← All vessels
BAY WOLF
Passenger (Inspected) · Passenger Ship class · Built 1980s · USCG Southwest District (CGD-SW) · Other hulls named BAY WOLF
BAY WOLF is a 1981 passenger vessel (inspected). The Coast Guard has recorded 24 inspections since 2014, most recently in December 2025, along with 49 deficiencies, 5 operational controls and 2 casualty investigations between 2019 and 2024.
Records from 2014 to 2025. Most recent: inspection, 8 December 2025.
- Built
- 1981
- Last inspected
- 8 December 2025
- Documentation
- Valid · documentation file of 10 September 2026
- Deficiencies
- 49 recorded · 0 without a recorded resolution
- Controls
- None recorded without a removal date
- Casualties
- 2 investigations · 2019–2024
Identity
641481
WDL7096
202333
Flag
UNITED STATES
367448040
Maury page id
psix-202333
Inspections, by type
…with no type recorded3
Years with a record
12 calendar years (2014–2025)
The 24 inspections in the strip above, split by the kind of activity the US
Coast Guard recorded. Years with a record are calendar years in which a record exists, not
years in service. What Maury does not do.
Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.
Documentation record
Registered dimensions (L × B × D)50.0 ft × 12.0 ft × 11.3 ft
Registered tonnagegross 33 / net 30
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderBILL LEE YACHTS INC · SOQUEL, CA, UNITED STATES · built 1981
Hull materialFRP (Fiberglass)
PropulsionAuxiliary Sail
Hull shapeSail (Distinct Keel)
Hull configurationMonohull
Hailing portSAUSALITO, CA
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 9 June 2026 · expires 30 June 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it33 - Simplified, Gross Ton
30 - Simplified, Net Ton
10 - Displacement, Ton
30 - Simplified, Net Ton
10 - Displacement, Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Radio station licence
WDL7096MMSI 367448040 · active · compulsorily equipped · granted 4 August 2020, expires 4 August 2030
WDF4104MMSI 367448040 · expired · compulsorily equipped · granted 20 April 2010, cancelled 20 June 2020
WBC4979MMSI not assigned · expired · voluntarily equipped · granted 15 August 1996, cancelled 27 January 2007
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its
US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown.
A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.
Inspection history · 24
8 December 2025
Hull Examination · Drydock Exam · Internal Structural Exam
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 8278327
18 March 2025
Annual Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 8095551
31 July 2024
Administrative Inspection · Deficiency Check · Damage Survey
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7971886
29 July 2024
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7974804
23 May 2024
Annual Inspection · Deficiency Check
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7918178
6 December 2023
Hull Examination · Deficiency Check · Drydock Exam · Internal Structural Exam
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7834054
2 March 2023
Annual Inspection · Deficiency Check
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7644068
28 February 2022
Administrative Inspection · Deficiency Check · Annual Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7401332
7 December 2021
Drydock Exam · Deficiency Check · Hull Examination · Internal Structural Exam
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7363243
16 February 2021
Deficiency Check · COI Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7141249
20 July 2020
Deficiency Check · Annual Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7011185
3 March 2020
Administrative Inspection · In-Service Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6921187
6 December 2019
Administrative Inspection · Drydock Exam
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6868867
30 October 2019
Administrative Inspection
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6845464
27 October 2019
Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6917248
15 March 2019
Administrative Inspection · Annual Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6643180
4 December 2018
Drydock Exam · Administrative Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6591544
11 October 2018
Type not recorded
No type recorded · Maritime Safety & Security Team San Francisco (91105) · Activity 6560648
22 June 2018
Administrative Inspection · Annual Inspection · Deficiency Check
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6451725
29 January 2018
Plan Review "T" Boat · Administrative Inspection
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6345503
7 February 2017
Administrative Inspection · Annual Inspection · In-Service Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6085200
15 November 2016
Deficiency Check · Drydock Exam · Internal Structural Exam · Examination of Repairs
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 6042270
12 October 2015
Excursion Permit
Administrative · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 5736846
5 August 2014
Deficiency Check · Annual Inspection
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 4944998
Deficiency record · 49
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 18 March 2025
Resolved
