07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 4 September 2025
Resolved
Shutoff valves, installed so as to close against the fuel flow, must be fitted in the fuel supply lines, one at the tank connection and one at the engine end of the fuel line to stop fuel flow when servicing accessories. The shutoff valve at the tank must be manually operable from outside the compartment in which the valve is located. The port fuel shutoff valve does not turn 90 degrees for full closure when activated remotely. 46 CFR 119.455(b)(3)
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 6 November 2025
Resolution: Accepted video of sat operation.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 4 September 2025
Resolved
A-Class bulkheads… must be so insulated with approved structural insulation, so that, if subjected to the standard fire test for the applicable time period, the average temperature on the unexposed side does not rise more than 250 °F above the original temperature, nor does the temperature at any one point rise more than 325 °F above the original temperature… Penetrations must be designed or insulated to withstand the same temperature rise limits as the boundary penetrated. The A-60 Class bulkhead forward in the lazarette is missing sections of non-combustible insulation starboard of the CO2 bottles and inadequate foam is used to seal penetrations on both sides of same bulkhead and overhead aft of access ladder. 46 CFR 116.415(a)(2)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 28 October 2025
Resolution: Accepted photo of correction.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 4 September 2025
Resolved
Nonconducting mats or grating must be provided on the deck in front of each switchboard. The nonconductive mat is missing. 46 CFR 120.330(g)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 28 October 2025
Resolution: Accepted photo of mat.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 4 September 2025
Resolved
Each ring life buoy on a vessel must, if on a vessel on an oceans or coastwise route, be orange in color. Two ring life buoys are excessively faded. 46 CFR 117.70(b)(5)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 28 October 2025
Resolution: Accepted photo of life rings.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 4 September 2025
Resolved
Each life jacket must be marked with Type I retroreflective material approved in accordance with § 164.018 in subchapter Q of this chapter. Ten child lifejackets had retroreflective material that was worn and partially painted over. 46 CFR 122.604(h)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 28 October 2025
Resolution: Accepted photo of lifejackets.
07 - Fire Safety › N/A - No Subsystem › Evaluation of crew performance (fire drills)
Issued 4 September 2025
Resolved
For a vessel described by 46 CFR 175.110(c), the training program in paragraph (a) of this section must address firefighting proficiency and must include (1) Training in the use and location of firefighting equipment and general firefighting knowledge, including: (i) Location of firefighting appliances and emergency escape routes; (ii) Types and sources of ignition; (iii) Flammable materials, fire hazards and spread of fire; (iv) The need for constant vigilance; (v) Actions to be taken on board; (vi) Fire and smoke detection and automatic systems on board; and (vii) Classification of fire and applicable extinguishing agents. Required training was not logged. 46 CFR 122.420
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 6 November 2025
Resolution: Accepted photo of logged training.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 4 September 2025
Resolved
Secured to the vessel by a painter with a float-free link permanently attached to the vessel except that a float-free link is not required if the vessel operates only on waters not as deep as the length of the painter. Painter on 2 of 4 IBA’s were found not connected to the weak link and would have prevented release in an emergency. 46 CFR 117.130
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 4 September 2025
Resolved 4 September 2025
Resolution: Corrected on the spot.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 4 September 2025
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected and all required guards and protective devices must be in satisfactory condition. Both outboard heating piping lines in the lazarette were holed in several locations allowing the potential for excess water accumulation in this space. 46 CFR 115.830
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 29 December 2025
Resolution: Accepted photos of replaced piping.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 4 September 2025
Resolved
Piping used in a vital system must meet 56.50 in subchapter F of this chapter. Lazarette bilge suction piping found with two sections of the piping joined with a 5” portion of non metallic material. Replace existing section of piping with material in accordance with the regulations. 46 CFR 119.710
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 October 2025
Resolved 29 December 2025
Resolution: Accepted photo of replaced piping.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 31 October 2024
Resolved
A vessel that is exposed to salt water more than three months in any 12 month period since the last examination must undergo a drydock examination and an internal structural at least once every two years. The vessel has not completed a drydock examination within the last two years. Conduct satisfactory drydock examination prior to the carriage of passengers.
