Records from 1984 to 2015. Most recent: inspection, 11 October 2015.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Inspection history · 81
11 October 2015
In-Service Inspection
Physical examination · USCG Heartland District · USCG Heartland District (CGD-H) · Activity 5740298
28 September 2015
COC-MODU Renew
Type not classified · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 5751739
25 February 2011
Examination of Repairs
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 3955731
11 May 2009
Deficiency Check · Administrative Inspection
Physical examination · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 3472150
6 February 2009
Administrative Inspection
Administrative · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 3413390
3 February 2009
Administrative Inspection
Administrative · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 3415022
27 January 2009
MARPOL Annex VI Survey · COI Inspection · Deficiency Check
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 3393837
3 December 2008
Internal Structural Exam
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 3372823
1 October 2007
Annual Inspection · Administrative Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3094827
5 September 2006
Annual Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 2761959
17 November 2005
COI Inspection · Hull Examination
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 2523907
7 January 2005
Re-Inspection
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 2270438
26 November 2003
Hull Examination · Re-Inspection
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1955052
26 January 2003
Administrative Inspection
Administrative · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1735484
13 November 2002
MARPOL Annex I Examination · Re-Inspection
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1716636
14 May 2002
Administrative Inspection
Administrative · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1616812
26 February 2002
Administrative Inspection
Administrative · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1489509
21 February 2002
Administrative Inspection
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1488272
30 January 2002
Administrative Inspection
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1482570
21 November 2001
Re-Inspection
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1419000
31 October 2001
Hull Examination
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1456039
12 October 2001
Administrative
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 772962
4 September 2001
Administrative
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1072320
11 May 2001
Administrative
Administrative · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1064308
16 April 2001
Administrative
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1062991
5 March 2001
Administrative
Administrative · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1059496
19 March 2000
Type not recorded
No type recorded · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1055338
21 October 1999
Re-Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1121825
20 September 1999
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 805758
10 December 1998
Hull Examination · COI Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 804781
20 May 1998
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1130416
25 September 1997
Re-Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1465335
28 August 1997
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 785021
23 January 1997
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1100598
18 December 1996
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1094805
18 December 1996
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1094809
13 December 1996
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1091477
6 November 1996
COI Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 872773
5 November 1996
Hull Examination
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1186242
5 March 1996
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1077452
12 January 1996
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1182446
28 November 1995
Re-Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 877587
2 January 1995
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 879110
2 December 1994
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1152787
17 November 1994
COI Inspection · Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 866181
19 May 1994
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1171914
16 March 1994
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 854275
16 March 1994
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1164583
15 March 1994
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1164836
4 March 1994
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 853133
24 November 1993
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1158596
2 November 1993
Hull Examination
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 851264
26 October 1993
Re-Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 848712
13 April 1993
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1152261
23 February 1993
Administrative
Administrative · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1149552
13 January 1993
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1137898
20 November 1992
COI Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1136736
29 May 1992
Deficiency Check
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1254798
23 April 1992
Type not recorded
No type recorded · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1253096
15 November 1991
Hull Examination
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1251901
11 November 1991
Re-Inspection
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 942600
25 January 1991
Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 934843
13 December 1990
COI Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 929962
10 December 1990
Administrative
Administrative · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1240477
25 January 1990
Re-Inspection
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1214557
4 January 1990
Administrative
Administrative · Commandant (CG-CVC) · Activity 925469
5 December 1989
Administrative
Administrative · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 909746
2 March 1989
Hull Examination
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1199349
8 December 1988
COI Inspection · Drydock Extension
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 893673
17 March 1988
Re-Inspection
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1300189
30 January 1987
Deficiency Check
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1315385
10 December 1986
COI Inspection · Hull Examination
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1010176
18 April 1986
Type not recorded
No type recorded · MSO Corpus Christi · USCG Heartland District (CGD-H) · Activity 1306427
18 March 1986
Deficiency Check
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1000032
23 February 1986
Damage Survey
Physical examination · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1310840
16 January 1986
Deficiency Check
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1304460
11 December 1985
Re-Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 986745
16 October 1985
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 996246
23 July 1985
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 987836
4 July 1985
Damage Survey
Physical examination · MSO BOSTON · USCG Northeast District (CGD-NE) · Activity 1293213
19 December 1984
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 980846
Engineering › Steam Boiler (auxiliary/waste heat) › Automation Equipment
Issued 11 May 2009
Resolved
Present Aux boilers (#1 & 2) for inspection/survey IAW provisions of 46 CFR Subchapter F prior to use.
