Records from 2019 to 2026. Most recent: inspection, 9 May 2026.
Inspection history · 9
9 May 2026
Administrative Inspection · COC-GAS Annual
Administrative · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8369683
26 June 2025
PSC B · COC-GAS Renew
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 8162550
14 February 2024
PSC B · COC-GAS Renew · Administrative Inspection
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7865166
22 August 2022
COC-GAS Annual · PSC B
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7538391
14 November 2021
Administrative Inspection
Administrative · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 7350488
17 September 2021
Deficiency Check · COC-GAS Renew · PSC B
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7306364
13 August 2019
Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6783596
9 August 2019
Deficiency Check · Ballast Water Examination · ISPS II Exam · COC-GAS Renew
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6766052
9 August 2019
Special
Type not classified · Liquefied Gas Carrier National Center of Expertise · Activity 6794987
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 22 August 2022
Resolved
Pressure relief valves should be set and sealed by a competent authority acceptable to the administration and a record of this action, including the valves of set pressure, should be retained aboard the ship.
PSCO ovserved cargo tanks relief valve 2PS and 2SB were serviced and resealed with new wire on 24 DEC 2021, however, class acceptance document is dated 03 JUL2019.
1993 IGC 8.2.5
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 September 2022
Resolved 29 August 2022
Resolution: Received required documentation attesting to the SRV cert being approved by class.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 September 2021
Resolved
17SOALS14/VII/13.1
93IGC/10.2.4.1
Ligthting fittings should have pressorized enclosures or should be of flameproof type.
PSCO found a cracked lighting fixture cover in the cargo compressor room.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 17 September 2021
Resolved 17 September 2021
Resolution: Cracked lighting fixture cover was replaced.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 17 September 2021
Resolved
74SOLAS14 I/11
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations.
Temperature sensor insulation/protective tube has failed at the following locations: Booster pump fitting to monitoring box on deck, port manifold vapor line, port and starboard vapor temperture monitoring boxes on deck.
Condition: Improper/Lack of Maintenance
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 17 October 2021
Resolved 18 October 2021
Resolution: Class report received.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 9 August 2019
Resolved
In every installation, the position of fixed sampling heads should be determined with due regard to the density of the vapors of the products intended to be carried and the dilution from compartment purging or ventilation.
Deck store space, a space located within the compressor room and considered a gas dangerous zone as defined by the code, is not fitted with gas sampling points in the upper part of the space despite being authorized to carry anhydrous ammonia, a cargo with a vapor density of approximately .597.
93IGC 13.6.2
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 September 2019
Resolved 19 August 2019
Resolution: Conducted administrative deficiency check. Vessel operator and classification society submitted report attesting to the use of toxic portable meters in place of upper fixed detectors for lighter cargoes.