Records from 2021 to 2025. Most recent: inspection, 26 October 2025.
Inspection history · 10
26 October 2025
PSC A · COC-CVE Annual
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8256566
12 April 2025
PSC B · COC-CVE Quarterly
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8109827
27 October 2024
Administrative Inspection · PSC A · COC-CVE Annual
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8024991
18 October 2023
PSC A · COC-CVE Annual
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7810731
23 January 2023
Administrative Inspection
Administrative · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 7626327
27 October 2022
Administrative Inspection · COC-CVE Annual · PSC A
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7581179
22 July 2022
Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 7513744
15 November 2021
Administrative Inspection
Administrative · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 7351253
4 November 2021
COC-CVE Initial · PSC B · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7341837
5 April 2021
COC-CVE Initial Prep
Type not classified · Activities Europe · Activity 7168641
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 26 October 2025
Resolved
Fire doors in main vertical zone bulkheads, galley boundaries and stairway enclosures, the approximate time of closure for hinged fire doors shall be no more than 40s and no less than 10s from the beginning of their movement. PSCO observed FSD A.5.36 closing at a rate of less than 10s and not fully latching closed.
74SOLAS20 II-2/9.4.1.1.5.2
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 26 October 2025
Resolution: Crew adjusted the door to slow down the rate of closure allowing the door to safely close and latch completely.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 27 October 2024
Resolved
All life-saving appliances and arrangements shall comply with the applicable requirements of the code. All life-saving appliances shall be fitted with retro-reflective material where it will assist in detection. PSCO observed lifeboat #7 missing retro-reflective tape.
74 SOLAS (20) III/34 LSA CODE 1.2.2.7
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 27 October 2024
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 27 October 2024
Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. PSCO's observed lifeboat crews 2, 4, 12 were unfamiliar with how to operate emergency steering.
74 SOLAS (20) III/19.2.1
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2024
Resolved 27 November 2024
03 - Water/Weathertight Conditions › N/A - No Subsystem › Freeboard marks
Issued 27 October 2024
Resolved
The ring, lines and letters shall be painted in a white or yellow on a dark background or in black on a light background. PSCO observed worn paint on the load line marking making it not visible or contrasting.
ICLL 66 Reg 8
Condition: Invalid
Action required: 10 - Deficiency Rectified
Resolved 27 October 2024
Resolution: Resolved
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 27 October 2024
Resolved
Passenger ships carrying more than 36 passengers shall be equiped with an automatic sprinkler, fire detection and fire alarm system of an approved type complying with the requirements of the Fire Safety Systems Code... Any required automatic sprinkler, fire detection and fire alarm system shall be capable of immediate operation at ll times and no action by the crew shall be necessary to set it in operation. PSCO observed a high fig bulb missing from crew galley deck 8.
74 SOLAS (20) II-2/10.6.1.1 FSS Code 8.2.5.1.1
Condition: Invalid
Action required: 10 - Deficiency Rectified
Resolved 27 October 2024
Resolution: Resolved.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 27 October 2024
Resolved
Cabin doors in "B" class divisions shall be of a self-closing type. Hold-back hooks are not permitted. PSCO observed fire screen door 2.4.08 being held open with a wedge.
74 SOLAS (20) II-2/9.4.1.2.2
Condition: Invalid
Action required: 10 - Deficiency Rectified
Resolved 27 October 2024
Resolution: Resolved.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 27 October 2022
Resolved
Stowage and care of cylinders. Cylinders must always be secured and, when not in use, they must be stowed in a rack in an upright position, with the valve protection cap in place. (46CFR147.60(b)(1)) (16ac)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2022
Resolved 7 November 2022
Resolution: Recieved class report.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 27 October 2022
Resolved
Fire doors in main vertical zone bulkheads, galley boundaries and stairway enclosures other than power-operated watertight doors and those which are normally locked shall satisfy the following requirements: the doors shall be self-closing and be capable of closing. FRS 2.2.63.2 (74SOLAS20 II-2/9.4.1.1.5.1) (16ac)
Condition: Placed in Improper Service
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 November 2022
Resolved 7 November 2022
Resolution: Recieved class report.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 27 October 2022
Resolved
Operational readiness. Fire-gighting systems and appliances shall be kept in good working order and readily available for immediate use. CO2 Cylinder Bistro Cooking Station mising key to unlock cabinet. (74SOLAS20 II-2/14.2.1.2) (10c)
Action required: 10 - Deficiency Rectified
Due 27 October 2022
Resolved 27 October 2022
Resolution: Missing key was replaced.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 27 October 2022
Resolved
Openings in bulkheads and decks in passenger ships. Fire doors in main vertical zone bulkheads, galley boundaries and stairways enclosures...the approx. time of closure for hinged fire doors shall be no more than 40 sec and no less than 10 sec. Multiple fire screen doors closed in less than 10 sec. FSD 10.3.25, FSD 7.2.31, FSD 6.3.30, FSD 3.5.27 (74SOLAS20 II-2/9.4.1.1.5.2) (10c)
Condition: Placed in Improper Service
Action required: 10 - Deficiency Rectified
Due 27 October 2022
Resolved 27 October 2022
Resolution: Doors adjusted on the spot and verified closure between 10 and 40 seconds.