Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Bulk Carrier class in Maury's sources begin in 2016.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
Tonnage as PSIX records it44029 - Convention (Subpart B), Gross Ton 81363 - Dead Weight, Ton 95226 - Displacement, Ton 27595 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
A report is not offered for this hull. Its record holds only 1 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 4 September 2020Resolved
Fire protection system and appliances shall be ketp in good working order and readily available for immediate use. Regarding fixed CO2 firefighting system 4 CO2 bottles (bottles 101-104) were found to have manifold hose disconnected at the bottle. Operation of CO2 system would have caused back fill from manifold into open air of CO2 room. Also rendering less charge discharged in desired space. 8 bottles (bottles 29-36) were found to have pilot line and actuator valve disconnected from bottle. This would have resulted in bottles not included in discharge if CO2 discharge was demanded. SOLAS 14 ii-2/ Reg 14.2.1
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 4 September 2020
Resolved 5 September 2020
Resolution: Deficiency rectified. Technician serviced CO2 system. Class and technician report submitted to Sector Puget Sound PSC.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 4 September 2020Resolved
Fire protection system and appliances shall be kept in good working order and readily available for immediate use. The valve was closed on the supply line to hyper mist system rendered it not readily available for immediate use. SOLAS 14 II-2/Reg 14.2.1
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Resolved 4 September 2020
Resolution: Placed valve in Open Position on the spot.