Action required: 705 - Other - as specified
Resolved 9 November 2009
Resolution: All required boiler commissioning test & inspections complete. Verified renewal and testing of steam drum outlet stop valve and leaking common steam outlet piping. All sta.
Engineering › Steam Boiler (auxiliary/waste heat) › Automation Equipment
Issued 22 April 2009
Resolved
Auxiliary boilers need to be surveyed under 46 CFR Subhapter F prior to use. Survey must be completed to satisfaction of attending Marine Inspector.
Action required: 705 - Other - as specified
Resolved 8 May 2009
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 3 February 2009
Resolved
Class "A" boundary door from galley to mess deck not closing completely
Due 3 March 2009
Resolved 4 February 2009
Resolution: OIM e-mailed repair report and picture of fixed "A" door.
//s// [name withheld]
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 3 February 2009
Resolved
Ensure proper distribution of life jackets in berthing spaces.
Due 10 February 2009
Resolved 4 February 2009
Resolution: OIM e-mailed that count had been completed.
//s// [name withheld]
Construction/Loadline › Hull › Bottom Plating
Issued 3 December 2008
Resolved
Complete exterior portion (Phase II) of hull exam prior to rig movement.
Action required: 17 - Rectify deficiencies prior to departure
Due 1 April 2009
Resolved 3 February 2009
Resolution: Phase II of hull exam completed
Lifesaving › Lifeboat › Embarkation/Disembarkation Capabilities
Issued 8 October 2007
Resolved
Prove proper operation of the limit switches for the #1 and #3 STBD lifeboats.
Action required: 705 - Other - as specified
Due 15 October 2007
Resolved 9 October 2007
Resolution: Received statement from OIM stating that all of the limit switches cleaned, lubricated and working properly.
Lifesaving › Lifeboat › Propeller Shaft
Issued 8 October 2007
Resolved
Determine where the noise is coming from when the #2 port lifeboat is clutched in.
Action required: 705 - Other - as specified
Due 8 November 2007
Resolved 10 October 2007
Resolution: Received statement from the OIM stating that the bearing was lubricated and boat was tested with no noise apparent.
Construction/Loadline › Structures › Door
Issued 8 October 2007
Resolved
Provide new gaskets for the following WTD'S: EDG space, STBD heavy equipment space, port and STBD thruster space emergency escape hatches.
Action required: 705 - Other - as specified
Due 8 November 2007
Resolved 10 October 2007
Resolution: Received statement from OIM stating that all gaskets were replaced on all listed WTD''S.
Fire Fighting › Ventilation Systems › Operating Controls
Issued 8 October 2007
Resolved
Prove proper operation of the emergency generator space ventilation clousure.
Action required: 705 - Other - as specified
Due 15 October 2007
Resolved 9 October 2007
Resolution: Received statement from the OIM stating that the ventilaction louvers were cleaned and adjusted.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 8 October 2007
Resolved
Provide annual servicing report for all fixed fire fighting equipment.
Action required: 705 - Other - as specified
Due 15 October 2007
Resolved 13 October 2007
Resolution: Received annual servicing certificate from OIM.
Fire Fighting › Ventilation Systems › Operating Controls
Issued 8 October 2007
Resolved
Prove proper operation of the pressure that secures the venlilation located in the EDG space.
Action required: 705 - Other - as specified
Due 15 October 2007
Resolved 9 October 2007
Resolution: Received statement from OIM stating that ventilation pressure switch was replaced and tested satisfactory.
