1.1
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: Lube Oil and Fuel Leaks repaired to the satisfaction of Class. See attached survey statement. PSCO witnessed Main Engine and Auxiliary Engine running. Major leak from flywheel o-ring repair held and not leaking. Minor Lube Oil leaks observed.
14 - Pollution Prevention › 141 - MARPOL Annex I › Other (MARPOL Annex I)
Issued 9 November 2022
Resolved
Each operation described in paragraph 2 of this regulation shall be fully recorded without delay in the Oil Record Book Part 1, so that all entries in the book appropriate to that operation are completed. In the Oil Record Book, item code entries were revised using whiteout instead of crossing each incorrect item in black ink, the proper method for correcting entries. Additionally, PSCO's discovered pre-signed, blank sludge receipt forms from a shore reception facility in the crew's possession.
MARPOL I/17.4
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: DNV addressed ORB entry requirements with C/E and crew. Removed pre-signed blank sludge receipts.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 9 November 2022
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Multiple valves on the HFO tank have been modified, including the disconnection of a quick-close valve.
74SOLAS(20) I/11
Condition: Placed in Improper Service
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: Valves returned to original configuration. Verified by [name withheld] survey statement for additional info.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 9 November 2022
Resolved
Means shall be provided to detect and give alarms at an early stage in case of fires near propulsion machinery. An oil mist detector was found to be inoperable, rendering it incapable of detecting an early stage of a fire.
74 SOLAS (04) II-1/47.1.2
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: Oil Mist Dectection system is taken offline when Main Engine is not in operation. PSCO witnness Oil Mist System in operation with Main Engine running.
09 - Working and Living Conditions › 091 - Living Conditions › Cleanliness
Issued 9 November 2022
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Sewage pipe was observed wasted and leaking on deck near main engine
74SOLAS(20) I/11
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: DNV Surveyor verified pipe and confirmed that the sewage pipe is not leaking. That the leak is condensation but that the corrosion/wastage of the pipe requires attention. DNV issued Condition of Class to repair pipe section.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 9 November 2022
Resolved
Where the contents and use of a space are such that there is doubt as to its classification for the purpose of this regulation, or where it is possible to assign two or more classifications to a space, it shall be treated as a space within the relevant category having the most stringent boundary requirements. Multiple void spaces are being left open and entered by ship’s crew for use of storage of electronics, insulation, chemicals, and other items.
74SOLAS(04) II-2/9.2.3.3.2.2
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: PSCO observed all void spaces secured with all bolts.
14 - Pollution Prevention › 145 - MARPOL Annex V › Garbage management plan
Issued 9 November 2022
Resolved
Every ship of 100 gross tonnage...shall carry a garbage management plan which the crew shall follow...providing written procedures for collecting, storing, and disposing of garbage. Several large trash bags filled with oily rags were found lying on deck in a ship’s storage room, in a location with no properly placed waste receptacles
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: PSCO witnessed oily rags and other waste being stored in adequate receptacles.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 9 November 2022
Resolved
Maintenance, testing and inspections shall be carried out based on the guidelines developed by the Organization and in a manner having due regard to ensuring the reliability of fire-fighting systems and appliances. Multiple portable fire extinguishers were not inspected since September.
74SOLAS(04) II-2/14.2.2.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: DNV attested to all portable fire extinguishers being inspected in his presence. PSCO conducted spot check of monthly inspections of fire extinguishers on board.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 9 November 2022
Resolved
In a ship in which oil fuel is used, the arrangements for the storage, distribution and utilization of the oil fuel shall be as such to ensure the safety of the ship and persons on board. Bunker fuel samples are being stored in the paint locker side shell longitudinals, not secured for sea.
74SOLAS(04) II-2/4.2.2
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: Bunker samples storage in paint locker properly secured for sea.
99 - Other › N/A - No Subsystem › Other (SOLAS operational)
Issued 9 November 2022
Resolved
Main and emergency switchboards shall be so arranged as to give easy access as may be needed to apparatus and equipment, without danger to personnel. Excessive storage behind switchboard in engine room is impeding access to equipment.
74SOLAS(04) II-1/45.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: PSCO witnessed areas behind switchboards cleared from stored items.
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Construction (including exempt.)
Issued 8 November 2022
Resolved
..The master or owner of the ship shall report at the earliest opportunity to the Administration, the nominated surveyor or recognized organization responsible for issuing the relevant certificate, who shall cause investigations to be initiated to determine whether a survey, as required by regulations 7,8,9 is necessary. R.O was aware of conditions onboard the vessel and issued short term Safety Construction Certificate on 11/7/22, one day before the ship's arrival and before further inspection could be undertaken.
