Records from 2000 to 2021. Most recent: inspection, 9 August 2021.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 11 June 2019
Resolved
A pre-engineered fixed fire extinguishing system must:
Automatically shut down all ventilation and engines.
Vessels fire extinguishing system did not shut down engines upon simulated test.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 June 2019
Resolved 2 July 2019
Resolution: Tested the engine kill switch as part of the installed fire suppression system. Test was satisfactory.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 11 June 2019
Resolved
Every vessel that operates in the high seas must have an EPIRB installed.
Vessels EPIRB was found to have an expired battery.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 June 2019
Resolved 28 June 2019
Resolution: Captain/Operator sent in satisfactory photos of the new battery unit for the EPIRB.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 June 2019
Resolved
Each hydrostatic release unit must be serviced: within 12 months of its manufacture and within 12 months of each subsequent servicing.
Vessels hydrostatic release for the EPIRB was expired.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 June 2019
Resolved 28 June 2019
Resolution: Captain/operator sent in satisfactory photos of the new hydrostatic release unit for the vessels EPIRB.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 7 June 2018
Resolved
Port side navigational light was inoperable.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 June 2018
Resolved 17 July 2018
Resolution: Verified the port running light is opeartional.
Operations/Management › Drug and Alcohol Testing › Employee Coverage
Issued 19 January 2017
Resolved
Needs consortium letter for crew on board and supervisory training for [name withheld] 46 CFR 16.401 & 201.
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: Reviewed DAPI and is considered satisfactory.
Fire Fighting › Portable CO2 Fire Extinguisher › Mounting Bracket
Issued 19 January 2017
Resolved
One fire extinguisher needs proper mount bracket IAW 46 CFR 181.520
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: Reviewed mounting brackets of extinguisher and is considered satisfactory.
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 19 January 2017
Resolved
Check and relabel all life jackets and stow in proper location IAW 46 CFR 180.78
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: PFD storage is considered satisfactory.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 19 January 2017
Resolved
Label life ring and clean, have life ring holder installed IAW 46 CFR 180.71
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: Markings on lifebuoys are considered satisfactory.
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 19 January 2017
Resolved
Child life jacket stowage door is missing a lock mechanism, repair or replace IAW 46 CFR 176.806
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: Storage of PFDs are considered satisfactory.
Operations/Management › Navigation Safety › Carriage of Charts and Publications
Issued 19 January 2017
Resolved
Updated nav pubs and charts IAW 46 CFR 184.420: Navrules, chart, lightlist and notices to mariners.
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: Charts and publications were reviewed and are considerd satisfactory.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 19 January 2017
Resolved
Bilge pumps and navlights need to be labeled and operate correctly. Label panel with on/off, auto, manual IAW 46 CFR 182.530
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 February 2017
Resolved 7 June 2018
Resolution: Confirmed labels for all indicators at the ops station
Engineering › Fuel Oil Service System › Tank
Issued 18 February 2016
Resolved
Fuel tank was not grounded. Ground fuel tank
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 10 March 2016
Resolved 4 March 2016
Resolution: Added bonding wire to ground fuel tank.
Navigation › Piloting/Steering › Marine Charts
Issued 18 February 2016
Resolved
Navigation publications were not up to date.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 March 2016
Resolved 4 March 2016
Resolution: Had new nav pubs
Engineering › Fuel Oil Service System › Ventilation
Issued 12 January 2016
Resolved
Vent covers were missing from ENG ventilation system.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 10 March 2016
Resolved 4 March 2016
Resolution: Vent covers were onboard
Operations/Management › Drills/Instruction › Safety Orientation
Issued 12 January 2016
Resolved
Man overboard and fire drills did not correspond with emergency instructions placard.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 10 March 2016
Resolved 4 March 2016
Resolution: Updated emergency instructions placard to reflect actual procedure.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 12 January 2016
Resolved
Line attached to ring lifebuoy was corroded.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 March 2016
Resolved 4 March 2016
Resolution: Replaced line.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 13 August 2008
Resolved
Provide and install guards over rotating machinery as per 46 CFR 177.960
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Guards were installed over rotating machinery.
Lifesaving › Lifejacket/PFD (Type I) › Marking
Issued 13 August 2008
Resolved
Provide onboard all required lifesaving equipment as per 46 CFR 180
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Proper lifesaving equipment is on board.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 13 August 2008
Resolved
Prove proper operation of and service of pre-engineered CO2 fire extiguishing system located in engine room as per 46 CFR 181.420
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Pre-engineered fire extinguishing system has been serviced and is operable.
Navigation › Piloting/Steering › Coast Guard Light List
Issued 13 August 2008
Resolved
Provide the required navigation charts and publications as per 46 CFR 184.420
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: All required navigation pubs and charts are on board.