Engineering › Bilge Water Management System › Not Operational
Issued 8 October 2007
Resolved
Prove proper operation of the bilge suction in the sack room.
Action required: 705 - Other - as specified
Due 15 October 2007
Resolved 9 October 2007
Resolution: Received statement from the OIM stating that the bilge suction in the sack room was cleaned and tested satisfactory.
Fire Fighting › Ventilation Systems › Exhaust Ducts (Galley Ranges)
Issued 8 October 2007
Resolved
Clean STBD galley exhaust fan vent.
Action required: 705 - Other - as specified
Due 8 November 2007
Resolved 13 November 2007
Resolution: Received statement from the OIM stating that the exhaust vent was cleaned.
Lifesaving › Line-Throwing Appliances › Projectiles
Issued 8 October 2007
Resolved
Provide up-dated line throwing devices.
Action required: 705 - Other - as specified
Due 8 November 2007
Resolved 10 October 2007
Resolution: Received statement from OIM stating that new line-throwing appliances were re-newed.
Construction/Loadline › Hull › Hull Plating
Issued 17 November 2005
Resolved
Complete Phase II of SEILOD (underwater/spud can) inspection before next rig move.
Due 13 December 2005
Resolved 13 December 2005
Resolution: Spud can/ underwater inspection completed with no deficiencies. Reports submitted to PATMS.
Lifesaving
Issued 21 November 2001
Resolved
Replace fall for liferaft davit stbd side and conduct weight test.
Condition: Unknown
Due 21 November 2001
Resolved 26 November 2001
Fire Fighting
Issued 21 October 1999
Resolved
INSTALL A PRESSURE SWITCH TO SHUT DOWN ELECTRICAL IN PAINT LOCKER UPON ACTIVATION OF CO-2 SYSTEM IN THE PAINT LOCKER.
Condition: Unknown
Due 21 October 1999
Resolved 2 November 1999
Lifesaving
Issued 21 October 1999
Resolved
FREE UP ZIPPERS FOR EXPOSURE SUITS AND PUT ITEM ON A REGULAR MAINTANCE SCHEDULE.
Condition: Unknown
Due 21 October 1999
Resolved 2 November 1999
Construction/Loadline
Issued 21 October 1999
Resolved
RENEW BILGE STRAINERS IN AFTER THRUSTER ROOMS.
Condition: Unknown
Due 21 October 1999
Resolved 2 November 1999
Electrical
Issued 21 October 1999
Resolved
REMOVE DEAD END WIRING AND REPACK UNUSED PACKING GLANDS IN THE MUD PIT ROOM.
Condition: Unknown
Due 21 October 1999
Resolved 2 November 1999
Lifesaving
Issued 10 December 1998
Resolved
PROVE PROPER OPERATION OF EMERGENCY LIGHTING AT THE #2 LIFEBOAT STATION.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Documentation
Issued 10 December 1998
Resolved
Provide an affidavit from the U.S. licensed Offshore Installation Manager (OIM) atesting to the state of compliance with U.S. laws and regulations onboard the vessel. In conjunction with this affidavit, provide documentary evidence of completion of applicable tests and inspections as completed.