46 CFR 176.600(c)(1)
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 9 December 2024
Resolution: Vessel conducted dry dock exam at Bay Ship and Yacht
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 6 June 2024
Resolved
The name of the vessel must be marked or painted in clearly legible letters on each life float paddle. Paddles for vessel's life floats did not have names. Label paddles properly to the satisfaction of the MI.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 June 2024
Resolved 8 July 2024
Resolution: Paddles were properly labled with vessel name.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 6 June 2024
Resolved
For a vessel described by 46 CFR 114.100(e), the training program in paragraph (a) of this section must address firefighting proficiency. MI observed limited details in vessel's drill logs. Crew training program must address the listed firefighting proficiencies to improve crewmember training and proficiency, including egress training for each member on board.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 June 2024
Resolved 8 July 2024
Resolution: Appropriate log entries detailing drills conducted during exam were completed.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 6 June 2024
Resolved
At each initial and subsequent inspection for certification of a vessel, the owner shall be prepared to conduct tests and have the vessel ready for inspections of the hull structure and its appurtenances. Temporary patch observed in overhead of storage void. Outer side of patch is on starboard main weatherdeck and there is a weld seam visible. Patch inside void is 10 ft forward of access ladder a few inches from sideshell. Remove patch during next drydock and make available for MI inspection.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 4 September 2025
Resolution: Area was opened during inspection and determined no further action needed.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 7 September 2023
Resolved
A vessel owner or operator may use an Alternative Security Program as approved under § 101.120 of this subchapter if: (a) The Alternative Security Program is appropriate to that class of vessel. Vessel’s security plan was found to be missing key elements needed in a vessel security plan and was deemed not appropriate for the class of the vessel. Vessel must update and renew their security plan to the satisfaction of the attending Marine Inspector, vessel will be restricted to less than 150 passengers until this deficiency is resolved.
33 CFR 104.140(a)
Condition: Design Flaw
Action required: 705 - Other - as specified
Resolved 19 October 2023
Resolution: Vessel conducted audit, updated security plan and is no longer restricted in pax count.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 7 September 2023
Resolved
Vessels described by 46 CFR 114.110(e) must have an interconnected fire detection system in compliance with 46 CFR 181.450 installed in all enclosed areas where passengers and crew have routine access, including accommodation spaces and machinery spaces. Vessel was found to not have an interconnected fire detection system on board. Vessel must have interconnected fire detection system in the machinery space, main deck accommodation space, and the pilot house and to the satisfaction of the attending Marine Inspector, vessel will be restricted to Limited Coastwise routes until this is resolved.
46 CFR 114.110(e)
46 CFR 118.400(d)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 19 October 2023
Resolved 19 October 2023
Resolution: Interconnected smoke detectors tested sat.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 7 September 2023
Resolved
Each portable fire extinguisher on a vessel must be of a type approved by the Commandant. The minimum number of portable fire extinguishers required on a vessel must be acceptable to the cognizant OCMI, but must be not less than the minimum number required by Table 118.500(a) of this section and other provisions of this section. There were multiple extinguishers found on the vessel that did not meet the requirements of Table 188.500(a) of the regulation. Vessel must review the requirements of table 118.500(a) and update and correct all portable fire extinguishers to the standard and the satisfaction of the attending Marine Inspector.
46 CFR 114.110(e)
46 CFR 118.500(a)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 September 2023
Resolved 14 March 2024
Resolution: Vessel's route has been restricted to limited coastwise due to inability of correcting deficiency.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 7 September 2023
Resolved
Each ring life buoy on a vessel must: (1) Be approved in accordance with § 160.050 in subchapter Q of this chapter, or other standard specified by the Commandant, including, but not limited to, approval series 160.150; (2) Be readily accessible; (3) Be stowed in a way that it can be rapidly cast loose; (4) Not be permanently secured in any way; and (5) If on a vessel on an oceans or coastwise route, be orange in color. Vessels port side lifebuoy was found worn where the orange coloring was degrading. Repair or replace the lifebuoy to the satisfaction of the attending Marine inspector.
46 CFR 117.70(b)(5)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 September 2023
Resolved 19 October 2023
Resolution: Lifebuoy was replaced satisfactorily.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 7 September 2023
Resolved
Each rescue boat and ring life buoy must be marked with Type II retroreflective material approved in accordance with § 164.018 in subchapter Q of this chapter, or other standard specified by the Commandant. The arrangement of the retroreflective material applied after March 11, 1996, must be as specified by IMO Resolution A.658(16). The vessels reflective material on the lifebuoys was found degraded and not up to the specifications of type II retroreflective material. Vessel must replace the reflective material on the lifebuoys to the satisfaction of the attending Marine Inspector.
46 CFR 122.604(i)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 September 2023
Resolved 19 October 2023
Resolution: Reflective tape was corrected.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 7 September 2023
Resolved
Spanner wrenches must be provided for each fire hydrant required by this regulation. Existing vessels must comply with this requirement by January 18, 2017. Port side fire station is missing a spanner wrench. Vessel must replace the missing spanner wrench to the satisfaction of the Marine Inspector.
