Records from 2014 to 2025. Most recent: inspection, 23 April 2025.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 23 April 2025
Resolved
Fuel lines must be accessible, protected from mechanical injury, and effectively secured against excessive movement. MI observed chaffing on fuel lines in the Engine Room.
46 CFR 182.455 (b)(3)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 8 May 2025
Resolution: Mechanic came on board to replenish the chaffed fuel lines.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 23 April 2025
Resolved
Machinery and equipment installed on each vessel must be suitable for the vessel and its operation and for the purpose intended. There was a fuel leak found in the centerline void space. Clean fuel.
46 CFR 182.100
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 9 May 2025
Resolution: Fuel in the centerline void is cleaned and crew advised not to overfill the fuel tanks or put 100% fuel next time to prevent the spill from air vent
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 23 April 2025
Resolved
Electrical equipment on a vessel must be installed and maintained to.. minimize accidental personnel contact with energized parts. Identified several dead end wires without caps/tape to in the console of the upper pilothouse.
46 CFR 183.200
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 8 May 2025
Resolution: Electricians are coming on Monday May 12th at 1:30 pm to take care off the dead end wires in upper pilothouse.
04 - Emergency Systems › N/A - No Subsystem › Muster list
Issued 23 April 2025
Resolved
The master and crew of a vessel will be familiar with the content of and have mounted at the operating station, emergency instructions containing the actions to be taken in the event of fire. No instructions posted for local operation of the fire suppression system.
46 CFR 185.510 (a)
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 9 May 2025
Resolution: Fire Suppression System instructions is printed and posted.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 23 April 2025
Resolved
A vessel must carry one floating waterlight attached to the ring life buoy. The battery in the light for the ring life buoy was expired.
46 CFR 180.70 (d) (1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 9 May 2025
Resolution: Battery in ring light is replaced
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 23 April 2025
Resolved
Ship station license present for operation of all maritime services transmitting equipment on board a vessel. FCC Radio telephony certificate was expired.
47 CFR 80.13 (b)
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 9 May 2025
Resolution: FCC cert reissued exp 2030
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for master and officers
Issued 23 April 2025
Resolved
The Coast Guard will issue a medical certificate to a mariner meeting the medical and physical standards for merchant mariners. The medical certificates onboard were expired.
46 CFR 10.301
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 9 May 2025
Resolution: Medical certificate on board
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 23 April 2025
Resolved
A first-aid kit may be considered acceptable if it meets all of the requirements of ISO 18813:2006(E) paragraph 4.12. Medications in the first aid kit were expired.
46 CFR 199.175 (b)(10)(i)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 7 May 2025
Resolved 9 May 2025
Resolution: First aid items replaced.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 9 April 2024
Resolved
Machinery and fuel tank spaces must be separated from accommodation spaces by boundaries that prevent the passage of vapors. Vapor tight boundary is not maintained due to a hole in void aft of the engine room.
46 CFR 177.405(c)
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 April 2024
Resolved 29 April 2024
Resolution: Verified photos.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 9 April 2024
Resolved
Electrical equipment on a vessel must be installed and maintained to.. minimize accidental personnel contact with energized parts. Identified three dead end wires without caps/tape to prevent from accidental electrical shock.
46 CFR 183.200
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 April 2024
Resolved 29 April 2024
Resolution: Verified removed dead end wires.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 9 April 2024
Resolved
The marine employer must have a sufficient number of alcohol testing devices readily accessible on board the vessel to determine the presence of alcohol in the system of each individual who was directly involved in the SMI. Identified expired drug alcohol swabs on board.
46 CFR 4.06-15
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 April 2024
Resolved 29 April 2024
Resolution: Verified alcohol strips.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 1 May 2023
Resolved
All wiring and cables shall be suitable for marine service and for particular installation used. Dead-end electrical wires are located in multiple spaces.
46 CFR 183.10-20(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 June 2023
Resolved 6 July 2023
Resolution: Attended vessel to confirm removal of dead end wires from fwd accomodation space, closet, and closet in passageway below main deck (fwd) of heads.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 1 May 2023
Resolved
A hatch cover must have securing devices. Hatch located in forward crew accommodation does not have securing devices. Effect repairs to the satisfaction of the attending Marine Inspector.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 June 2023
Resolved 6 July 2023
Resolution: Hatch properly secured. Attended to verify.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 1 May 2023
Resolved
At each initial and subsequent inspection for certification and re-inspection the inspector shall examine and test all items in the ship's outfit, such as ground tackle, navigation lights, compass, etc., which are required to be carried by the regulations in this sub-chapter. Navigation lights are inoperable.
