Records from 2021 to 2026. Most recent: inspection, 13 January 2026.
Documentation record
Registered dimensions (L × B × D)55.0 ft × 20.0 ft × 8.0 ft
Registered tonnagegross 58 / net 47
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderCORN ISLAND SHIPYARD INC · GRANDVIEW, IN, UNITED STATES · built 2021
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portNORFOLK, VA
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 17 February 2026 · expires 28 February 2027
Service, as the file records itTowing Vessel
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it58 - Simplified, Gross Ton
47 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Inspection history · 12
13 January 2026
Internal Structural Exam · Drydock Exam
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8295747
16 December 2024
Annual Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8043312
29 April 2024
Annual Inspection
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 7903075
29 February 2024
Drydock Exam · Internal Structural Exam
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 7870539
30 October 2023
Type not recorded
No type recorded · Marine Safety Unit Lewes · USCG East District (CGD-E) · Activity 7848745
29 April 2023
Type not recorded
No type recorded · Sector Virginia · USCG East District (CGD-E) · Activity 7684315
25 April 2023
Annual Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7674383
4 March 2022
Annual Inspection · Administrative Inspection · Deficiency Check
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 7406074
24 June 2021
Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7234955
20 May 2021
Type not recorded
No type recorded · Sector Virginia · USCG East District (CGD-E) · Activity 7208101
19 May 2021
Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7206122
29 January 2021
Initial Certification
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7123745
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 16 December 2024
Resolved
Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew. Vessel does not have monthly records of inspections being completed.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 December 2024
Resolved 16 December 2024
Resolution: Vessel added maintenance tags, sent photo proof; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 16 December 2024
Resolved
When the towing vessel is underway, the EPIRB must be stowed in its float-free bracket with the controls set for automatic activation and be mounted in a manner so that it will float free if the towing vessel sinks. The vessels EPIRB was not mounted.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 December 2024
Resolved 17 December 2024
Resolution: EPIRB was properly mounted, recievied phoot proof; all sat.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 16 December 2024
Resolved
All portable fire extinguishers, semi-portable fire-extinguishing systems, fire-detection systems, and fixed fire-extinguishing systems, including ventilation, machinery shutdowns, and fixed fire-extinguishing system pressure-operated dampers on board the vessel, must be inspected or tested at least once every 12 months, as prescribed in paragraphs (a)(1) through (8) of this section. No updated records on board for fixed system.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 December 2024
Resolved 16 December 2024
Resolution: Received certificate; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 16 December 2024
Resolved
At least two lifebuoys on a towing vessel greater than 26 feet must be fitted with a floating electric water light approved under approval series 161.010 or 161.110. Floating electric water light approved under approval series 161.010 or 161.110 must have lithium-ion batteries. 03 floating electric water lights on board did not have lithium-ion batteries.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 December 2024
Resolved 17 December 2024
Resolution: Batteries replaced; all sat.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 29 April 2024
Resolved
The portable fire pump must be self-priming and power-driven, with: (1) A minimum capacity of at least 300 LPM (80 gpm) at a discharge gauge pressure of not less than 414 kPa (60 psi), measured at the pump discharge. Vessel's self-priming fire pump did not have a pressure gauge, thus 60psi output could not be verified. Outfit pump with an appropriate gauge.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2024
Resolved 30 April 2024
Resolution: O/O provided photos of newly installed self-priming fire pump gauge & proof of the gauge reading the pumps pressure during operation.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 29 April 2024
Resolved
Marine employers shall establish programs for the chemical testing for dangerous drugs on a random basis of crewmembers on inspected vessels who: (1) Occupy a position, or perform the duties and functions of a position, required by the vessel's Certificate of Inspection; (2) Perform the duties and functions of patrolmen or watchmen required by this chapter; or, (3) Are specifically assigned the duties of warning, mustering, assembling, assisting, or controlling the movement of passengers during emergencies. Vessel rep &master couldn't located Drug and Alcohol Program documents on vessel at time of inspection. MIs could not verify presence of ship-run testing program, random testing of crew, and testing protocol. Locate & keep onboard approved Drug and Alcohol Program docs for insp.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2024
Resolved 30 April 2024
Resolution: O/O provided DAPI paperwork with annual testing register & random testing schedule.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 17 March 2022
Resolved
(e) The portable fire pump must be self-priming and power-driven, with: (1) A minimum capacity of at least 300 LPM (80 gpm) at a discharge gauge pressure of not less than 414 kPa (60 psi), measured at the pump discharge;...(f) The pump must be stowed with its hose and nozzle outside of the machinery space. MI found portable fire pump not to be self-priming and the location of the pump was in attached space to the machinery space, provide self-priming pump and relocate self-primimng pump in order to comply with 46cfr142.325 and to the satisfaction of the attending MI.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 April 2022
Resolved 30 March 2022
Resolution: Witnessed proper operation of portable pump, def cleared.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 17 March 2022
Resolved
(2) A fixed fire-extinguishing system installed to protect the engine room. MI found fixed
fire-extinguishing system nozzles with sealant tape, provide fire-extinguishing system piping diagram for the engine room area to the satisfaction of attending MI.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 April 2022
Resolved 17 March 2022
Resolution: Objective evidence provided to the satisfaction of attending MI.