Condition: Unknown
Due 31 December 1998
Resolved 10 December 1998
Accommodation/Occupational Safety
Issued 10 December 1998
Resolved
REMOVE, NON-APPROVED WOOD PANELLING IN CHANGE ROOM ABOVE LOCKERS. FUTURE INSTALLATIONS MUST MEET STRUCTURAL FIRE PROTECTION STANDARDS INCLUDING REVIEW AND APPROVAL OF PLANS AND FIRE LOAD CALCULATIONS.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Electrical
Issued 10 December 1998
Resolved
INSTALL ACCEPTABLE CABLE TRAY AND GUARD FOR CABLES ON DECK IN WAY OF CANTILEVER DRILL DECK.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Deck/Cargo
Issued 10 December 1998
Resolved
RENEW RELIEF VALVES ON LOW PRESSURE SIDE OF SHIPS SERVICE AIR COMPRESSORS.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Deck/Cargo
Issued 10 December 1998
Resolved
PROVIDE RELIEF VALVES ON THE DISCHARGE SIDE OF BULK AIR COMPRESSORS.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Navigation
Issued 10 December 1998
Resolved
PROVIDE THREE (3) BLACK BALL DAYSHAPES AND ONE (1) BLACK DIAMOND DAYSHAPE.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Fire Fighting
Issued 10 December 1998
Resolved
REMOVE SUFFICIENT PORTION OF FIRE STATION #2 HOSE RACK STANCION TO ALLOW EASIER ACCESS TO COUPLINGS FOR THE HOSE CONNECTION.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Engineering
Issued 10 December 1998
Resolved
PROVIDE DOCUMENTATION OR OTHER EVIDENCE ATTESTING TO THE SUITABILITY OF THESAFETY RELIEF VALVES, ON THE TWO (2) CLAYTON STEAM GENERATORS, FOR USE WITHSTEAM, OR REPLACE WITH APPROPRIATE TYPE VALVES.
Condition: Unknown
Due 10 January 1999
Resolved 19 February 1999
Navigation
Issued 25 September 1997
Resolved
TROUBLESHOOT, REPAIR, AND PROVE PROPER OPERATION OF ALL NAVIGATION LIGHTS, PRIOR TO OTHER THAN DAY LIGHT OPERATION.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE DOOR CLOSER FOR EXTERIOR DOOR OF HOSPITAL SPACE.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROPERLY LABEL HIDDEN FIRE DAMPER FOR CONFERENCE ROOM.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
STAIR TOWER FIRE DOORS MODIFIED LATCH PLATES REMOVED, HOLES LEFT IN DOORS. RESTORE STAIR TOWER FIRE DOORS TO ORIGINAL RATING. MAKE PROPER REPAIR TO FIRE DOORS.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIR TO #3 + #5 MAIN DIESEL ENGINES LOW LUBE OIL TRIPS.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Fire Fighting
Issued 25 September 1997
Resolved
NUMBER ONE FIRE PUMP PIPING HOLED AND PATCHED. MAKE PERMANENT REPAIRS TO FIRE PUMP PIPING AND HYDROSTATICALLY TEST IN ACCORDANCE WITH 46CFR 56.97- 40.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
MUD PIT ROOM AND MUD PUMP ROOM DOORS IN DISREPAIR. RENEW OR PROPERLY REPAIR BOTH MUD PIT ROOM AND MUD PUMP ROOM GAS TIGHT DOORS, IN ACCORDANCE WITH 46 CFR 111.105-33.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
TROUBLE SHOOT, REPAIR, AND PROVE PROPER OPERATION OF NON OPERATIONAL FIRE PUMP RELIEF VALVE.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Lifesaving
Issued 25 September 1997
Resolved
MAKE RIG AVAILABLE FOR FULL BATTERY OF EMERGENCY SHUT DOWN TESTS, INCLUDINGESD'S, VENT SHUT DOWNS, MOTOR ROOM SHUT DOWNS, REMOTE STOPS, EMERGENCY LIGHTING, UPS CIRCUITS.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Electrical
Issued 25 September 1997
Resolved
REMOVE WATER FROM FOG HORN BATTERY BOX.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
PROPERLY LABEL EMERGENCY LIGHTING FIXTURES THROUGHOUT RIG, IN ACCORDANCE WITH 46CFR 108.639 AND 108.621.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROVIDE DOCUMENTATION OF ALL TESTING PERFORMED ON THE HELO FUEL MARINE PORTABLE TANKS, IN ACCORDANCE WITH 46 CFR 98.30.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROPERLY LABEL FIRE STATIONS IN ACCORDANCE WITH 46 CFR 108.633.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROPERLY LABEL ALL LIFESAVING EQUIPMENT IN ACCORDANCE WITH 46CFR 108.646.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
FREE UP ALL FROZEN/RUSTED QUICK RELEASE RING BUOY CAGES.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Construction/Loadline
Issued 25 September 1997
Resolved
INSTALL ISOLATION VALVES OF STEEL OR EQUIVALENT CONSTRUCTION BETWEEN PVC PIPING AND STEEL PIPING WHERE THEY PENETRATE WATERTIGHT BULKHEADS IN THE FOLLOWING LOCATIONS: (A) MOTOR ROOM ON DISCHARGE/OVERBOARD LINE OF DISTILLING UNIT, (B) MUD PUMP ROOM OVERHEAD IN WAY OF PUMP #1.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
