SIERRA is a freight ship. The Coast Guard has recorded 7 inspections in 2016, along with 13 deficiencies and 2 operational controls.

Records in 2016. Most recent: inspection, 15 April 2016.

Built
Not recorded
Last inspected
15 April 2016
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

This record may be incomplete: the most recent inspection recorded for this vessel was 10 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Bulk Carrier class in Maury's sources begin in 2016.

Inspection record

Last inspected 15 April 2016
…with no type recorded4
Operational controls None recorded without a removal date
Years with a record 1 calendar year (2016)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9587685
1382190
Flag
LIBERIA
Maury page id
psix-1382190

Documentation record

Tonnage as PSIX records it24319 - Dead Weight, Metric Ton
31130 - Displacement, Metric Ton
15601 - Convention (Subpart B), Gross Ton
8183 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report

A report is not offered for this hull. Its Coast Guard record spans fewer than two calendar years. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 7

15 April 2016 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5854920
5 April 2016 ISPS II Exam · PII Safety Exam · Ballast Water Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5842093
1 April 2016 Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5845559
1 April 2016 COE-Offshore
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5845623
1 April 2016 Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5845626
1 April 2016 Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5856876
28 March 2016 Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 5842170

Deficiency record · 13

Electrical › Electric Generation Source (service) › Number of Sources
Issued 5 April 2016 Resolved
1430-AUXILIARY ENGINES-[name withheld] THE #1 & #3 SSDG'S TO BE OUT OF SERVICE WITH NO DISPENSATION FROM FLAG. PROVIDE CLASS REPORT ATTESTING TO PROPER OPERATION OF THE #1 & #3 SSDG'S PRIOR TO MOVEMENT-60a-SOLAS II-1/41
Action required: 705 - Other - as specified
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating #1 SSDG was repaired with spare parts and tested satisfactorily with electrical load in parallel with #2 SSDG. Vessel was issued a dispensation from Flag to operate without #3 SSDG until 04JUN16.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Piping
Issued 5 April 2016 Resolved
0725-FIXED FIRE EXTINGUISHING-[name withheld] HOSES BETWEEN CO2 TANKS AND CO2 MANIFOLD TO BE DRY ROTTED. PROVIDE CLASS REPORT ATTESTING TO INSTALLATION PRIOR TO MOVEMENT-60a-SOLAS II-2/14.2.1.2
Action required: 705 - Other - as specified
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating new CO2 hoses have ben procured from shore company and they have been installed by same shore side company.
Fire Fighting › Remote Fuel Shutoff › General
Issued 5 April 2016 Resolved
0710-FIRE PREVENTION-[name withheld] OPERATING THE EDG QUICK CLOSING VALVE TO BE PARTED, RENDERING THE VALVE INOPERABLE FROM OUTSIDE THE SPACE. PROVIDE CLASS REPORT ATTESTING TO PROPER OPERATION PRIOR TO MOVEMENT-60a-SOLAS II-2/4.2.2.3.4
Action required: 705 - Other - as specified
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating ships crew installed new cable and assembly was tested satisfactorily by class surveyor.
Lifesaving › Lifeboat › Propulsion Starting System
Issued 5 April 2016 Resolved
0610-LIFEBOATS-[name withheld] LIFEBOAT WAS ONLY ABLE TO START THE ENGIONE WHEN BOTH BATTERIES ARE IN PARALLEL. PROVIDE CLASS REPORT ATTESTING TO PROPER OPERATION OF BOTH BATTERIES ON INDIVIDUAL STARTING CIRCUITS-17a-SOLAS III/34 LSA CODE 4.4.6.2
Action required: 17 - Rectify deficiencies prior to departure
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating two new batteries were procured and installed. Both starting circuits were tested satisfactorily by class surveyor.
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 5 April 2016 Resolved
