MAURY USCG vessel records
← All vessels

MOREHEAD CITY

MOREHEAD CITY is a 2020 industrial vessel. The Coast Guard has recorded 10 inspections since 2020, most recently in June 2024, along with 21 deficiencies.

Records from 2020 to 2024. Most recent: inspection, 20 June 2024.

Built
2020
Last inspected
20 June 2024
Documentation
Valid · documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Miscellaneous Vessel class in Maury's sources begin in 2016.

Inspection record

Last inspected 20 June 2024
Operational controls None recorded without a removal date
Years with a record 5 calendar years (2020–2024)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDL7788
1575603
Flag
UNITED STATES
Maury page id
psix-1575603

Documentation record

Registered dimensions (L × B × D)45.5 ft × 20.0 ft × 6.5 ft
Registered tonnagegross 39 / net 31
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderCONRAD SHIPYARD LLC · MORGAN CITY, LA, UNITED STATES · built 2020
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portMANNS HARBOR, NC
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 9 April 2026 · expires 30 April 2027
Service, as the file records itIndustrial Vessel
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it39 - Simplified, Gross Ton
31 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Vessel history report

A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 10

20 June 2024 Administrative Inspection · In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7941249
26 March 2024 Administrative Inspection · Appeal
Administrative · USCG East District (dp) · USCG East District (CGD-E) · Activity 7885002
12 December 2023 Annual Inspection · Deficiency Check
Physical examination · Marine Safety Detachment Fort Macon · USCG East District (CGD-E) · Activity 7837349
29 September 2023 Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 7800525
25 August 2023 Administrative Inspection · Appeal
Administrative · Sector North Carolina · USCG East District (CGD-E) · Activity 7812784
21 November 2022 Annual Inspection · Deficiency Check
Physical examination · Marine Safety Detachment Fort Macon · USCG East District (CGD-E) · Activity 7591232
6 January 2022 Annual Inspection
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 7371570
30 July 2021 Administrative Inspection
Administrative · Sector North Carolina · USCG East District (CGD-E) · Activity 7276939
7 October 2020 Special · Deficiency Check
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 7073049
10 July 2020 Construction Oversight · COI Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 7006258