46 CFR 176.25-40(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 May 2023
Resolved 6 July 2023
Resolution: Verified operation of all nav-lights.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 8 December 2022
Resolved
Each pressure type wire connector and lug must meet UL 486A (incorporated by reference; see 46 CFR 175.600) or other standard specified by the Commandant. The use of twist-on type wire nuts is permitted under the following conditions: (1) The connections must be made within an enclosure and the insulated cap of the connector must be secured to prevent loosening due to vibration; and (2) Twist-on type connectors may not be used for making joints in cables, facilitating a conductor splice, or extending the length of a circuit - MI found a loose wire in the vicinity of the bilge space underneath port side deck. Request owner/operator to secure the wire IAW 46 CFR 183.340(i)(1).
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 January 2023
Resolved 1 January 2023
Resolution: Master properly secured the wire.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 8 December 2022
Resolved
Electrical equipment on a vessel must be maintained and installed to protect passengers, crew, and other persons and the vessel from electrical hazards. Vessel had several loose wiring from inoperable electrical equipment and dead end wires. Vessel shall clear all dead end wiring, disconnected from power sources, and make all possible attempts to remove the wiring from the vessel.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 8 January 2023
Resolved 1 January 2023
Resolution: Master removed all dead end wiring.
10 - Safety of Navigation › N/A - No Subsystem › Life-saving signals
Issued 24 March 2021
Resolved
A vessel on limited coastwise route must carry six red hand flare distress signals and six orange smoke signals. Vessel has seven red flares and 2 orange smoke signals.
46 CFR 180.68(a)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 March 2021
Resolution: Operator obtained four additional red flares, bringing the total to eleven red hand flares and two orange smoke signals.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 24 March 2021
Resolved
On a vessel of at least 26 feet in length, a visual and audible alarm must be provided at the operating station to indicate a high water level in each of the following normally unmanned spaces: (1) A space with a through-hull fitting below the deepest load waterline, such as a lazarette; (2) A machinery space bilge, bilge well, shaft alley bilge, or other spaces subject to flooding from sea water piping within the space; and (3) A space with a non-watertight closure, such as a space with a non-watertight hatch on the main deck. Vessel's visual indicators for high level bilge alarms are not operable.
46 CFR 182.530(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 April 2021
Resolved 25 April 2021
Resolution: Received photographic evidence of bilge alarm light working for all spaces.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 24 March 2021
Resolved
Each watertight bulkhead must be of sufficient strength to be capable of remaining watertight with a head of water to the top of the bulkhead. Vessel has a flex hose penetrating the second forward-most watertight bulkhead without any watertight sealant.
46 CFR 179.320(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 April 2021
Resolved 25 April 2021
Resolution: Received picture of penetration in question properly sealed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 24 March 2021
Resolved
A vessel of more than 26 feet in length, but not more than 65 feet, must carry a minimum of one life buoy of not less than 24 inches in diameter. Each ring life buoy must be approved in accordance with 160.150 in subchapter Q of this chapter. The grab line shall be 3/8-inch diameter polyethylene, polypropylene, or other suitable buoyant type synthetic material having a minimum breaking strength of 1,350 pounds. Vessel's ring life buoy is not in a serviceable condition, including the grab line, which are significantly deteriorated.
46 CFR 180.170(a)(2)
46 CFR 180.170(b)(1)
46 CFR 160.050-3(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 April 2021
Resolved 25 April 2021
Resolution: Operator replaced life ring and properly rigged life line and floating light to life ring.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 24 March 2021
Resolved
Each survival craft must be secured to the vessel by a painter with a float-free link permanently attached to the vessel. Vessel's IBA painter was not connected to the float free link.
46 CFR 180.130(a)(1)
Action required: 10 - Deficiency Rectified
Resolved 24 March 2021
Resolution: Operator properly secured painter to hydrostatic release weak link prior to MI departure from vessel.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 24 March 2021
Resolved
A carbon dioxide cylinder may not be inclined more than 30° from the vertical unless fitted with flexible or bent siphon tubes, in which case it may be inclined not more than 80° from the vertical. Vessel's fixed firefighting carbon dioxide bottle is inclined past 30° and does not have an indication of being fitted with a siphon tube.
46 CFR 181.410(c)(7)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 March 2021
Resolution: Vessel provided a schematic of the CO2 bottle, which indicates a siphone tube.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 21 January 2020
Resolved
A vessel on a limited coastwise route must carry six red flares approved IAW 160.021 and six orange smoke distress signals approved IAW 160.037. Vessel is missing 3 red and 3 orange flares or approved substitutions. 46CFR180.68
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 January 2020
Resolved 22 January 2020
Resolution: 6 additional Red Flares that meet 46 CFR 160.021 were provided.