IMMERSION SUIT STORAGE LOCKER IN DISREPAIR, DOORS RUSTED AND STIFF. PERFORM PREVENTATIVE MAINTENANCE ON IMMERSION SUIT STORAGE LOCKER STBD SIDEAND PROVE OPERATIONAL.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Fire Fighting
Issued 25 September 1997
Resolved
REPAIR CHEMICAL ROOM FIRE DOOR CLOSER.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
RELOCATE AND PROPERLY LABEL GENERAL ALARM BELL IN STBD STORE ROOM, (PAN CANADIAN WORKSHOP)
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Accommodation/Occupational Safety
Issued 25 September 1997
Resolved
ESCAPE LADDER MISSING FROM STARBOARD THRUSTER ROOM. PROVIDE ADEQUATE ESCAPE EXIT FROM STARBOARD THRUSTER ROOM.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROPERLY LABEL GENERAL ALARM BELLS IN THE FOLLOWING LOCATIONS, (A) MUD PUMPROOM, (B) CHEMICAL ROOM, (C) WIRE ROPE ROOM, IN ACCORDANCE WITH 46 CFR 108.625.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE AND INSTALL PROPER HAND WHEEL FOR MOTOR ROOM FIRE STATION.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Construction/Loadline
Issued 25 September 1997
Resolved
PROVIDE COPY OF ALL NDT RESULTS AND REPORTS ON REPAIRS FOR SPUD CANS.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROPERLY LABEL LIFE PRESERVER AND IMMERSION SUIT STORAGE BOXES IN ACCORDANCE WITH 46 CFR 108.646.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
NUMEROUS IMMERSION SUITS FOUND WITH STUCK AND STIFF OPERATING ZIPPERS. COMPLETE ANNUAL SERVICING OF ALL IMMERSION SUITS.
Condition: Unknown
Due 30 November 1997
Resolved 22 October 1997
Lifesaving
Issued 25 September 1997
Resolved
PROPERLY LABEL ACCESS TO HELO LANDING AREA IN ACCORDANCE WITH 46 CFR 108.653,C and D.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Engineering
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIR, IN LIEU OF TEMPORARY REPAIR, TO LEAKING UNION ON FUEL OIL SUPPLY LINE TO MOTOR ROOM DIESEL ENGINES .
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Unknown
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIR TO DISTILLING PLANT OVERBOARD DISCHARGE PIPING WHERE CURRENTLY TEMPORARILY REPAIRED.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Engineering
Issued 25 September 1997
Resolved
PROVIDE AND INSTALL DRAINPLUG FOR FUEL TANK VENT CONTAINMENT FOR FUEL OIL TANKS #2, +#4.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Electrical
Issued 25 September 1997
Resolved
PROPERLY INSTALL ELECTRICAL CABLE CURRENTLY PLASTIC WIRE TIED TO HALON PIPING ON CONFERENCE ROOM EXTERIOR BULKHEAD.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
PROPERLY INSTALL VERTICAL WIRE RUN ON EXTERIOR OF CONFERENCE ROOM CURRENTLYHANGING FREE.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Accommodation/Occupational Safety
Issued 25 September 1997
Resolved
RENEW CHIPPED AND BROKEN TILES IN GALLEY FLOOR.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
UPDATE ALL ELECTRICAL PANEL BOX DIRECTORIES IN ACCORDANCE WITH 46CFR 111.40-11.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE AND INSTALL HOLD BACK PIN FOR MOTOR ROOM DISCHARGE VENTILATION FLAPPER/CLOSURE.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PERFORM HYDRO TESTING ON OXYGEN BOTTLE FROM HOSPITAL SPACE.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Electrical
Issued 25 September 1997
Resolved
LABEL ESD WARNING LIGHTS IN CEMENT ROOM.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIR TO EMERGENCY LIGHTING FIXTURE IN WAY OF HELO DECK ESCAPE ROUTE PORT SIDE.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVE PROPER OPERATION OF HALON PRESSURE SWITCHES FOR MAIN MOTOR ROOM AND PROPERLY IDENTIFY PURPOSE OF SAME.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
REPAIR AND PROVE PROPER OPERATION OF EMERGENCY LIGHTS FOR ENTIRE REC_x001C_ DECK/MUSTER AREA.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Electrical
Issued 25 September 1997
Resolved
REPAIR AND PROVE PROPER OPERATION OF EMERGENCY LIGHTS FOR ENTIRE REC DECK/MUSTER AREA.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE/INSTALL BULKHEAD/CEILING TILES IN WAY OF SECOND DECK ROOM #211 AND THE SECOND DECK TOILET AND SHOWER AREA IN ACCORDANCE WITH APPROVED SAFETY PLAN, AND 46 CFR 72.05-10 (H).