46 CFR 118.310(e)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 September 2023
Resolved 19 October 2023
Resolution: Spanner wrench was added to the station.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 7 September 2023
Resolved
The master of the vessel shall ensure that: (c) The EPIRB test is required by paragraph (a) shall be logged or otherwise documented, as applicable. Vessel logbook was found with multiple missing EPIRB tests along with other important entries. Vessel Master and crew were educated on the importance of logging the critical information as well as when they need to be logging the information.
46 CFR 122.728(c)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 7 September 2023
Resolved 7 September 2023
Resolution: Corrected on the spot.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 6 October 2022
Resolved
At each initial and subsequent inspection for certification of a vessel, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspections of the hull structure and its appurtenances. Cracked and missing welds were noted in the forepeak and fore most storage room. Locations were marked appropriately within the space and need repaired.
46 CFR 115.802(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 October 2022
Resolved 25 October 2022
Resolution: Verified proper welds on identified areas.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 6 October 2022
Resolved
At each initial and subsequent inspection for certification of a vessel, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspections of the hull structure and its appurtenances. Two pieces of longitudinal framing were missing in the STBD side overhead in the forepeak.
46 CFR 115.802(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 October 2022
Resolved 3 November 2022
Resolution: Missing framing was welded onto existing framing
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 7 September 2022
Resolved
At each initial and subsequent inspection for certification, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment, including the following: Inspection of fixed gas fire extinguishing system to check for excessive corrosion and general condition. CO2 cylinders have a large amount of corrosion on the bottom as the steel cylinders are mounted on an aluminum tray. Operator states that cylinders have not been weighed or moved in over two years.
46 CFR 115.810(a)(1)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 November 2022
Resolution: Tech report lists installatoin of new clyinders and weighed ammounts.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 7 September 2022
Resolved
At each initial and subsequent inspection for certification, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment, including the following: For fixed gas fire extinguishing systems, the inspections and tests required by Table 115.810(b). During inspection, operator could not show inspector’s report documenting tests completed IAW requirements in table referenced.
46 CFR 115.810(b)(2)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 November 2022
Resolution: Tech report lists required servicing completed on Sept 12th, 2022.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 7 September 2022
Resolved
At each initial and subsequent inspection for certification, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of its fire protection equipment, including the following: Inspection and testing of smoke and fire detecting systems (including sensors and alarms) and fire confining appliances (such as fire screen doors and fire dampers). Operator could not show evidence of testing of detection system.
46 CFR 115.810(a)(7)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 November 2022
Resolution: Tech report lists satisfactory testing of detection system.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 7 September 2022
Resolved
A device must be provided to automatically shut down power ventilation serving the protected space and engines that draw intake air from the protected space prior to release of the extinguishing agent into the space. Engine room has powered ventilation that is not on the pressure switch circuit and will not shut down upon activation of CO2 system. 46 CFR 118.410(b)(10)
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 November 2022
Resolution: Tech report lists satisfactory servicing of ventilation closures that were already installed in the system.
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 7 September 2022
Resolved
A fire control plan (FCP) must be posted on the vessel in a location that is accessible and visible to all passengers. The plan must show escape routes, areas of refuge, embarkation stations, the location of fire protection/emergency equipment, compartment titles and hazard classification of accommodation and service spaces, and structural fire protection boundaries. Vessel has a Fire Control Plan that is not approved by OCMI and is not visible to all passengers. Additionally, several modifications to the vessel has been made since the current FCP was developed. Submit new plan for review by Marine Safety Center and approval by OCMI.
46 CFR 116.530
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 19 October 2023
Resolution: FCP was updated and posted.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 7 September 2022
Resolved
Fire load calculations must be submitted by the owner for review to the Marine Safety Center when: A space is designated as a low risk accommodation space by the owner; or the cognizant OCMI determines, based on the quantity of combustibles, that the fire load present in a high risk accommodations space may exceed 37.5 kg (7.5 pounds) of combustibles per square meter (square foot) of deck area. Vessel is using unapproved Fire Control Plan that was developed using fire load calculations that were done before extensive remodeling took place. Boundaries have been moved, flooring has been installed, and furniture has been installed; all of which raises concerns about fire load calculations. Submit calculations to Marine Safety Center for review and approval by OCMI.
