Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Towing Vessel class in Maury's sources begin in 1980.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
Tonnage as PSIX records it89 - Simplified, Net Ton 111 - Simplified, Gross Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 1980 to
2026 for this class, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
Inspection history · 6
19 May 2026Annual Inspection · Administrative Inspection
Physical examination · Sector Upper Mississippi River · USCG Heartland District (CGD-H) · Activity 8373245
12 November 2025In-Service Inspection · Administrative Inspection
Physical examination · Sector Upper Mississippi River · USCG Heartland District (CGD-H) · Activity 8267522
8 May 2025Administrative Inspection · Deficiency Check
Physical examination · Sector Upper Mississippi River · USCG Heartland District (CGD-H) · Activity 8130808
5 May 2025Administrative Inspection · Annual Inspection
Physical examination · Sector Upper Mississippi River · USCG Heartland District (CGD-H) · Activity 8121602
12 December 2023COI Inspection · Administrative Inspection · Initial Certification
Physical examination · Sector Upper Mississippi River · USCG Heartland District (CGD-H) · Activity 7838186
15 March 2022Initial Certification
Physical examination · Sector Upper Mississippi River · USCG Heartland District (CGD-H) · Activity 7412904
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 12 November 2025Resolved
Machinery must be designed and maintained to provide for
safe operation of the vessel under normal and emergency
conditions. It was reported that one of the generators lost power which caused a momentary loss of power throughout the vessel. Prove proper operation prior to movement.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 14 November 2025
Resolution: 835 cleared
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 7 May 2025Resolved
Each towing vessel must have a reliable means to provide notification when an emergency condition exists or an essential system develops problems that require attention. The high bilge audible alarm was inoperable in the pilothouse.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 May 2025
Resolved 8 May 2025
Resolution: The deficiency was cleared to the satisfaction of a USCG Marine Inspector.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 12 December 2023Resolved
46 CFR 143.235 (b)(3)
Has installed, in the engine room and any other area where background noise makes a general alarm hard to hear, a supplemental flashing red light that is identified with a sign that reads: “Attention General Alarm—When Alarm Sounds or Flashes Go to Your Station”;
No signage next to the general alarm flashing light in the engine room.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 12 December 2023Resolved
46 CFR 143.260
Fuel shutoff required to stop the flow of fuel in the
event of a fire or break in the fuel line. must be operable from a safe place outside the space where the valve is installed; must be marked in clearly
legible letters, at least 25 millimeters (1 inch) high,
indicating the purpose of the valve and the way to
operate it.
1. Fuel shut off valves labels were not 1 inch in height 2. Tool to operate shut off valve needs to be in the vicinity of the valves.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
07 - Fire Safety › N/A - No Subsystem › Evaluation of crew performance (fire drills)
Issued 12 December 2023Resolved
46 CFR 136.212
The inspection will ensure that the vessel is in
satisfactory condition and fit for the service for which
it is intended. Fire drill, Man over board, abandon ship
drill to be completed in presence of a marine inspector
prior to the issuance of a COI.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attneding MI conducted MOB and Fire Drills, All sat.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 12 December 2023Resolved
46 CFR 142.330 (a)(7)
The design of the system and its installation on the towing vessel is certified and inspected by a registered professional engineer with experience in fire-detection system design, by a technician with qualifications as a National Institute for Certification in Engineering Technologies (NICET) level IV fire alarm engineering technician, or by an authorized classification society with equivalent experience, to comply with paragraphs (a)(1) through (6) of this section.
1. installed fire detection system and panel design and installation hasn't been approved by a PE.
2. When 12 Volt backup supply is disconnected, no alarm
3. Galley Sensor does not activate system.
The master must ensure that all hatches, doors, and other openings designed to be watertight or weather-tight function properly. Quick-acting water tight door in FWD storage room is not water-tight.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
46 CFR 140.610 (b)
The master must ensure that all hatches, doors, and other openings designed to be watertight or weather-tight function properly. Quick-acting water tight door in FWD storage room is not water-tight.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI witnessed proper operation of QAWTD.
46 CFR 140.605 (a)
The vessel's operation or a history of satisfactory service does not cause the stability of the vessel to be questioned by either the Coast Guard or a TPO engaged to perform an audit or survey.
1. There is no letter attesting to the vessels stability.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
08 - Alarms › N/A - No Subsystem › Emergency signal
Issued 12 December 2023Resolved
46 CFR 143.230 (a)(5)
Each towing vessel must have a reliable means to provide notification when an emergency condition exists or an essential system develops problems that require attention. The following alarms must be provided: (5)Click to open paragraph tools High bilge levels
High level bilge alarm for forward starboard void – visual light does not operate.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI witnessed proper operation of fwd stbd void bilge alarm, all sat.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 12 December 2023Resolved
46 CFR 143.400(a)
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards.
1. Electronics room has exposed dead end wire(s)
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 12 December 2023Resolved
46 CFR 140.435
Each towing vessel must be equipped with an industrial type first aid cabinet or kit, appropriate to the size of the crew and operating conditions.
1. First aid kit at operator’s station contains expired items
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 12 December 2023Resolved
33 CFR 164.72
Each VHF radio operator must hold a restricted operator's license or higher. 1. Army issued radio station license not available for inspection.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 12 December 2023Resolved
46 CFR 142.240
Fixed fire-extinguishing system maintenance receipts and other records generated by these inspections and tests must be retained for at least 1 year and made available upon request.
1. unable to provide fixed fire-extinguishing annual maintenance and testing records.
Action required: 705 - Other - as specified
Resolved 4 March 2024
Resolution: Attending MI completed def check on item, all sat.