UTWIST

UTWIST is a 2021 passenger vessel (inspected). The Coast Guard has recorded 10 inspections since 2020, most recently in October 2025, along with 9 deficiencies.

Records from 2020 to 2025. Most recent: inspection, 9 October 2025.

Built
2021
Last inspected
9 October 2025
Documentation
Valid · documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 9 October 2025
Operational controls None recorded without a removal date
Years with a record 5 calendar years (2020–2025)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDM3483
1646255
Flag
UNITED STATES
Maury page id
psix-1646255

Documentation record

Registered dimensions (L × B × D)30.0 ft × 10.3 ft × 5.6 ft
Registered tonnagegross 11 / net 9
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderSMOKY MOUNTAIN JET BOAT BUILDING LLC · BRYSON CITY, NC, UNITED STATES · built 2021
Hull materialAluminum
PropulsionJet Drive
Hull shapeShip
Hull configurationMonohull
Hailing portMIAMI, FL
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 15 April 2026 · expires 31 March 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it11 - Simplified, Gross Ton
9 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Vessel history report

A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 10

9 October 2025 Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8258346
1 April 2025 Internal Structural Exam · Deficiency Check · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8103077
24 October 2024 Annual Inspection · Internal Structural Exam · Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8023934
15 November 2023 Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7829058
24 May 2023 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7695663
24 April 2023 Drydock Exam · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7674340
10 February 2023 DAPI Audit · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7634684
25 January 2023 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7626857
8 July 2021 Administrative Inspection · In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7249390
6 October 2020 Construction Oversight · Administrative Inspection · Initial Certification · Plan Review "T" Boat
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7104119

Deficiency record · 9

07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 24 October 2024 Resolved
Portable fire extinguishers must be maintained IAW NFPA 10. Fire extinguishers shall be inspected at least once per calendar month. Did not have log of monthly inspections. Implement plan to document monthly inspections.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 31 October 2024
Resolution: Operator included portable fire extinguisher check in their electronic maintenance log.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 24 October 2024 Resolved
Gauges to indicate engine RPM, jacket water discharge temperature, and lubricating oil pressure must be provided for all propulsion engines installed in the vessel. The gauges must be readily visible at the operating stations. Electronic gauge screen was damaged. Replace gauge.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 31 October 2024
Resolution: Operator used one of the digital displays from the module in the E/R. The replacement for the control station was backordered.
01 - Certificates & Documentation › 012 - Crew Certificates › Doc evidence for personnel on passenger ships
Issued 10 February 2023 Resolved
Marine employers shall ensure that chemical testing of personnel is conducted in accordance with the procedures detailed in 49 CFR Part 40; Marine employer did not have proof of employee assistance program, proof of employee assistance program training for supervisors and crewmembers, means of conducting post-casualty alcohol testing, and reasonable cause testing training for supervisors.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 February 2023
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 February 2023 Resolved
A vessel not required to have a power driven power driven pump must have at least 3, 2.5 gallon buckets. During inspection fire buckets were not readily accessible. 46 CFR 181.610
Action required: 10 - Deficiency Rectified
Resolved 10 February 2023
Resolution: Fire buckets were removed from locked bags.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 10 February 2023 Resolved
Each floating water light installed must be attached to the lanyard with a corrosion resistant clip. 46 CFR 180.70
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 February 2023
Resolution: vessel restricted to day time operations.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 10 February 2023 Resolved
A vessel must carry either a first aid kit approved under approval series 160.041. Vessel aspirin is expired since 2022. 46 CFR 184.710
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 February 2023
Resolution: Owner acquired new aspirin for all vessels.
01 - Certificates & Documentation › 012 - Crew Certificates › Doc evidence for personnel on passenger ships
Issued 10 February 2023 Resolved
Chemical testing of personnel must be conducted as required by this subpart. Vessel does not have an EAP program, vessel alcohol testing strips are expired, no records of negative tests for employees, no training for resonable cause testing, and no training for EAP. 46 CFR 16.201
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 17 February 2023
Resolution: IOs conducted def check.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 25 January 2023 Resolved
To maintain a valid Certificate of Inspection, you must complete your annual inspection within the periods specified in 176.500(b)(1) [annual inspection within 3 months before or after each anniversary date] and your Certificate of Inspection must be endorsed. Vessel is outside of three month window for Inspection and is not permitted to operate until annual inspection has been completed.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 February 2023
Resolution: Annual inspection completed on 10FEB2023.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 4 May 2021 Resolved
A space containing propulsion machinery must be equipped with a fixed fire extinguishing system, the engine compartment is 332 CU.FT.; based of the label on the installed Fireboy system it does not provide adequate coverage for the engine compartment.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 September 2021

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.