Deficiency record · 21

07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 12 December 2023 Resolved
Each towing vessel must have a fire-detection system installed to detect engine room fires. The owner or managing operator must ensure the following: The system is installed, tested, and maintained in accordance with the manufacturer's design manual. During inspection, MI discovered a fault light was energized on the fire detection panel.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 12 December 2023
Resolved 12 December 2023
Resolution: After further investigation, it was determined that the back up battery was disconnected from the system. Crew reconnected back up battery and system is working as designed.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 12 December 2023 Resolved
A power-driven vessel underway shall exhibit: (iii) operational Sidelights. MI's discovered port side running light was extinguished. Replace with in-kind equipment and make available for inspection of attending MI. Vessel is only to be operated during day light hours and clear visibility.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 December 2023
Resolved 2 January 2024
Resolution: NCDOT Replaced lamp. Operational test SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Ropes and wires
Issued 12 December 2023 Resolved
The results of the inspections required by 33 CFR 164.76 must be documented in the TVR, official logbook, or in accordance with the TSMS applicable to the vessel. A record of the type, size, and service of each towline, face wire, and spring line, used to make the towing vessel fast to her tow, must be available to the Coast Guard or third-party auditor for review. The following minimum information is required in the record: The dates when examinations were performed, the identification of each item of towing gear examined, and the name(s) of the person(s) conducting the examinations. During inspection, MI discovered there was no documentation on rigging/towing equipment. Three of four wire ropes on deck were missing rigging tags. The TVR was missing the above required information. MI also discovered multiple wire strands broken in wire rope that were not properly documented. Install rigging tags on missing wire ropes. Crew needs to conduct a proper inspection on all rigging equipment and log results in TVR.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 December 2023
Resolved 18 December 2023
Resolution: NCDOT replaced the wire ropes and properly documented in vessels TVR. All SAT
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 21 November 2022 Resolved
Guardrails must be installed near the periphery of all decks accessible to the crew. Vsl has removed all the installed guardrails from around the main deck. Vsl must provide guardrails near the periphery of the main deck when not operating as a workboat in a worksite. 46 CFR 144.800
Action required: 17 - Rectify deficiencies prior to departure
Resolved 6 December 2022
Resolution: Handrails were installed and verified.
05 - Radio Communications › N/A - No Subsystem › Functional requirements
Issued 21 November 2022 Resolved
VHF radio must be equipped with the DSC function. Vsl has not integrated GPS into the VHF system so DSC is inop. Vsl must provide VHF radio equipped with DSC functions. 47 CFR 80.13
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 December 2022
Resolution: GPS integrated with vhf radio and CG test conducted satisfactory.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 16 October 2020 Resolved
During underway inspection, excessive vibration and abnormal noise was identified coming from the port shaft. Identify and correct cause of vibration/noise.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 October 2020
Resolution: Cleared during underway trials.
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 16 October 2020 Resolved
Program MMSI number into radios located in the pilot house.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: MMSI was added to radio, verified when radio was turned on.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 16 October 2020 Resolved
Replace emergency battery for fire control panel and correct fault alarm that is displayed.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Alarm was due to dead back up battery, new battery was installed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 16 October 2020 Resolved
Life jackets must have a light and whistle attached in accordance with 46 CFR 141.340.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Lights and whistles were added to all life jackets.
11 - Life Saving Appliances › N/A - No Subsystem › Immersion suits
Issued 16 October 2020 Resolved
Immersion suits must be stowed on the vessel for each person on board.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Immersion suits were added to vessel.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 16 October 2020 Resolved
Provide the following placards on the vessel: Garbage management placard 46 CFR 151.59, Dischage of oil prohibited 33 CFR 155.450, Emergency duties and stations 46 CFR 140.405(c).
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Placards were added in the wheel house.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 16 October 2020 Resolved
Provide a Health and Safety Plan in accordance with 46 CFR 140.500.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 4 January 2021
Resolution: Received digital copy of the valid COD and cleared.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 16 October 2020 Resolved
Provide an official logbook in accordance with 140.190.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: A new Offical Log Book was placed in wheelhouse.
09 - Working and Living Conditions › 092 - Working Conditions › Guards - fencing around dangerous machinery parts
Issued 16 October 2020 Resolved
Install machinery guards over rotating machinery near the main engines in the engine room.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Machinery guards were installed over rotating machinery on the front and aft ends of both main engines.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 16 October 2020 Resolved
Identify and correct low voltage warnings that continuously appear on electronic equipment in wheelhouse.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Power to panel was changed and no longer has low voltage alarm.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 16 October 2020 Resolved
Identify and correct "loop failure" alarm on steering control panel located to the right of the helm.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Alarm rectifited when low voltage def was fixed.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 16 October 2020 Resolved
Low water pressure alarm on port shaft continuously alarms when vessel is in idle or low RPMs. Correct alarm to function as intended.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: Sensor alarm point was lowerd and no longer alarms during normal operation.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 16 October 2020 Resolved
Vessel is currently equipped with a Rigid buoyant apparatus. Install an Inflatable buoyant apparatus prior to operating in Cold Water (December 01).
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: 4 person inflatable life raft was installed ontop of wheel house.
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 16 October 2020 Resolved
Provide valid COD for vessel.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 4 January 2021
Resolution: Received digital copy of HSP and cleared.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 16 October 2020 Resolved
Provide general alarms system to meet requirements set forth in 46 CGR 143.235.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 23 October 2020
Resolution: General alarm was installed
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 16 October 2020 Resolved
Provide means to energize fire pump at the pump.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 October 2020
Resolved 28 October 2020
Resolution: Valve was installed at pump location to allow local activation.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.