46 CFR 116.427(a)
Condition: Placed in Improper Service
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 19 October 2023
Resolution: Fire load calculations were updated and submitted to MSC for review.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 7 September 2022
Resolved
A-Class bulkheads or decks must be composed of steel or equivalent material, suitably stiffened and made intact with the main structure of the vessel, such as the shell, structural bulkheads, and decks. They must be so constructed that, if subjected to the standard fire test, they are capable of preventing the passage of smoke and flame for 1 hour. In addition, they must be so insulated with approved structural insulation, bulkhead panels, or deck covering so that, if subjected to the standard fire test for the applicable time period listed below, the average temperature on the unexposed side does not rise more than (250 °F) above the original temperature, nor does the temperature at any one point, including any joint, rise more than (325 °F) above the original temperature: A-60 Class – 60 minutes. Vessel does not have boundaries in lazarette that meet this requirement. Fire Control Plan lists this space a A-60 boundary.
46 CFR 116.415(a)(2)(i)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 3 November 2022
Resolution: MI verified insulation meets SFP requirements and is of an approved international type.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 7 September 2022
Resolved
Penetrations in A-Class fire control boundaries for electrical cables, pipes, trunks, ducts, etc. must be constructed to prevent the passage of flame and smoke for one hour. In addition, the penetration must be designed or insulated so that it will withstand the same temperature rise limits as the boundary penetrated. A-60 boundary materials are missing in engine room in way of cable and piping penetrations leading out of engine room.
46 CFR 116.415(a)(2)(ii)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Installation materials surround cabling penetrations to most reasonable expectations.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 7 September 2022
Resolved
Sight-flow glasses may be used in lubricating-oil systems provided it has been demonstrated, to the satisfaction of the Commanding Officer, Marine Safety Center, that they can withstand exposure to a flame at a temperature of 927 °C (1700 °F) for one hour, without failure or appreciable leakage. Lube oil tank sight glass has been replaced with a flexible clear PVC tubing. Replace to original design to satisfaction of attending marine inspector.
46 CFR 56.50-80(h)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 3 November 2022
Resolution: Operator installed glass sight tube
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 7 September 2022
Resolved
Electrical equipment on a vessel must be installed and maintained to: Prevent electrical ignition of flammable vapors. Vessel has installed in engine room a portable, temporary, clipped on, non-UL listed light, and utilizes an uncovered bulb in the engine room.
46 CFR 120.200(d)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator removed unapproved light from space.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 7 September 2022
Resolved
At each inspection for certification and at every other vessel inspection the bilges and other spaces may be examined to see that there is no excessive accumulation of oil, trash, debris, or other matter that might create a fire hazard, clog bilge pumping systems, or block emergency escapes. Engine rooms were found with bilges containing excessive amounts of oil and temporary catches for oil. Determine the cause of oil accumulation and make repairs to satisfaction of OCMI.
46 CFR 115.830(b)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator tightened loose oil pan bolts on bottoms of both engines and thoroughly cleaned out bilges.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 September 2022
Resolved
Tests must verify that automated vital systems are designed, constructed, and operate in accordance with all applicable requirements of part 62 of this subchapter. The tests must be based upon the failure analysis, if required by § 62.20-3(b) of this subchapter, functional performance requirements, and the Periodic Safety tests of § 61.40-6. Tests must be performed immediately after the installation of the automated equipment or before the issuance of the initial Certificate of Inspection. Vessel has installed electronic engine controls and does not have an approved set of Design Verification Test Procedures, Qualitative
Failure Analysis, or Periodic Safety Test Procedures.
46 CFR 61.40-3
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 February 2024
Resolution: Vessel submitted new PSTP/DVTP to MSC for upcoming repower.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 7 September 2022
Resolved
The OCMI may require an inspection and testing whenever a repair or alteration is undertaken. Vessel has installed a thru hull penetration in the bottom shell of the hull that attempts to make watertight by use of epoxy and composite material. Penetration is under fuel tank. Vessel to submit repair proposal that includes returning hull scantlings and watertight. Once approved, vessel to have properly installed equipment prior to next credit drydock.
46 CFR 115.700(d)
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 3 November 2022
Resolution: Verified material is watertight and provides proper seal in through hull penetration. Material verified by BSY to be used as tranducer backing.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 September 2022
Resolved
Electrical equipment used in the following locations must be dripproof: A machinery Space. Engine electronic control modules for port and starboard main engines have wire bundle drip shields that are not placed on connections properly. Additionally, it looks like excessive dust and debris may have entered wire bundle female connection. Clear of debris and properly install drip shields to satisfaction of attending marine inspector.