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 13 August 2008
Resolved
Provide a Certificate of Documentation as per 46 CFR 67.7
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Valid COD is on board.
Documentation › Certificates/Documents › Stability Letter
Issued 13 August 2008
Resolved
Provide a Stability Letter as per 46 CFR 176.306
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Valid stability letter is on board.
Engineering › Diesel Engine (propulsion-direct drive) › Crankcase
Issued 13 August 2008
Resolved
Prove proper operation of main propulsion engine and engine shutdown at operating station as per 46 CFR 184,620(b)
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Main engine is operable and shuts down at the operating station.
Engineering › Fuel Oil Service System › Valve, Control
Issued 13 August 2008
Resolved
Prove proper operation of fuel shutoffs as per 46 CFR 182.455(b)(4)
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Fuel shutoffs are operable.
Documentation › Logs/Records › Logbook/Record (unofficial)
Issued 13 August 2008
Resolved
Provide a current training logbook as per 46 CFR 185.420(c)
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: Proper, updated training log is on board.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 13 August 2008
Resolved
Prove proper operation of navigation lights as per 46 CFR 184.420
Action required: 705 - Other - as specified
Due 15 September 2008
Resolved 1 June 2009
Resolution: All navigation lights are operable.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 13 August 2008
Resolved
Provide fire servicing certificate as per 46 CFR 176.810
Action required: 705 - Other - as specified
Due 26 March 2009
Resolved 1 June 2009
Resolution: Valid fire servicing certificate is on board.
Lifesaving › Lifejacket/PFD (Type I) › Storage
Issued 13 August 2008
Resolved
Properly label lifejacket stowage for adult and child lifejackets as per 46 CFR 180.78
Action required: 705 - Other - as specified
Due 26 March 2009
Resolved 1 June 2009
Resolution: All PFD stowage is properly marked.
Lifesaving › Lifejacket/PFD (Type I) › Storage
Issued 13 August 2008
Resolved
Properly segregate adult and child lifejackets as per 46 CFR 180.78
Action required: 705 - Other - as specified
Due 26 March 2009
Resolved 1 June 2009
Resolution: Adult and child PFD''s are properly segregated.
Lifesaving › Lifejacket/PFD (Type I) › Retroreflective Material
Issued 13 August 2008
Resolved
Provide and apply proper retroreflective tape to lifejackets as per 46 CFR 180.75 and 161.012
Action required: 705 - Other - as specified
Due 26 March 2009
Resolved 1 June 2009
Resolution: All PFD''s are properly marked with retroreflective tape.
Construction/Loadline › Penetrations
Issued 9 June 2003
Resolved
INSTALL ACCESS PLATES IN FORWARD HOLD. LEGACY COMPONENT DESC: Hull Access
Condition: Design Flaw
Due 9 July 2003
Resolved 9 October 2003
Lifesaving › Lifejacket/PFD (Type IV)
Issued 9 June 2003
Resolved
REPLACE 24" LIFERING AND 60' OF FLOATABLE LINE, WATERLIGHT WITH 6' OF FLOATABLE LINE, DETACHABLE CLIP, RETROFLECTIVE MATERIAL, AND STENCILED WITH VESSEL NAME. LEGACY COMPONENT DESC: Condition
Condition: Improper/Lack of Maintenance
Due 9 July 2003
Resolved 29 October 2003
Engineering › Bilge Water Management System
Issued 9 June 2003
Resolved
INSTALL POSITIVE CLOSURE DEVICES ON ALL BILGE DISCHARGES. INSTALL ACCESS FOR FORWARD BLIGE DISCHARGE. LEGACY COMPONENT DESC: Piping
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Fire Fighting › Portable Dry Chemical Fire Extinguisher
Issued 9 June 2003
Resolved
ADD ONE ADDITIONAL USCG TYPE B-II FIRE EXTINGUISHER. LEGACY COMPONENT DESC: Number
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Lifesaving › Hand Flares
Issued 9 June 2003
Resolved
PROVIDE 12 HAND HELD DAY/NIGHT FLARES. LEGACY COMPONENT DESC: Quantity
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Engineering › Bilge Water Management System
Issued 9 June 2003
Resolved
PROVIDE PORTABLE BILGE PUMP. LEGACY COMPONENT DESC: Portable Pump
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Communications › Radio Communications
Issued 9 June 2003
Resolved
PROVIDE FCC RADIOTELEPHONE SAFETY CERTIFICATE. LEGACY COMPONENT DESC: Certificates
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Navigation › Collision/Grounding Avoidance
Issued 9 June 2003
Resolved
PROVIDE SHIPS BELL. LEGACY COMPONENT DESC: Bell
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Operations/Management › Drills/Instruction
Issued 9 June 2003
Resolved
POST EMERGENCY INSTRUCTIONS. LEGACY COMPONENT DESC: Emergency Insructions
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Communications › Radio Communications
Issued 9 June 2003
Resolved
POST EMERGENCY BROADCAST PLACARD. LEGACY COMPONENT DESC: Emergency Broadcat Placard.
