Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
The counts in the strip above are the same counts; this table splits the inspections by
the kind of activity recorded. A blank resolution means none was recorded in this data; it
does not establish that a deficiency is outstanding. Years with a record are calendar
years in which a record exists, not years in service.
What Maury does not do.
Documentation record
Tonnage as PSIX records it26573 - Convention (Subpart B), Gross Ton 25178 - Regulatory (Subpart C or D), Gross Ton 38065 - Dead Weight, Ton 23967 - Convention (Subpart B), Net Ton 9448 - Regulatory (Subpart C or D), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.
Inspection history · 7
19 August 2025Administrative Inspection · PSC B · COC-CHEM & TVE Annual
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 22 August 2024Resolved
No electrical wquipment shall be installed in any space where flammable mixtures are liable to collect including those on board tankers. The emergency lighting for a hazardous area was not intrinsically safe.
74 Solas (04) II-1 / 45.10
Action required: 15 - Rectify deficiencies by next port
Resolved 6 September 2024
Resolution: Received Class Survey Report. ALL SAT. Accepted.
07 - Fire Safety › N/A - No Subsystem › Inert gas system
Issued 22 August 2024Resolved
Automatic shut down of the inert gas system aand components parts shall be arranged on predetermined limits being reached. 5 set points were not as per class approved manual No. FE060L-11002 dated 08Nov2006.
74 SOLAS (04) II-2 / 4.5.5
FSS Code 15.2.2.2.2
Action required: 10 - Deficiency Rectified
Due 22 August 2024
Resolved 22 August 2024
Resolution: 5 set points were set back to class approved manual values.
07 - Fire Safety › N/A - No Subsystem › Inert gas system
Issued 22 August 2024Resolved
An automatic shut down of cargo pumps shall be provided to operate on predetermined limits of low pressure in the inert gas main being reached. Class approved IG manual indicates cargo pump to shut down on ID Pall-6.33. Cargo pump did not shut down when alarm was recieved. Vessel is restricted from loading cargoesthat require inerting per IBC.
74 SOLAS (04) II-2 / 4.5.5
FSS Code Ch 15.2.2.4.5.3
Action required: 15 - Rectify deficiencies by next port
Resolved 6 September 2024
Resolution: Received Class Survey Report. ALL SAT. Accepted.