74SOLAS(04)I/11(c)
Condition: Improper/Lack of Maintenance
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: DNV postponed expired Conditions of Class and Control Actions to protect vessel and DNV from poetential PSC and/or third party questions on arrival. Questions on DNV/RO actions remain and being forwarded to CVC-2.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 8 November 2022
Resolved
Doors required to be self-closing shall not be fitted with hold back-hooks. Several "A" Class fire doors which are required by the fire Control Plan to be self-closing were found blocked in the open position by wooden wedges. This includes self-closing doors in the machinery space boundaries and the main stairwell.
74SOLAS(04)II-2/4.2.2
Condition: Placed in Improper Service
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: Blocks and hold backs removed from selfclosing doors. Verified by [name withheld] instructed crew on requirements. See survey report.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 8 November 2022
Resolved
Oil fuel pipes shall be fitted with a cock or valve directly on the tank capable of being closed from a safe position outside the safe position outside the space concerned in the event of a fire occurring in the space in which such tanks are situated. Fuel oil quick close valve was found blocked by a fabricated metal sheet and tie on settling tank.
74SOLAS(04) II-2/4/2.2.3.4
Condition: Placed in Improper Service
Action required: 30 - Ship detained
Resolved 12 November 2022
Resolution: Fabricated block on remote shutoff valve removed. PSCO tested all HFO remote shutoff valves satifactorily. See Survey Statement for additional info.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 8 November 2022
Resolved
The level of knowledge of the material listed in column 2 of table A-III/1 shall be sufficient for engineer officers to carry out their watchkeeping duties. Chief Engineer was not able to operate oily water separator in accordance with manufacturer’s instructions.
STCW III/4
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: [name withheld] demonstrated knowledge on OWS operation in prescence of PSCOs.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 8 November 2022
Resolved
Fire detection and fire alarm systems shall be kept in good order so as to ensure their required performance if a fire occurs. The crew conducted the flame detector test using lighter without reference to onboard procedures, which were not available to PSCO’s upon request.
74 SOLAS (04) II-2/14.2.1.1.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: Approved Flame detector testing device ordered.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 8 November 2022
Resolved
A ship must have a placard of at least 5 by 8 inches, made of durable material fixed in a conspicuous place in each machinery space, or at the bilge and ballast pump control station, stating the following: Discharge of Oil Prohibited... Vessel did not have required placard in each machinery space nor at the bilge control station
33CFR155.450(c)
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 November 2022
Resolution: Placard provided by DNV inadequate. PSCO provided adequate placard sticker and witness C/E attach it to bilge/ballast pumping control station.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 8 November 2022
Resolved
Cables and wiring shall be installed and supported in such a manner as to avoid chaffing or other damage. Port Side deck light and switch for search light found to be fully supported by zip ties and electrical socket on port side found to be attached to mounting bracket that was wasted off bulkhead and left electrical installation insupported.
74 SOLAS (20) II-1/45.5.5
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 November 2022
Resolution: Temporary repairs conducted by crew and approved by DNV surveyor. Condition of class issued for permanent repairs due 31DEC2022.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 8 November 2022
Resolved
The following fire protection systems shall be kept in good order so as to ensure their required performance if a fire occurs... FIre detection and fire alarm system. Smoke detector in paint storage room was found to be covered by a plastic bag. Vessel received ISM audit on 12NOV2022 and Class survey on 12NOV2022 addressing this specific issue with the crew.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 13 November 2022
Resolution: DNV surveyor witnessed pastic bag removed from smoke detector.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 8 November 2022
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provision of the present regulation. Air handler on second level of the engine room stbd side was observed to be in damaged condition with combing coming apart.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2022
Resolution: DNV issued condition of class due 11FEB2022 for the repairs to ventilation ducts
09 - Working and Living Conditions › 092 - Working Conditions › Structural features (ship)
Issued 8 November 2022
Resolved
Efficient guard rails or bulwarks shall be fitted to all exposed parts of the freeboard and supersctructure decks, Guard rail on stbd side main deck was found to be snapped and broken.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 13 November 2022
Resolution: Attending DNV Surveyor issued condition of class for guard rail repair due 31DEC2022.
10 - Safety of Navigation › N/A - No Subsystem › Echo sounder
Issued 30 August 2022
Resolved
ALL SHIPS OF 300 GROSS TONNAGE AND UPWARDS … SHALL … BE FITTED WITH: AN ECHO-SOUNDING DEVICE, OR OTHER ELECTRONIC MEANS, TO MEASURE AND DISPLAY THE AVAILABLE DEPTH OF WATER. PSCOs OBSERVED THAT THE ECHO-SOUNDING DEVICE WAS NON-OPERATIONAL.
74 SOLAS (20CONS) V/19.2.3.1. 16ac.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 September 2022
Resolved 1 September 2022
Resolution: Received work order. Equipment was tested and its fully operational.