A pre-engineered fixed gas fire extinguishing system must be installed in accordance with the manufacturer's instructions. Observed the overriding function of the Fireboy system was unable to be properly function and restart the engine in a timely manner. (46 CFR 181.420(a)(4))
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 18 March 2025
Resolved
Each lifesaving appliance must be in good working order and ready for immediate use at all times when the unit is in operation. Observed the ring life buoy needs to be replaced due to peeling of outer protecting coating. (46 CFR 180.70(b)(2))
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 18 March 2025
Resolved
Each lifesaving appliance must be in good working order and ready for immediate use at all times when the unit is in operation. Observed Jim buoy had cracks on its surface and small chunks missing from the body. (46 CFR 109.301(a))
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 18 March 2025
Resolved
Electrical equipment exposed to corrosive environments must be of suitable construction and corrosion-resistant. Observed one of four batteries improperly secured allowing part of the battery to lay in the corner hull of the bilge. (46 CFR 183.210(c))
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 18 March 2025
Resolved
The design, materials, and construction of masts, posts, yards, booms, bowsprits, and standing rigging on a sailing vessel must be suitable for the intended service. The hull structure must be adequately reinforced to ensure sufficient strength and resistance to plate buckling. MI observed missing cotter pin on the turnbuckle holding the deck partner in place, new cotter pin has been installed. (46 CFR 177.330)
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 31 July 2024
Resolved
The cognizant OCMI may require that a vessel and its equipment undergo any additional test or inspection deemed reasonable and necessary to determine that the vessel and its equipment are suitable for the service in which they are to be employed. Vessel has suspected internal structural damage to FWD bulkhead following a collision. Complete inspection of damaged area with marine inspector prior to carrying passengers.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 23 May 2024
Resolved
For fixed-gas fire extinguishing systems, the inspections and tests required by Table 176.810(b) of this section, in addition to the tests required by 46 CFR 147.60 and 147.65. The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. Operator was not able to provide a fire servicing report for the installed system.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 23 May 2024
Resolved
A vessel not required to have a power driven fire pump by § 181.300 must have at least three 9.5 liter (2 1/2 gallon) buckets, with an attached lanyard satisfactory to the cognizant OCMI, placed so as to be easily available during an emergency. The words “FIRE BUCKET” must be stenciled in a contrasting color on each bucket. Vessel was missing one bucket.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 23 May 2024
Resolved
Each survival craft must be: Stowed so that when the vessel sinks the survival craft floats free and, if inflatable, inflates automatically. Vessel is required to use a Hydrostatic Release Unit (HRU) for the Lifefloat. The HRU has expired.
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 23 May 2024
Resolved
Each ship transporting more than six passengers for hire equipped with a radiotelephone station in accordance with Part III of Title III of the Communications Act must carry a radio operator who meets the following requirements: (1) Where the station power does not exceed 250 watts carrier power or 1500 watts peak envelope power, the radio operator must hold a marine radio operator permit or higher class license. None of the crew held such license. Provide proof of license for all crew that company will employ as radio operator.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 23 May 2024
Resolved
A submersible electric bilge pump may be used as a power bilge pump required by Table 182.520(a) only on a vessel of not more than 19.8 meters (65 feet) in length carrying not more than 49 passengers, other than a ferry, provided that:
(1) The pump is listed by an independent laboratory as meeting the requirements in UL 1113 (incorporated by reference; see 46 CFR 175.600). (Bilge pump onboard is not UL 1113. Additionally, pump seems to run incessantly which is a concern for overheating/fire).
(3) The pump is permanently mounted. (Pump is not permanently mounted and sloshes around in the bilge).
(7) A positive shutoff valve is installed at the hull penetration. (There is no positive shutoff valve at the hull penetration).
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 23 May 2024
Resolved
The cognizant OCMI may require that a vessel and its equipment undergo any additional test or inspection deemed reasonable and necessary to determine that the vessel and its equipment are suitable for the service in which they are to be employed. Marine Inspector found that operator is not following the approved Preventative Maintenance Plan for sail rigging onboard this vessel and has made pen and ink changes that required specific inspections by crew. As a result and as required by NVIC 02-16, Marine Inspector found several areas that require inspection by a Third Party Rigging Surveyor:
-All rigging aloft (No aloft rigging inspection has been done in last year).