Condition: Improper Installation
Due 9 July 2003
Resolved 9 October 2003
Lifesaving › Hand Flares
Issued 9 June 2003
Resolved
Prior to the carriage of passengers, label flare box "DISTRESS SIGNALS", as per 46CFR185.614. LEGACY COMPONENT DESC: Storage
Condition: Improper/Lack of Maintenance
Due 9 October 2003
Resolved 29 October 2003
Lifesaving › Lifejacket/PFD (General)
Issued 9 June 2003
Resolved
Prior to the carriage of passengers, label life preserver stowage as per 46CFR180.78. LEGACY COMPONENT DESC: Storage
Condition: Improper/Lack of Maintenance
Due 9 October 2003
Resolved 29 October 2003
Operations/Management › Drills/Instruction
Issued 9 June 2003
Resolved
Prior to the carriage of passengers, provide Red Cross First Aid/CPR cards for 50% of crew as per NVIC 1-91. LEGACY COMPONENT DESC: First aid/ CPR cards
Condition: Unknown
Due 9 October 2003
Resolved 29 October 2003
Navigation › Piloting/Steering
Issued 9 June 2003
Resolved
Prior to the carriage of passengers, provide navigation publications as per 46CFR184.420. LEGACY COMPONENT DESC: Publications
Condition: Improper/Lack of Maintenance
Due 9 October 2003
Resolved 29 October 2003
Navigation
Issued 5 June 2001
Resolved
INSTALL 8" BELL.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: RE-ISSUED
Lifesaving
Issued 5 June 2001
Resolved
INSTALL CORROSION RESISTANT LINK TO WATERLIGHT ON LIFE RING PRIOR TO CARRIAGE OF PASSENGERS.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: RE-ISSUED
Construction/Loadline
Issued 5 June 2001
Resolved
INSTALL POSITIVE CLOSURE DEVICE ON BILGE DISCHARGES.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: RE-ISSUED.
Construction/Loadline
Issued 5 June 2001
Resolved
INSTALL PORTABLE BILGE PUMP PRIOR TO CARRIAGE OF PASENGERS.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: RE-ISSUED.
Documentation
Issued 5 June 2001
Resolved
PROVIDE CURRENT DRUG CONSORTIUM AND CREW LIST.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: SAT
Documentation
Issued 5 June 2001
Resolved
PROVIDE CURRENT CREW TRAINING LOGS (MAN OVERBOARD, ABANDON SHIP, FIRE, AND EPIRB TESTS).
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Lifesaving
Issued 5 June 2001
Resolved
PROPERLY REGISTER EPIRB.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: SAT
Documentation
Issued 5 June 2001
Resolved
PROVIDE FCC RADIO STATION LICENSE AND FCC RADIOTELEPHONE SAFETY CERTIFICATE.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: RE-ISSUED
Documentation
Issued 5 June 2001
Resolved
PROVIDE STABILITY LETTER.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: SAT
Lifesaving
Issued 5 June 2001
Resolved
PROVIDE 3 RED AND 3 ORANGE HAND HELD FLARES PRIOR TO CARRIAGE OF PASSENGERS.
Condition: Unknown
Due 22 June 2001
Resolved 9 June 2003
Resolution: RE-ISSUED.
Lifesaving
Issued 16 March 2000
Resolved
INSTALL 406 MHZ CAT. 1 EPIRB AS PRIMARY LIFESAVING PRIOR TO CARRAGE OF PASSENGERS PASSED DEMARCATION.
Condition: Unknown
Due 28 March 2000
Resolved 29 March 2000
Lifesaving
Issued 16 March 2000
Resolved
MOUNT LIFERING WITH 60' OF FLOATABLE LINE ATTACHED PRIOR TO CARRIAGE OF PASSENGERS.
Condition: Unknown
Due 20 March 2000
Resolved 29 March 2000
Engineering
Issued 1 March 2000
Resolved
Ground fuel vent lines.
Condition: Unknown
Due 1 March 2000
Resolved 1 March 2000
Lifesaving
Issued 1 March 2000
Resolved
Conduct emergency drills prior to operating.
Condition: Unknown
Due 1 March 2000
Resolved 1 March 2000
Documentation
Issued 1 March 2000
Resolved
Provide licensed operator enrolled in an approved random drug testing program.
Condition: Unknown
Due 1 March 2000
Resolved 1 March 2000