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Navigation
Issued 25 September 1997
Resolved
REPAIR AND PROVE PROPER OPERATION OF ANCHOR LIGHT ON BOW LEG PORT SIDE.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Documentation
Issued 25 September 1997
Resolved
PROVIDE DOCUMENTATION SHOWING PROOF OF DRUG TESTING PROGRAM IN ACCORDANCE WITH 46 CFR PART 16.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIRS TO FOAM MONITORS ON HELO DECK.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
DEMONSTRATE SPRINKLER SYSTEM. REPAIR ALL DAMAGED SPRINKLER HEADS FOR MARINE PORTABLE TANK FUELING AREA.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Lifesaving
Issued 25 September 1997
Resolved
LABEL GENERAL ALARM BELLS IN ACCORDANCE WITH 46 CFR 108.625 ON THE SHAKER_x001C_ HOUSE ROOF TOP, AND THE STBD CRANE PEDESTAL.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROPERLY MOUNT PORTABLE FIRE EXTINQUISHERS ON THE HELO DECK. _x001C_
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROPERLY LABEL FIRE CONTROL PLAN LOCATION AT HELO DECK.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIRS TO FIRE NOZZLE OF FIRE STATION PORT SIDE OF HELO DECK.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Engineering
Issued 25 September 1997
Resolved
PROPERLY SECURE/MOUNT FUEL HOSES FOR BOTH PORT AND STBD HEATER UNITS.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Construction/Loadline
Issued 25 September 1997
Resolved
OPEN FOR EXAMINATION OVERHAUL AND PROVE PROPER OPERATION OF FROZEN OVERBOARD DISCHARGE VALVES IN STBD P-TANK ROOM.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Engineering
Issued 25 September 1997
Resolved
CONDUCT OPERATIONAL TESTS OF BOTH HEATER UNITS.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Engineering
Issued 25 September 1997
Resolved
PROPERLY SECURE/MOUNT ELECTRICAL CABLES ADRIFT IN BOTH PORT AND STBD HEATERUNITS.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Accommodation/Occupational Safety
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIRS TO WASTED AND HOLED FAN HOUSING IN PORT SIDE_x001C_ HEATER UNIT.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
PROVE PROPER OPERATION OF EMERGENCY LIGHTING (ORIGINIAL) IN EMERGENCY GENERATOR SPACE, BATTERIES DIED IN APPROX 10 MINUTES DURING TEST.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Electrical
Issued 25 September 1997
Resolved
PROVE PROPER OPERATION OF EMERGENCY LIGHTS AT STBD SIDE HELO DECK ESCAPE ROUTE, AND DIRECTLY FORWARD OF THE PAN CANADIAN OFFICE.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Accommodation/Occupational Safety
Issued 25 September 1997
Resolved
PROVIDE PROPER LABEL FOR EVACUATION OF EMERGENCY GENERATOR SPACE WHEN HALONSYSTEM IS ACTIVATED IN ACCORDANCE WITH 46 CFR 108.627.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Engineering
Issued 25 September 1997
Resolved
REPLACE/RENEW ALL DAMAGED SECTIONS OF FUEL OIL TRANSFER HOSE, AND COMPLETE PROPER ANNUAL HYDROSTATIC TEST OF RENEWED/REPLACED/COMPLETE HOSE ASSEMBLY AND LABEL SAME.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVE PROPER OPERATION OF NON OPERATIONAL REMOTE FUEL SHUT OFF VALVE FOR PORT HEATING UNIT.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROPERLY LABEL BOTH PORT AND STBD HEATER UNIT REMOTE FUEL OIL SHUT OFF VALVES.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Engineering
Issued 25 September 1997
Resolved
MAKE FUEL OIL TRANSFER HOSE AVAILABLE FOR INSPECTION.