-Inspect forestay turnbuckle under roller furling drum.
-Inspect backing plate at very bottom of forestay chainplate. Inspector found wasted backing plate beyond repairable scantlings.
-Inspect pitting and corrosion in mast step.
Rigging Surveyor shall be vetted IAW NVIC 02-16 by OCMI prior to inspection and be able to provide a written report of findings and recommendations. Marine Inspector shall attend Third Party Rigging Survey.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 May 2024
Resolved
Abandon ship and man overboard drills and training shall be logged or otherwise documented for review by the Coast Guard upon request. The drill entry shall include the following information: Date of the drill and training; and General description of the drill scenario and training topics. Vessel has not logged any drills for the year 2024 and Master has not participated in a drill since hire. Marine Inspector conducted drills with crew and ensured that was entered in logbook.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 May 2024
Resolved
Fire fighting drills and training shall be logged or otherwise documented for review by the Coast Guard upon request. The drill entry shall include the following information: Date of the drill and training; and General description of the drill scenario and training topics. Vessel has not logged any drills for the year 2024 and Master has not participated in a drill since hire. Marine Inspector conducted drills with crew and ensured that was entered in logbook.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 2 March 2023
Resolved
Electrical equipment on a vessel must be installed and maintained to: Provide services necessary for safety under normal and emergency conditions; Protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock; Minimize accidental personnel contact with energized parts; and Prevent electrical ignition of flammable vapors. A wire was disconnected and not properly terminated. Repair to the satisfaction of the marine inspector.
01 - Certificates & Documentation › 012 - Crew Certificates › Medical certificate
Issued 2 March 2023
Resolved
A person may not employ or engage an individual in a position required to hold an MMC unless that individual maintains a current medical certificate. Operator could not provide proof of medical certificate. Provide proof to the satisfaction of the marine inspector.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 2 March 2023
Resolved
The control cabinets or spaces containing valves, manifolds or controls for the various fire extinguishing systems must be marked in conspicuous red letters at least 2 inches high: “[STEAM/CARBON DIOXIDE/CLEAN AGENT/FOAM/WATER SPRAY - as appropriate] FIRE APPARATUS.” Remote fireboy activation did not have a sign. Create proper signage to the satisfaction of the marine inspector.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 2 March 2023
Resolved
A vessel must carry either a first-aid kit that meets the requirements in 46 CFR 199.175(b)(10) or a kit with equivalent contents and instructions. For equivalent kits, the contents must be stowed in a suitable, watertight container that is marked “First-Aid Kit”. A first-aid kit must be easily visible and readily available to the crew. First aid kit had expired burn gel and eye ointment. Replace to the satisfaction of the marine inspector.
09 - Working and Living Conditions › 092 - Working Conditions › Ropes and wires
Issued 2 March 2023
Resolved
A vessel is inspected for compliance with the standards required by this subchapter. Machinery, equipment, materials, and arrangements not covered by standards in this subchapter may be inspected in accordance with standards acceptable to the cognizant OCMI as good marine practice. Vessel's rigging plan and maintenance system did not match recommended manufacturer's instructions. Operator updated plan.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 28 February 2022
Resolved
Each survival craft must be stowed so that when the vessel sinks the survival craft floats free. Life float is stowed with a cover that will not allow device to float free. Updated 04MAR2022 to authorize one time charter before installing HRU.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 28 February 2022
Resolved
For fixed-gas fire extinguishing systems, the inspections and tests required by Table 176.810(b) of this section. The owner must provide satisfactory evidence of the required servicing to the marine inspector. Owner did not have annual service certificate from servicing company for pre-engineered firefighting system.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 28 February 2022
Resolved
A sailing vessel underway shall exhibit sidelights and a sternlight. Starboard running light is extinguished.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 February 2021
Resolved
Fuel shutoff valves must be fitted in the fuel supply lines to stop fuel slow. Emergency fuel shutoff line needs wooden cover installed at all times in order to actuate valve.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 20 July 2020
Resolved
A VESSEL MUST COMPLY WITH THE APPLICABLE REQUIREMENTS FOR ANY RADIO AND EPIRB INSTALLATIONS, INCLUDING THE REQUIREMENTS FOR A STATION LICENSE AND INSTALLATION CERTIFICATES TO BE ISSUED BY THE FCC, AS SET FORTH IN 47 CFR 80. DISCOVERED VESSEL'S FCC STATION LICENSE WAS EXPIRED. VESSEL RESTRICTED TO VOYAGES LESS THAN 1000FT FROM SHORE.