0715-DETECTION-[name withheld] OVER #2SSDG COVERED WITH A PLASTIC BAG, RENDERING IT INOPERABLE. WHEN BAG WAS REMOVED DETECTOR WOULD NOT OPERATE WHEN TESTED. UPON CLEANING, DETECTOR WAS ABLE TO OPERATE. PROVIDE CLASS REPORT ATTESTING TO PROPER OPERATION OF FIRE DETECTION SYSTEM-17a-SOLAS II-2/7.4.2
Action required: 17 - Rectify deficiencies prior to departure
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating fixed fire detection system was tested satisfactorily.
Engineering › Diesel Engine (propulsion-direct drive) › Cylinder Head
Issued 5 April 2016 Resolved
1410-PROPULSION MAIN ENGINE-[name withheld] LEAKS ON THE MAIN ENGINE CYLINDERS #1 & #7. PROVIDE CLASS REPORT UPON COMPLETION OF REPAIRS-16a-SOLAS I/11
Action required: 705 - Other - as specified
Due 19 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating cylinders #1 & #7 were overhauled by ships crew and tested satisfactorily by class surveyor.
Communications › Radio Communications › Emergency Source of Power
Issued 5 April 2016 Resolved
1677-RESERVE SOURCES OF ENERGY-[name withheld] BOUGHT BATTERY CHARGERS IN THE GMDSS BATTERY ROOM WITH POWER CABLES LEADING OUT OF SPACE AND WIRED INTO AN ELECTRICAL FIXTURE IN AN ADJACENT SPACE. PROVIDE CLARIFICATION & ATTESTATION TO OPERATIONAL SAFETY FROM CLASS-16a-SOLAS IV/13.1
Action required: 705 - Other - as specified
Due 19 April 2016
Resolved 25 April 2016
Resolution: Received, reviewed and accepted clas report from RINA stating new GMDSS battery charger has been installed and tested satisfactorily.
Construction/Loadline › Structures › Door
Issued 5 April 2016 Resolved
1270-DOORS-[name withheld] ROOM DOOR WAS REMOVED AND NOT IN PLACE. PROVIDE CLASS REPORT ATTESTING TO REPAIRS-16a-SOLAS I/11
Action required: 705 - Other - as specified
Due 19 April 2016
Resolved 25 April 2016
Resolution: Received, reviewed and accepted class report from RINA stating new door has been installed.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 April 2016 Resolved
0950-ELEC EQUIPMENT IN GENERAL-[name withheld] JUNCTION BOXES INSTALLED BY THE CREW THAT WERE NOT INSTALLED IAW ORIGINAL DESIGN OF VESSEL. PROVIDE REPORT FROM CLASS ATTESTING TO INSTALLATIONS-16a-SOLAS I/11
Action required: 705 - Other - as specified
Due 19 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating all junction boxes were repaired satisfactorily.
Operations/Management › Pollution › Control of Discharge of Oil
Issued 5 April 2016 Resolved
1740-OIL DISCHARGE MONITOR SYSTEM-ENGINEERING DEPT DID NOT KNOW HOW TO RECALL INFORMATION FROM THE OIL CONTENT METER MEMORY. PROVIDE CORRECTIVE ACTION PLAN FROM COMPANY WITH CONCURRENCE FROM FLAG-40b-MARPOL I/11 MEPC 107(49)
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating training was conducted for engineering department and engineering officers were able to succesfully obtain recoreded data from OCM.
Operations/Management › Pollution › Compliance with Transfer Procedures
Issued 5 April 2016 Resolved
0199-OTHER-C/E WAS UNABLE TO PROVIDE SUITABLE TRANSFER PROCEDURES. PROVIDE TRANSFER PROCEDURES PRIOR TO CONDUCTING BUNKERING OPERATIONS-c-33CFR155.720
Action required: 703 - Prior to bunkering operations
Due 5 April 2016
Resolved 8 April 2016
Resolution: Received, reviewed and accepted approved transfer procedures for bunkering.
Engineering › Fuel Oil Storage/Transfer System › Piping
Issued 5 April 2016 Resolved
0899-OTHER ACCIDENT PREVENTION-C/E WAS UNABLE TO PROVIDE RECORDS OF BUNKER LINE HYDROSTATIC TESTING. PROVIDE DOCUMENTATION ATTESTING TO LIQUID HYDROSTATIC TESTING OF BUNKER TRANSFER PIPING PRIOR TO BUNKERING OPERATIONS IN THE UNITED STATES-c-33CFR156.170
Action required: 703 - Prior to bunkering operations
Due 5 April 2016
Resolved 8 April 2016
Resolution: Received, reviewed and accepted documentation stating hydrostatic test was completed.
Documentation › Safety Management System › Conformity Maintenance Procedures
Issued 5 April 2016 Resolved
2560-COMPANY VERIFICATION-DUE TO ABOVE LISTED DEFICIENCIES, REQUEST COMPANY CONDUCT AN INTERNAL ISM AUDIT-17a-SOLAS IX/5 ISM CODE 12.2
Action required: 17 - Rectify deficiencies prior to departure
Due 5 April 2016
Resolved 14 April 2016
Resolution: Received class report from RINA stating company supervisor conducted internal audit.