46 CFR 120.210(a)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator cleaned and installed individual drip and debris shields on all female connections.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 7 September 2022
Resolved
C'-Class bulkheads must be constructed to prevent the passage of smoke between adjacent areas. Penetrations in C'-Class boundaries for electrical cables, pipes, trunks, ducts, etc. must be constructed so as to preserve the smoke-tight integrity of the boundary. There three holes in the stairs leading to upper deck. Holes are in a C-Class boundary according to Fire Control Plan.
46 CFR 116.415(a)(2)(vi)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator plugged 03 holes in stairs.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 7 September 2022
Resolved
A vessel must carry either a first-aid kit approved under approval series 160.041 or a kit with equivalent contents and instructions. Eyewash and aspirin are expired and must be replaced.
46 CFR 121.710
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 17 October 2022
Resolution: reviewed contents of new first aid kit
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 7 September 2022
Resolved
Each vessel that operates on the high seas, or that operates beyond three miles from the coastline of the Great Lakes, must have on board an FCC Type Accepted Category 1, 406 MHz EPIRB, installed to automatically float free and activate. EPIRB battery and hydrostatic release were expired.
46 CFR 117.64
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 7 September 2022
Resolution: Replaced EPIRB battery and hydrostatic release.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 7 September 2022
Resolved
The number and identification of the items stowed inside, and their sizes, must be marked in clearly legible letters and numbers on each container for life jackets and immersion suits. Child life jacket storage container is labeled for 25 instead of the required 26 life jackets.
46 CFR 122.604
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Updated signage to read 26 lifejackets.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 7 September 2022
Resolved
Portable fire extinguishers must be located so that they are clearly visible and readily accessible from the space being protected. The installation and location must be to the satisfaction of the cognizant [name withheld] fire extinguishers in the galley and operating station must be stored in suitable mounting bracket.
46 CFR 118.520
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Fire extinguishers mounted in approved mounts.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 7 September 2022
Resolved
Carbon dioxide warning signs. Each entrance to a space storing carbon dioxide cylinders, a space protected by carbon dioxide systems, or any space into which carbon dioxide might migrate must be conspicuously marked as follows: (1) Spaces storing carbon dioxide - “CARBON DIOXIDE GAS CAN CAUSE INJURY OR DEATH. VENTILATE THE AREA BEFORE ENTERING. A HIGH CONCENTRATION CAN OCCUR IN THIS AREA AND CAN CAUSE SUFFOCATION.” (2)Spaces protected by carbon dioxide - “CARBON DIOXIDE GAS CAN CAUSE INJURY OR DEATH. WHEN ALARM OPERATES OR WINTERGREEN SCENT IS DETECTED, DO NOT ENTER UNTIL VENTILATED. LOCK OUT SYSTEM WHEN SERVICING.” Carbon dioxide warning signs are not posted. Verbiage from 46 CFR 122.612(i)(1) must be posted at entrance to lazarette and verbiage from 46 CFR 122.612(i)(2) must be posted at the entrance to the engine room.
46 CFR 122.612(i)(1)(2)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 7 October 2022
Resolution: Appropriate signage posted to engine room (protected space) and laz (storage space).
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 September 2022
Resolved
The arrangement of a vessel must allow the safe operation of the vessel giving consideration to protection against fire. Open and unsecured plastic bottle of hydraulic fluid is being used as overfill for steering system and placed on top of pilot house console. Remove overfill line and plastic bottle from the pilot house.
46 CFR 116.100(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Plastic bottle and excessive hose was removed.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 7 September 2022
Resolved
Electrical equipment on a vessel must be installed and maintained to protect passengers and crew from electrical hazards originating in electrical equipment. Multiple dead end and unused wires are stowed behind pilot house console. Remove all unnecessary wires and dead end wires from space.
46 CFR 120.220(b)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: All dead end wires and unused wires removed from space.
02 - Structural Conditions › N/A - No Subsystem › Bulkheads - cracking
Issued 7 September 2022
Resolved
The construction and arrangement of a vessel must allow for the safe operation of the vessel giving consideration to provisions for a seaworthy hull. Significant hole was made on the starboard bulkhead of the pilot house with insulation exposed to the weather. Ensure weather tight boundary in bulkhead.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator installed proper vent for hole in bulkhead.
08 - Alarms › N/A - No Subsystem › Engineers' alarm
Issued 7 September 2022
Resolved
Alterations to machinery or equipment that affect the safety of the vessel must not be made without the approval of the OCMI, except during an emergency. Alarms for the bow and stern thrusters are covered in duct tape, minimizing the operation and intent of the alarm. Remove tape from alarm.