46 CFR 184.502
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 20 July 2020
Resolved
EACH LIFE FLOAT MUST BE MARKED OR PAINTED WITH THE VESSEL'S NAME AND TOTAL NUMBER OF PERSONS CAPACITY OF EACH SPECIFIC UNIT IN CLEARLY LEGIBLE LETTERS AND NUMBERS. LIFE FLOAT ONBOARD WAS MISSING THE REQUIRED MARKINGS.
46 CFR 185.604(a) &
46 CFR 185.604(e)
14 - Pollution Prevention › 145 - MARPOL Annex V › Placards
Issued 20 July 2020
Resolved
A SHIP MUST HAVE AN OIL POLLUTION PLACARD OF AT LEAST 5 BY 8 INCHES, MADE OF DURABLE MATERIAL FIXED IN A CONSPICUOUS PLACE IN EACH MACHINERY SPACE, OR AT THE BILGE AND BALLAST PUMP CONTROL STATION. VESSEL WAS MISSING AN OIL POLLUTION PLACARD.
33 CFR 155.450
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 20 July 2020
Resolved
WIRES AND CABLES SHOULD BE INSTALLED IN AN ORGANIZED MANNER WITH METAL SUPPORTS SPACED NOT MORE THAN 610 MILLIMETERS (24 INCHES) APART. WIRES NOT IN USE SHALL BE CAPPED TO REDUCE A POTENTIAL HAZARD. MULTIPLE EXPOSED WIRE ENDS DISCOVERED, ALONG WITH INSUFFICIENT SUPPORTS FOR THE WIRES AND CABLES ONBOARD.
46 CFR 183.340
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 20 July 2020
Resolved
EACH CHILD SIZE LIFE JACKET MUST BE STOWED IN A LOCATION THAT IS APPROPRIATELY MARKED AND SEPARATED FROM ADULT LIFE JACKETS SO THE CHILD SIZE LIFE JACKETS ARE NOT MISTAKEN FOR ADULT LIFE JACKETS. CHILD SIZE LIFE JACKETS WERE NOT SEPARATED FROM THE VESSEL'S ADULT SIZE LIFE JACKETS.
46 CFR 180.78(a)(5)
09 - Working and Living Conditions › 092 - Working Conditions › Ropes and wires
Issued 6 December 2019
Resolved
Inspection of the condition of the superstructure, masts, and similar arrangements constructed on the hull, and on a sailing vessel all spars, standing rigging, running rigging, blocks, fittings, and sails;Vessels forward headstay has a crack on the left side where the member meets the main deck. Provide proof of the extent of the crack and repair the crack.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 30 October 2019
Resolved
Repairs or alterations to the hull, machinery or equipment that affect the safety of the vessel must not be made without the approval of the cognizant OCMI. Vessel reported damage to the bow of the BAY WOLF. Vessel must make repairs to the satisfaction of the OCMI prior to carrying passengers.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 18 March 2019
Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from machinery failure. The vessel's propeller is not operating as intended in astern operation. Provide technician's feedback on current propeller operation. Submit repair proposal to satisfaction of the Marine Inspector.
46 CFR 182.100
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 18 March 2019
Resolved
At each initial and subsequent inspection for certification, the owner shall be prepared to have the vessel ready for inspection. A log of the inspections and maintenance shall be maintained by the Captains and Crew of the vessel and shall be kept on board for review as requested by USCG Marine Safety Inspectors. Maintenance records not available for review. Provide maintenance records following sailboat specific preventative maintenance schedule.