02 - Structural Conditions › N/A - No Subsystem › Loading/Ballast condition
Issued 30 August 2022
Resolved
THE RING … SHALL BE PAINTED IN WHITE OR YELLOW ON A DARK GROUND OR IN BLACK ON A LIGHT GROUND. THE RING WAS NOT PAINTED WHITE OR YELLOW ON A DARK GROUND OR IN BLACK ON A LIGHT GROUND. PSCOs OBSERVED WORN PAINT ON LOADLINE.
ICLL ANNEX I REG 8. 40ac.
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 1 September 2022
Resolution: Received survey with pictures of ring being painted. Rectified.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 25 February 2022
Resolved
Main and emergency switchboards shall be so arranged … . The sides and the rear … shall be suitably guarded. PSCOs observed automatic remote control valve cabinet panel, located on the port side of vessel within the engine room, was observed to be open and unprotected.
74 SOLAS (04 Cons) II-1/45.2
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 March 2022
Resolved 8 March 2022
Resolution: PSCO's received satisfactory evidence of the defiency being resolved. Photographs and RO approval was obtained through email. Deficiency closed.
10 - Safety of Navigation › N/A - No Subsystem › Radar
Issued 13 February 2022
Resolved
ALL SHIPS OF 300 GROSS TONNAGE AND UPWARDS...SHALL BE FITTED WITH A 9GHZ RADAR. THE VESSEL'S X-BAND RADAR IS INOPERABLE
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 13 February 2022
Resolved 13 February 2022
Resolution: Received report from DNV allowing vessel to sail.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 February 2021
Resolved
All lifesaving appliances and arrangements shall comply with the applicable requirements of the code. Every lifebuoy shall be fitted with a grabline... The grabline shall be secured at four equidistant points around the circumference of the buoy to form four equal loops. All lifebuoys on deck maintain improperly fitted grablines.
74SOLA(2014) III/34
LSA Code 2.1.1.8
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 February 2021
Resolved 20 February 2021
Resolution: Attestation received from DNV GL indicating grablines renewed on all lifebuoys
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 11 February 2021
Resolved
The fire integrity of the divisions shall be maintained at openings and penetrations. Forward Port switch room class "A" door has lines tied through doorframe preventing the door from closing.
74SOLAS (2014) II-2/9.1.3
Action required: 10 - Deficiency Rectified
Resolved 11 February 2021
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 February 2021
Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be... ready for immediate use. Port side bridge wing lifebuoy quick-release handle was broken.
74SOLAS(2014) III/20.2
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 February 2021
Resolved 20 February 2021
Resolution: Attestation received from DNV GL indicating Quick Release Handle renewed.
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 29 January 2021
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. While loading containers onto the vessel, the crane operator inadvertently struck the inside of the cargo hold fracturing the weld on the fuel tank between holds two and three causing a discharge of #6 oil into the hold. A repair plan for the damaged tank must be submitted and approved by Class and the U.S. Coast Guard prior to vessel departure.
74 SOLAS(2004 CONS.) CH. I/REG 11.a
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Due 29 January 2021
Resolved 29 January 2021
Resolution: Vessel provided Classification Society Survey Report attesting to the temporary repairs and issuing the vessel a condition of class to effect permanent repairs by 29 MAR 2021.
Engineering › Fuel Oil Service System › Filter
Issued 9 May 2018
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Vessel lost propulsion en route to San Juan, Puerto Rico. Ship engineers were able to rectify the issue. Class report to follow. 74SOLAS(14)I/11(a)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 May 2018
Resolution: CFS panjang supplied a class report concering the defective flow meter and corrective action taken.
Lifesaving › Line-Throwing Appliances › Lines
Issued 9 May 2018
Resolved
Every line throwing appliance shall include not less than four lines, each having a breaking strength of not less than 2 KN. Vessel only had 02 line throwing appliances. 74SOLAS(14)III/18 LSA Code 7.1.1.3
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 May 2018
Resolution: CFS Panjang supplied documentation proving that 2 additional line throwers had been purchased and were on board.
Operations/Management › Lifesaving › Op Readiness/Maintenance/Inspection
Issued 9 May 2018
Resolved
Every ship to which chapter I applies shall carry an appropriate portable atmosphere testing instrument. Suitable means shall be provided for the calibration of all such instruments. Vessel's onboard portable atmosphere testing instruments are not calibrated and vessel does not have means for calibration onboard.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 May 2018
Resolved 25 May 2018
Resolution: Received report from class accepting the shore side calibration of vessel's portable atmosphere testing instruments.
Operations/Management › Port and Waterways Safety › Notice of Hazardous Condition
Issued 9 May 2018
Resolved
The vessel secured propulsion at approximately 0150 on 10 MAY 18 and was adrift for approximately 8 hours before the Coast Guard was notified.
Action required: 10 - Deficiency Rectified
Due 10 May 2018
Resolved 10 May 2018