46 CFR 115.700(a)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 7 September 2022
Resolution: Operator removed tape from alarms.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 September 2022
Resolved
Nonmetallic piping materials, including nonmetallic flexible hose assemblies, must meet the requirements of § 56.60-25 in subchapter F of this chapter. Vessel has a length of piping from a thru-hull to the sewage raw water pump. Submit piping diagram repair proposal that meets 56.50-25 requirements for approval by OCMI.
46 CFR 119.720
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator replaced unapproved piping with SAE J1942 flexible hose.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 7 September 2022
Resolved
Non-metallic flexible hose must be in accordance with SAE J1942. 46 CFR 56-60.25(b). Vessel had unauthorized tank truck hoses on both port and starboard engines. Replace with an approved hose.
46 CFR 119.720
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Replaced tank truck hose with SAE J1942 hose.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 September 2022
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices…and other hazardous situations must be corrected. Vessel has installed an air compressor/receiver in the engine room. Equipment is installed with undersized hardware that is under excessive strain.
46 CFR 115.830(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 3 November 2022
Resolution: Air compressor has been installed with a strap to add stability to the battery mount.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 7 September 2022
Resolved
Nonferrous metallic piping materials are acceptable for use in the following: non-vital systems. Bilge pump piping under fuel tank uses a 12” section of flexible hose material to connect piping to strainer.
46 CFR 119.730(a)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator installed approved SAE J1942 flexible hose
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 7 September 2022
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices…and other hazardous situations must be corrected. Bilge high level alarms in lazarette and storage void can get stuck in the up position.
46 CFR 115.830(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Installed proper functioning bilge alarm.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 7 September 2022
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected. Explosive MAP gas cylinder was found in storage void.
46 CFR 115.830(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Gas cylinder was removed from space.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 7 September 2022
Resolved
Sluice valves are not permitted in watertight bulkheads. Bilge piping leading to forepeak and through collision bulkhead is fitted with a sluice (gate) valve.
46 CFR 119.500(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 25 October 2022
Resolution: Vessel replace sluice valve with ball valve at 2022 dry dock.
04 - Emergency Systems › N/A - No Subsystem › Emergency fire pump and its pipes
Issued 7 September 2022
Resolved
At each initial and subsequent inspection for certification of a vessel, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspections of…piping systems, including the following: Operational test of all overboard discharge and intake valves and watertight bulkhead pipe penetration valves. During testing of the fire pump/ bilge pump system, raw water intake valve was found stuck open. After several tries, operator was able to close valve.
46 CFR 115.804(g)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 7 September 2022
Resolution: Proper valve function witnessed.
04 - Emergency Systems › N/A - No Subsystem › Emergency fire pump and its pipes
Issued 7 September 2022
Resolved
The fire pump must be capable of delivering a single hose stream from the highest hydrant, through the hose and nozzle required by § 118.320 of this part, at a pitot tube pressure of 345 kPa (50 psi). During testing of the fire pump, 50 psi could not be reached. Marine Inspector found that overboard discharge valve could not close all the way due to an improperly maintained/stuck ball valve and an installation to ball valve that has handle hitting the bulkhead before fully seated in the closed position. After several attempts, operator was able to close valve. Subsequently, fire pump pressure was able to reach the minimum 50 psi.
46 CFR 118.300(b)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 7 September 2022
Resolution: Fire pump reached 50 psi.
09 - Working and Living Conditions › 092 - Working Conditions › Pipes, wires (insulation)
Issued 7 September 2022
Resolved
Penetrations and openings in watertight bulkheads must have a means to make them watertight. Cable penetrations must be made watertight.
46 CFR 171.114(a)(2)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 6 October 2022
Resolution: Operator used fire block to make penetrations watertight.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 September 2022
Resolved
All cable and wire must be installed with metal supports spaced not more than 24 inches. The use of plastic tie wraps must be limited to bundling and not used as a means of support. Plastic ties and rope was observed in the engineroom in multiple places as a means of support of cable, wire and hoses. Properly support cable, wiring and hoses.
46 CFR 120.340(b)(4)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 September 2022
Resolved 7 October 2022
Resolution: Operator installed metal supports in engine room.
