Records from 2016 to 2026. Most recent: inspection, 15 April 2026.
Documentation record
Registered dimensions (L × B × D)45.0 ft × 14.0 ft × 3.0 ft
Registered tonnagegross 15 / net 15
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderALUMA MARINE · HARVEY, LA, UNITED STATES · built 2016
Hull materialAluminum
PropulsionGasoline Outboard
Hull shapeBox
Hull configurationMonohull
Hailing portLAFITTE, LA
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 4 June 2026 · expires 30 June 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it15 - Simplified, Gross Ton
15 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Inspection history · 10
15 April 2026
COI Inspection · Drydock Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 8344896
17 February 2025
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 8080367
20 June 2023
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7697222
6 June 2022
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7469867
20 April 2021
COI Inspection · Drydock Exam · Internal Structural Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7168843
9 July 2020
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7001548
17 April 2019
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6664509
5 April 2018
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6381931
13 April 2017
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6121573
18 March 2016
COI Inspection · Construction Oversight
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5836069
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 April 2026
No resolution recorded
Gasoline fill pipes and sounding pipes must extend to within one-half of their diameter from the bottom of the tank. The gasoline tank was not fitted with a fill pipe that terminates near the bottom of the tank. Submit a plan of repair within 30 days to the cognizant OCMI.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 16 May 2026 — due date passed with no resolution recorded
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 7 April 2025
Resolved
The Certificate of Inspection must be posted under glass or other suitable transparent material, such that all pages are visible, in a conspicuous place on the vessel where observation by passengers is likely. If posting is impracticable, such as in an open boat, the certificates must be kept on board in a weathertight container readily available for use by the crew and display to passengers and others on request. MI observed no COI was posted in practicable location.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2025
Resolved 22 April 2025
Resolution: Witnessed satisfactory placement of COI at the vessels opperation station.
01 - Certificates & Documentation › 013 - Documents › Stability Information Booklet
Issued 7 April 2025
Resolved
A vessel must be provided with a stability letter, the stability letter must be posted under glass or other suitable transparent material, such that all pages are visible, at the operating station of the vessel. If posting is impracticable, the stability letter must be kept on board in a weathertight container readily available for use by the crew and display to passengers and others on request. MI observed no Stability letter was posted in practicable location.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2025
Resolved 22 April 2025
Resolution: Witnessed satisfactory placement of the Stability Letter at the vessels opperating station.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage of rescue boats
Issued 7 April 2025
Resolved
Each floating waterlight must be approved in accordance with § 161.010 in subchapter Q, or other standard specified by the Commandant, including, but not limited to, approval series 160.110. MI observed incompatible alkaline batteries were installed.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2025
Resolved 22 April 2025
Resolution: MI reinspected float light. Vessel replaced alkaline batteries with Lithium Ion, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 February 2025
Resolved
Remote fuel shutoff stations must be marked in clearly legible letters at least 25 millimeters (1 inch) high indicating purpose of the valve and direction of operation. MI observed no labeling at either fuel shut off valve.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 April 2025
Resolved 22 April 2025
Resolution: MI witnessed satisfactory labeling of fuel shut off valves. All Sat.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 20 June 2023
Resolved
Shutoff valves, installed so as to close against the fuel flow, must be fitted in the fuel supply lines, one at the tank connection and one at the engine end of the fuel line to stop fuel flow when servicing accessories. MI observed valve handle for fuel supply line at the tank missing and not installed.
46 CFR 182.455(b)(4) 10C
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 20 June 2023
Resolved 20 June 2023
Resolution: Valve handle and direction was installed, labeled, and tested. All sat
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 20 June 2023
Resolved
Remote fuel shutoff stations must be marked in clearly legible letters at least 25 millimeters (1 inch) high indicating purpose of the valve and direction of operation. MI observed fuel valves not labeled.
46 CFR 185.608 10c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 20 June 2023
Resolved 20 June 2023
Resolution: Valves were labeled and are all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 20 June 2023
Resolved
Each life jacket, immersion suit, and life ring buoy must be marked in clearly legible block capital letters with the vessel's name. MI observed several unlabeled life jackets on vessel.
46 CFR 185.604(b) 16c
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 4 July 2023
Resolved 20 June 2023
Resolution: Life jackets were re-labeled accordingly with correct information. all sat
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 20 June 2023
Resolved
The number and identification of the items stowed inside, and their sizes, must be marked in clearly legible letters and numbers on each container for life jackets and immersion suits. MI observed stowage locations and quantities not marked as required.
46 CFR 185.604(f) 16c
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 12 July 2023
Resolution: Storage locations were re-labeled with lifejacket size and quantities. all sat
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 20 June 2023
Resolved
The Certificate of Inspection and any SOLAS Certificates must be posted under glass or other suitable transparent material. If posting is impracticable, such as in an open boat, the certificates must be kept on board in a weather-tight container. Certificate of Inspection, Stability Letter, and Certificate of Documentation found not kept on board. Retain copy on board vessel.
46 CFR 176.302 16C
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 12 July 2023
Resolution: Certificate were laminated and placed onboard in binder. all sat
14 - Pollution Prevention › 145 - MARPOL Annex V › Placards
Issued 20 June 2023
Resolved
A vessel must comply with the applicable design, equipment, personnel procedures, and record requirements of 33 CFR Parts 151, 155, and 156. The master or person in charge of a ship, including a drilling rig or platform, to which this section applies shall ensure that one or more placards meeting the requirements of this section are displayed in prominent locations. MI observed no garbage placard installed.
46 CFR 184.702
33 CFR 151.59(a) 16C
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 July 2023
Resolved 12 July 2023
Resolution: Proper garbage placard was installed by the helm location. all sat
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 23 June 2022
Resolved
A vessel must carry one floating waterlight, unless it is limited to daytime operation, in which case no floating waterlight is required.
Each life jacket, immersion suit, and ring life buoy must be marked in clearly legible block capital letters with the vessel's name.
Life ring buoy on board was missing floating waterlight and vessel's name.
Action required: 10 - Deficiency Rectified
Resolved 23 June 2022
Resolution: Light and vessel's name added on scene
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 20 April 2021
Resolved
46CFR180.71(a) - 50C - An adult life jacket must be provided for each person carried on board a vessel. While checking vessel's life jackets, inspector's noted that 05 life jackets were ripped and faded, rendering them ineffective. Life jackets were stowed in an overhead bracket, causing them to be subjected to extreme heat, which resulted in premature wear. Vessel representative needs to provide new stowage plan to prevent further degradation to the satisfaction of the attending USCG Marine Inspector.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 May 2021
Resolved 17 May 2021
Resolution: Vessel rep sent picture of lifejackets having been relocated to underneath seats.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 April 2019
Resolved
Wire connectors were not of the captive type at the 12vDC screw type terminal block.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 May 2019
Resolved 20 May 2019
Resolution: Non-captive wire connectors were replaced with ring type connectors.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 April 2019
Resolved
Overcurrent protection for the 12vDC electrical system used non-approved blade type fuses. Fuses must be the cartridge type that are UL-listed.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 May 2019
Resolved 20 May 2019
Resolution: Non-approved fuses were replaced with cartridge type fuses and compatable fuse box.