04 - Emergency Systems › N/A - No Subsystem › Functionality of Safety Systems
Issued 21 January 2020
Resolved
Each space accessible to passengers or used by crew on a regular basis must have at least two means of escape. Emergency escapes in aft berthing areas overheads have no ladders or means for a passenger to climb out. Provide means for passenger to climb out of emergency escapes. 46 CFR 177.15
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2020
Resolved 20 March 2020
Resolution: Escape ladder provided.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 January 2020
Resolved
Wiring where subject to mechanical damage shall be protected IAW the National Electrical Code. Wire run for engineroom high water alarm, engineroom U-lube system, wire in aft engine room above the racor assembly are not secured and installed properly creating the possibility for wire chaffing. 46 CFR 183.05-50 (a)(2)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2020
Resolved 20 March 2020
Resolution: Properly installed wiring.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 21 January 2020
Resolved
Penetrations and openings in watertight bulkheads must have a means to make them watertight. Port Engineroom bulkhead has through hull penetration that is not watertight. 46CFR171.114(a)(2)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 February 2020
Resolved 5 March 2020
Resolution: Holes in bulkhead made watertight.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 3 April 2019
Resolved
All wiring and cables shall be suitable for marine service and for the particular installation used. Lighting cable located starboard side forward bulkhead next to entrance of engine room has exposed splice utilizing twist connectors. 46 CFR 183.10-20
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 9 May 2019
Resolution: Junction box installed and wires spliced in junction box.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 3 April 2019
Resolved
At each vessel inspection, hazardous situations must be corrected. Vessel sign limiting 11 passengers to upper deck is missing. 46 CFR 184.502
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: Signage installed limiting 8 passengers to the upperdeck.
10 - Safety of Navigation › N/A - No Subsystem › Other (navigation)
Issued 3 April 2019
Resolved
A vessel must comply with the applicable requirements for any radio including the requirements for a station license and installation certificates to be issued by the FCC, as set forth in 47 CFR part 80. Vessel is missing FCC License and Safety Certificate. 46 CFR 184.502
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: [withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 3 April 2019
Resolved
As appropriate for the intended voyage, a vessel must carry up to date charts, coast pilot, light list, and tide tables. Charts, Light List, and Coast Pilot are not current. 46 CFR 184.420 (a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: Updated navigation publications provided.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 3 April 2019
Resolved
The installation of a fire extinguisher must be to the satisfaction of the Officer in Charge, Marine Inspections. Galley fire extinguisher and bracket is not mounted. 46 CFR 181.520
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: Fire Extinguisher mounted in bracket.
09 - Working and Living Conditions › 091 - Living Conditions › Access/structure
Issued 3 April 2019
Resolved
On a vessel engaged on excursion type operations, rails shall be fitted with bulwarks, chain link fencing, wire mesh, or the equivalent. Rail courses have gaps near 12 inches near bottom and top courses of rail. 46 CFR 177.35-1 (c)
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 17 July 2019
Resolution: Vessel owner provided netting over spacing between rails.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 3 April 2019
Resolved
All machinery installed must be maintained to afford adequate protection from machinery failure. Both ram seals leaking on steering ram. 46 CFR 182.01-5
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: Ram Seals replaced.
09 - Working and Living Conditions › 091 - Living Conditions › Access/structure
Issued 3 April 2019
Resolved
Suitable rails shall be installed in way of all exposed hazards. Port side rail for upper deck ladder is loose where it mounts to the helm dash. 46 CFR 177-35-15
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: Rails were tighted leading to upper deck.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 3 April 2019
Resolved
At each inspection, the marine inspector shall require hazardous situations to be corrected. Port Window 4th aft from bow is cracked.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 May 2019
Resolved 16 September 2019
Resolution: Received documentation from Delta Glass of window replacement. Window was replaced with Laminated Safety Glass.
Communications › Radio Communications › EPIRB
Issued 22 March 2017
Resolved
EPIRB hydro sticker missing and battery expired.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 25 March 2017
Resolved 24 March 2017
Resolution: Owner replaced EPIRB and installed new hydrostatic release unit.
Operations/Management › Drug and Alcohol Testing › Testing, Equipment
Issued 22 March 2017
Resolved
Alcohol Testing Kit expired
Action required: 705 - Other - as specified
Due 22 March 2017
Resolved 22 March 2017
Resolution: Corrected on the spot