09 - Working and Living Conditions › 092 - Working Conditions › Safe means of access
Issued 9 June 2021
Resolved
On a vessel on which the number of passengers permitted on upper decks is limited by stability criteria, as indicated by the vessel's stability letter, the maximum number of passengers allowed on an upper deck must be indicated by a durable marking of at least 1 inch numbers and letters at the entranceway to that deck. Upper deck restricted to 166 passengers as per stability letter not marked.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 July 2021
Resolved 7 July 2021
Resolution: Received photo of installed sign
11 - Life Saving Appliances › N/A - No Subsystem › Operation of Life Saving Appliances
Issued 9 June 2021
Resolved
Each survival craft must be: stowed so that when the vessel sinks the survival craft floats free and, if inflatable, inflates automatically. Hydrostatic release was improperly connected on 01 IBA preventing its automatic release.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 9 June 2021
Resolved 9 June 2021
Resolution: Crew properly connected hydro release.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 9 June 2021
Resolved
Each door, hatch, or scuttle, used as a means of escape, must be capable of being opened by one person, from either side. Emergency escape hatch in storage void seized from the inside.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 June 2021
Resolved 9 June 2021
Resolution: Crew serviced hatch.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 9 June 2021
Resolved
Life floats must not be stowed in tiers more than 4 high. When stowed in tiers, the separate units must be kept apart by spacers. Life floats were not separated by spacers.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 July 2021
Resolved 7 July 2021
Resolution: Received photo of spacers.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 13 March 2019
Resolved
Passed service date.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 April 2019
Resolution: Provided report
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 13 March 2019
Resolved
missing 86 pmls
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 April 2019
Resolution: Provided photos
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 13 March 2019
Resolved
Hand rails 01 deck aft do not meet 39.5 after MOD.
Condition: Placed in Improper Service
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 April 2019
Resolved 30 April 2019
Resolution: Provided documentation that was found satisfactory.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 13 March 2019
Resolved
VSL Security Plan not onboard and outdated. Vsl rep stated the vessel will remain in DD until sold. If vessel is placed into the water a new plan will need to be submitted and approved.
Action required: 705 - Other - as specified
Resolved 14 December 2020
Resolution: As directed by the CID this deficiency is cleared for MISLE cleanup, vessel is out of service and a special note has been added for this activity to ensure this deficiency is reviewed prior to issuing COI. VSL in CA requesting new to zone.
15 - Safety Management Systems (ISM) › N/A - No Subsystem › Emergency preparedness
Issued 13 March 2019
Resolved
Conducted underway drills prior to carring passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 14 December 2020
Resolution: As directed by the CID this deficiency is cleared for MISLE cleanup, vessel is out of service and a special note has been added for this activity to ensure this deficiency is reviewed prior to issuing COI. Vsl in CA and will be requesting new to zone.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 13 March 2019
Resolved
Out of service date.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 April 2019
Resolution: Provided third party report
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 13 March 2019
Resolved
Life jacket storage adrift, need to be properly secured 02 deck.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 April 2019
Resolution: provided photos
05 - Radio Communications › N/A - No Subsystem › VHF EPIRB
Issued 13 March 2019
Resolved
Hydro release out of date.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 April 2019
Resolved 30 April 2019
Resolution: Provided documentation that was found satisfactory.
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 13 August 2018
Resolved
The vessel is currently broadcasting (1) Zero Draft, (2) Ship Type missing.
Condition: Invalid
Action required: 705 - Other - as specified
Due 13 September 2018
Resolved 14 December 2020
Resolution: As directed by the CID this deficiency is cleared for MISLE clean up.Vessel is out of service and special note has been added for this activity to ensure the deficiency is recieved
Engineering › Gasoline Engine (auxiliary) › Fuel Intake (2 stroke)
Issued 25 June 2018
Resolved
Port F/O supple hose from filter to gov. wasted. Port SSDG.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 2 July 2018
Resolved 2 July 2018
Resolution: replaced hose
Engineering › Diesel Engine (propulsion-reduction gear) › Waste Heat Recovery
Issued 25 June 2018
Resolved
Port and STBD MDE exp. tank pressure caps leaking.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 25 June 2018
Resolved 25 June 2018
Resolution: Provided photos of new caps installed
Engineering › Diesel Engine (propulsion-reduction gear) › Nozzle, Injection (fuel injection)
Issued 24 June 2018
Resolved
Vessel loss propulsion during mooring on port engine. Would not allow for start up during, initial attemps. Captain was able to start moring after, engine did start and ran at idle next morning. Company is trouble shooting.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 June 2018
Resolved 25 June 2018
Resolution: Vessel changed fuel filter and conducted sea trails with MIs onboard all test SAT. Visual inspection of fuel filters conducted, dirty filters were observed.
Engineering › Generator (propulsion-electric) › Winding
Issued 24 June 2018
Resolved
The port generator set was recently installed improperly, mounting bolts are missing.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 June 2018
Resolved 25 June 2018
Resolution: Gen set mounting hardware installed.
