Records from 2017 to 2021. Most recent: operational control imposed, 24 March 2021.
Inspection history · 5
24 March 2021
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7162258
15 March 2021
MARPOL Annex I Examination
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7156408
8 March 2021
Deficiency Check · PSC B
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7148151
9 March 2017
Ballast Water Examination · PII Safety Exam · ISPS II Exam
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6098878
6 March 2017
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6099801
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 8 March 2021
Resolved
07126 - MEANS SHALL BE PROVIDED TO CONTROL LEAKS OF FLAMMABLE LIQUIDS. PSCO FOUND SEVERAL AREAS WHERE THE ACCUMULATION OF OIL AND OIL LEAKS WERE PRESENT INCLUDING #5 AND #6 FUEL INJECTORS AND #1 AND #5 FUEL PUMPS. - 74 SOLAS (14) II-2/4.1.1 - 17AC
Action required: 17 - Rectify deficiencies prior to departure
Resolved 15 March 2021
Resolution: FUEL OIL LEAKS CLEANED. FUEL INJECTORS AND FUEL PUMPS FIXED.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 8 March 2021
Resolved
07120 - THE CSO MUST ENSURE CONSISTENCY BETWEEN SECURITY AND SAFETY REQUIREMENTS. THE ESCAPE ROUTE FROM THE S/G ROOM TO THE MAIN DECK IS SECURED FROM INSIDE WITH NO ACCESS FROM OUTSIDE. - 74 SOLAS (14) XI-2/4.2 ISPS CODE PART A/11.2.11 - 10C
Action required: 10 - Deficiency Rectified
Resolved 8 March 2021
Resolution: CREW UNBOLTED THE DOOR FROM THE INSIDE AND FIXED THE LOCK ON THE OUTSIDE OF THE DOOR.
10 - Safety of Navigation › N/A - No Subsystem › Rudder angle indicator
Issued 8 March 2021
Resolved
THE NAVIGATIONAL EQUIPMENT AND SYSTEMS REFERRED TO IN THIS REGULATION SHALL BE SO INSTALLED, TESTED AND MAINTAINED AS TO MINIMIZE MALFUNCTION. RUDDER ANGLE INDICATOR DISPLAYED DEVIANCE OF 7 DEGREES FROM ACTUAL POSITION. - 74 SOLAS (14) V/19.4 - 10C
Action required: 10 - Deficiency Rectified
Resolved 8 March 2021
Resolution: ELECTRICIAN FIXED RUDDER ANGLE INDICATOR TO SHOW CORRECT RUDDER ANGLE.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 8 March 2021
Resolved
07126 - MEANS SHALL BE PROVIDED TO CONTROL LEAKS OF FLAMMABLE LIQUIDS. PSCO OBSERVED APPROXIMATELY 50 LITERS OF FUEL OIL/WATER MISTURE COATING STARBOARD SIDE ENGINE ROOM BILGE. - 74 SOLAS (14) II-2/4.1.1 - 17AC
Action required: 17 - Rectify deficiencies prior to departure
Resolved 15 March 2021
Resolution: OILY WATER MIXTURE CLEANED OUT OF BILGE.
02 - Structural Conditions › N/A - No Subsystem › Loading/Ballast condition
Issued 8 March 2021
Resolved
02134 - TO DISCHARGE BALLAST WATER INTO WATERS OF UNITED STATES, THE MASTER/OWNER/OPERATOR/AGENT OR PERSON IN CHARGE OF A VESSEL SUBJECT TO 151.2025 OF THIS SUBPART MUST EITHER ENSURE THAT THE BALLAST WATER MEETS THE BALLAST WATER DISCHARGE STANDARD AS DEFINED IN 151.2030(a), USE AN AMS AS DESCRIBED IN 151.2025(a)(3), OR BALLAST EXCLUSIVELY WITH WATER FROM A US PUBLIC WATER SYSTEM. PSCO FOUND VESSEL HAS INOPERABLE BALLAST WATER MANAGEMENT SYSTEM. DISCHARGE OF UNTREATED BALLAST INTO US WATERS IS NOT AUTHORIZED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM LOCAL COTP UNDER PROVISIONS OF 33 CFR 151.2040(b) - 33 CFR 151.2035(a) - 50C
Action required: 10 - Deficiency Rectified
Resolved 10 March 2021
Resolution: Flag (Singapore) provided dispensation for Ballast Water Treatment System.
Pollution Prevention/Response › Prevention Equipment › Oily Water Separator (15 ppm)
Issued 9 March 2017
Resolved
1730- Oily water separating equipment-Oil filtering equipment shall be of a design approved by the administration. PSCO observed OWS piping did not match manufacturer’s diagram. With the current configuration bypassing the OCM is possible and effluent above 15ppm can be sent overboard. MARPOL Annex 1 Reg. 14.6 50b
Action required: 705 - Other - as specified
Due 9 April 2017
Resolved 14 March 2017
Resolution: Received class report attesting to the proper installation and operation of the OWS.
Fire Fighting › Remote Fuel Shutoff › General
Issued 9 March 2017
Resolved
0799- Other (fire-fighting equipment) service tanks with capacity of 500L or more shall be fitted with a valve capable of being closed from a safe place outside the space. PSCO observed quick closing valve to the 1st standby generator blocked open preventing it from being closed in an emergency. SOLAS (09) II-2 4.2.2.3.4 10c
Action required: 705 - Other - as specified
Due 9 March 2017
Resolved 9 March 2017
Resolution: Gave guidance to the C/E on removing blocking devices after conducting maintenance.