46 CFR 176.802(a)
NVIC 02-16
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 18 March 2019
Resolved
All cable and wire must be installed with metal supports spaced not more than 24 inches apart, and in such a manner as to avoid chafing and other damage. The use of plastic tie wraps must be limited to bundling or retention of multiple cable installations. Numerous runs of cable throughout the vessel are lacking metal supports. Install metal supports spaced not more than 24 inches apart IAW 46 CFR 183.340. Provide proof of installation to satisfaction of Marine Inspector.
46 CFR 183.340(b)(4)
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 18 March 2019
Resolved
All cable and wire must be installed with metal supports and in such a manner as to avoid chafing and other damage. The forward electric windlass control is being supported by rope. Install metal support IAW 46 CFR 183.340. Provide proof of installation to satisfaction of Marine Inspector.
46 CFR 183.340(b)(4)
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 18 March 2019
Resolved
Each hatch used as a means of escape must have a permanently installed handle not capable of being removed. The forward escape hatch is opened with a wrench temporarily installed. Permanently install handle IAW 46 CFR 177.500. Provide proof of installation to satisfaction of Marine Inspector.
46 CFR 177.500
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2019
Resolved
Vapor barriers must be provided where insulation of any type is used in spaces where flammable and combustible liquids or vapors are present such as machinery spaces. The Engine Compartment does not have a suitable vapor barrier. Repair vapor barrier IAW 46 CFR 177.405. Provide proof of repair to satisfaction of the MI.
46 CFR 177.405(e)
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2019
Resolved
The general construction of the vessel must be such as to minimize fire hazards insofar as it is reasonable and practicable. The fuel supply lines for the propulsion engine are attached to the bulkhead with plastic zip ties. Renew the plastic supports with metal supports to offer continued support in the event of a fire. Provide proof of repair to satisfaction of Marine Inspector.
46 CFR 177.405(a)
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 18 March 2019
Resolved
The weather deck on a flush deck vessel must be watertight and have no obstruction to overboard drainage. The vessel's cockpit has drilled holes compromising the watertight integrity of the deck. Repair the deck IAW 46 CFR 178.410. Provide proof of repair to satisfaction of Marine Inspector.
46 CFR 178.410(a)
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 18 March 2019
Resolved
Deck rails must be constructed to withstand a point load of 200 pounds applied at any point in any direction. The port deck rail has a broken stanchion. Replace during the next dry dock IAW 46 CFR 177.900.
46 CFR 177.900(b)
Documentation › Certificates/Documents › FCC Safety Radiotelephony Certificate
Issued 22 June 2018
Resolved
Renew FCC safety certificate. 47CFR80
Fire Fighting › Means of Escape › Blocked
Issued 22 June 2018
Resolved
Make fwd emergency escape hatch operable from both sides.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Instructions
Issued 22 June 2018
Resolved
Provide fireboy operating instruction for engine restart in over-ride mode (post IVO fireboy controls).
Sail Rigging › Mast Step › Base
Issued 22 June 2018
Resolved
Create/submit vessel specific sailboat maintenance plan. NVIC 02-16
Sail Rigging › Deck Hardware › Furling Gear
Issued 5 August 2014
Resolved
46 CFR 177.330: Replace headstay U-bolt anchor.
Lifesaving › Lifejacket/PFD (Type I) › Quantity
Issued 5 August 2014
Resolved
46 CFR 180.71: Provide 1 adult PFD to total 27 as required on COI. Correct prior to carrying more than 26 passengers.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 5 August 2014
Resolved
46 CFR 161.010: Replace batteries in 2 waterlights. Correct prior to getting underway at night.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 5 August 2014
Resolved
46 CFR 16.260: Update crew list and provide proof of drug testing for all crew.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 5 August 2014
Resolved
46 CFR 185.520: Conduct and log sufficient drills and training.
Operations/Management › Drills/Instruction › Not Conducted
Issued 5 August 2014
Resolved
Did not coduct drills due to No Sail.
Casualty record · 2
27 October 2019Routine · role: Involved in a Marine Casualty · activity 6917248
29 July 2024Routine · role: Involved in a Marine Casualty · activity 7974804
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.
Ownership record
The Coast Guard's documentation record for this hull -- the Abstract of Title,
with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National
Vessel Documentation Center, files it here with its date, and every reader of this page gets it.