Engineering › Gasoline Engine (auxiliary) › Fuel Intake (2 stroke)
Issued 24 June 2018
Resolved
Port SSDG return F/O hose is worn and wasted.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 2 July 2018
Resolved 2 July 2018
Resolution: replaced hose
Lifesaving › Work Vest › Condition
Issued 9 May 2018
Resolved
Provide proper size lifevest for MOB drill.
Action required: 705 - Other - as specified
Due 18 May 2018
Resolved 15 May 2018
Resolution: Proper size lifejacket.
Operations/Management › Lifesaving › Op Readiness/Maintenance/Inspection
Issued 9 May 2018
Resolved
Properly secure rescue plat form while conducting MOB drill.
Action required: 705 - Other - as specified
Due 18 May 2018
Resolved 15 May 2018
Resolution: Provided chains to secure rescue plat form.
Engineering › Diesel Engine (propulsion-reduction gear) › Exhaust Manifold
Issued 12 February 2018
Resolved
The owner made modifications to the vessels MDE approved exhaust piping system. Prove proper operation of the modified system as currently installed.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 5 April 2018
Resolved 7 April 2018
Resolution: Attending M/I conducted sea trials of vessel with satisfactory results. See narrative for details.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 12 February 2018
Resolved
The vessels main engine room and rudder room hatchs are not insulated iaw approved drawnings, no means of securing, and is not air tight, that would other wise prevent smoke or co2 if activated egress from inside the protected space.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 5 April 2018
Resolved 7 April 2018
Resolution: Attended vessel inspected temporary installation and accepted this date as satisfactory. See narrative for details.
Construction/Loadline › Hull › Weld
Issued 24 October 2017
Resolved
Vessel has an approx. 30" crack along weld at port side (amid ship) open passenger deck on previous welding insert. See narrative for details.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 15 November 2017
Resolved 22 November 2017
Resolution: Attending Marine Inspector confirmed proper repairs were completed. See narrative for further details AN 6298193
Engineering › Compressed Air System (control) › Compressor
Issued 15 March 2017
Resolved
IAW 46 CFR 54.01-5(4) Class II; III Pressure vessels that have a net internal volume of less than 5 ft3 must be stamped with either the ASME "U" or "UM" symbol. The existing pressure vessel does not have a "U' stamp; shows signs of corrosion. Replace with approved pressure vessel.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Owner replaced pressure vessel with new pressure vessel (craftsman), serial No. 0113405 rated for 150 psi and stamped with the ASME U IAW 46 CFR 54.01-5(4).
Fire Fighting › Structural Fire Protection - General › Structural Bulkhead Construction
Issued 15 March 2017
Resolved
Repair structural fire protection in engine room and tankroom where indicated.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Inspected repairs to structural fire protection in engine room and tank room.
Electrical › Electric Supply System (service) › Cable
Issued 15 March 2017
Resolved
Install guard over a/c - d/c converters atop batteries port and STBD sides. Exposed cable connections.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Inspected new guards over AC-DC converters.
Electrical › Electric Supply System (service) › Battery Charger
Issued 15 March 2017
Resolved
Install drip shield for charge on stbd side of engine room where indicated.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Verified new installation of aluminum drip shield over battery charger on starboard side of engine room.
Electrical › Lighting (service) › Lighting Branch Circuit
Issued 15 March 2017
Resolved
Provide DATA on LED rope lighting on second deck passenger area.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Owner provided data on LED rope lighting which verified the lighting to be UL Listed. Verified operational test of circuit breaker.
Fire Fighting › Structural - A Class Divisions › Store-rooms
Issued 15 March 2017
Resolved
Remove all spray foam "Great Stuff" from bulkhead penetrations throughout vessel as indicated. Install approved fire stop.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Great Stuff was removed from watertight bulkhead penetrations. Verified application of fire stop.
Construction/Loadline › Structures › Transverse Bulkhead
Issued 15 March 2017
Resolved
Repair cracked weld in Rod room where indicated. STBD side first bulkhead on the fwd side.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Inspected repaired weld. All Sat.
Electrical › Electric Supply System (service) › Cable
Issued 15 March 2017
Resolved
Remove all dead end cables in engine room as indicated.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: All dead end cables were removed from the engine room.
Navigation › Collision/Grounding Avoidance › Radar
Issued 15 March 2017
Resolved
Repair #1 Radar, will not turn on.
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 31 March 2017
Resolution: Owner opted to remove radar from the vessel. Vessel has one fully functioning radar and is not required two radars.
Operations/Management › Drills/Instruction › Abandon Ship
Issued 15 March 2017
Resolved
Conduct drills. MOB, SECURITY, and FIRE. Unable to conduct underway drills due to weather.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 21 March 2017
Resolution: Completed all emergency drills satisfactory.