Records from 2017 to 2022. Most recent: inspection, 28 September 2022.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 28 September 2022
Resolved
07109 - Fixed fire extinguishing installation - THE PURPOSE OF THIS REGULATION IS TO SUPPRESS AND SWIFTLY EXTINGUISH A FIRE IN THE SPACE OF ORIGIN... FIRE EXTINGUISHING APPLIANCES SHALL BE READILY AVAILABLE. PSCO OBSERVED REMOTE/MANUAL SELECTOR SWITCH ON FIXED PRESSURE WATER - SPRAYING FIRE EXTINGUISHER SYSTEM CONTROL PANEL SET TO MANUAL. - 74SOLAS(20)II-2/10.1.1.2 - 17ac
Action required: 17 - Rectify deficiencies prior to departure
Due 28 September 2022
Resolved 30 September 2022
Resolution: Received, reviewed and accepted class report from NKK stating the deficiency was rectified. Fixed pressure water-spraying fire extinguishing was examined and tested in manual and auto mode and found operating satisfactorily.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 28 September 2022
Resolved
07126 - OIL ACCUMULATION IN ENGINE ROOM - MEANS SHALL BE PROVIDED TO CONTROL LEAKS OF FLAMMABLE LIQUIDS. PSCO OBSERVED SEVERAL AREAS WHERE THE ACCUMULATION OF OIL AND OIL LEAKS WERE PRESENT, INCLUDING: F.O. SETTLING TANK PIPING, NO. 1 F.O. BOOST PUMP PIPING, NO. 1 F.O. CIRC. PUMP PIPING, AND NO 2 & NO. 3 CYLINDERS ON M.E. FUEL INJECTOR LINES. - 74SOLAS(20) II-2/4.1.1 - 17AC
Action required: 17 - Rectify deficiencies prior to departure
Due 28 September 2022
Resolved 30 September 2022
Resolution: Received, reviewed and accepted class report from NKK stating the deficiency was rectified. All leakages were rectified and confirmand by surveyor. Condition of Class issued for permanent repairs w/in two months.
'Condi
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 28 September 2022
Resolved
07114 - REMOTE MEANS OF CONTROL - OIL FUEL PIPES, WHICH, IF DAMAGED, WOULD ALLOW OIL TO ESCAPE FROM A STORAGE... TANK HAVING A CAPACITY OF 500L AND ABOVE... SHALL BE FITTED WITH A COCK OR VALVE... CAPABLE OF BEING CLOSED FROM A SAFE POSITION OUTSIDE THE SPACE. PSCO OBSERVED REMOTELY OPERATED VALVE ON EMERGENCY GENERATOR FUEL TANK TO BE INOPERABLE. - 74SOLAS(20)II-2/4.2.2.3.4 - 10C
Action required: 10 - Deficiency Rectified
Due 28 September 2022
Resolved 28 September 2022
Resolution: Crew repaired f/o shut off valve.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 September 2022
Resolved
11118 - LIFEJACKETS INCL. PROVISON AND DISPOSITION - A LIFEJACKET COMPLYYING WITH THE REQUIREMENTS OF PARAGRAPH 2.2.1 OR 2.2.2 OF THE CODE SHALL BE PROVIDED FOR EVERY PERSON ON BOARD THE SHIP, EACH LIFEJACKET SHALL BE PROVIDED WITH MEANS OF SECURING A LIFEJACKET LIGHT. PSCO OBSERVED 02 LIFEJACKETS IN ENGINE CONTROL ROOM TO BE WITHOUT LIGHTS. - 74SOLAS(20) III/7.2.2 LSA CODE 2.2.1.13 - 10C
Action required: 10 - Deficiency Rectified
Due 28 September 2022
Resolved 28 September 2022
Resolution: CREW ATTACHED LIGHTS TO LIFEJACKETS.