Condition: Unknown
Due 30 November 1997
Resolved 22 October 1997
Electrical
Issued 25 September 1997
Resolved
PROPERLY SECURE ELECTRICAL CABLE PRESENTLY ADRIFT IN WAY OF HATCHWAY OVER DRAWWORKS.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE COPY OF FIRE SYSTEM SERVICE REPORT AND FOAM ANALYSIS REPORT.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIR TO GENERAL ALARM BELLS IN THE ELECTRIC SHOP, AND MOTOR ROOM, 2ND LEVEL OF ACCOMODATION SPACE, AND DRILL FLOOR.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
MAKE PERMANENT REPAIRS TO GENERAL ALARM CONTACT MAKERS IN MOTOR ROOM AND SHAKER HOUSE.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROPERLY LABEL LIFE RAFT EMBARKATION AREAS IN ACCORDANCE WITH 46 CFR 108.647.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE INSTRUCTIONS FOR EMERGENCY GENERATOR FIXED HALON FIRE FIGHTING SYSTEM IN ACCORDANCE WITH 46 CFR 108.631 AND NAVIGATION INSPECTION CIRCULAR6-72,CH-1.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROVE PROPER OPERATION OF EMBARKATION LIGHTING FOR LIFEBOAT CAPSULES #1, AND #3.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Lifesaving
Issued 25 September 1997
Resolved
PROPERLY LABEL GENERAL ALARM CONTACT MAKER IN SHALE SHAKER ROOM IN ACCORDANCE WITH 46CFR 108.623.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Fire Fighting
Issued 25 September 1997
Resolved
PROVIDE ADEQUATE INSTRUCTIONS FOR MOTOR ROOM FIXED HALON FIRE FIGHTING SYSTEM IN ACCORDANCE WITH 46 CFR 108.631 AND NVIC 6-72,CH-1.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Unknown
Issued 25 September 1997
Resolved
PROVIDE LOG BOOK WITH PROPER ENTRIES IN ACCORDANCE WITH 46CFR 109.431 AND 46CFR 109.433.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
CONDUCT DRILLS ON THE USE OF THE LINE THROWING APPLIANCE AT LEAST ONCE EVERY THREE MONTHS IN ACCORDANCE WITH 46 CFR 109.213 (e).
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROVIDE EMBARKATION LADDERS FOR LIFE RAFT STATIONS IN ACCORDANCE WITH 46_x001C_ CFR 108.545.
Condition: Unknown
Due 25 September 1997
Resolved 25 September 1997
Lifesaving
Issued 25 September 1997
Resolved
PROVIDE LEGIBLE LAUNCHING INSTRUCTIONS FOR STBD LIFE RAFT STATION IN ACCORDANCE WITH 46CFR 108.655.
Condition: Unknown
Due 30 November 1997
Resolved 21 October 1997
Electrical
Issued 6 November 1996
Resolved
PROPERLY DEAD END IMPROPERLY DEAD ENDED CABLE AT MUD PUMP #1.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Electrical
Issued 6 November 1996
Resolved
INSTALL BLANKS WHERE MISSING CIRCUIT BREAKER IN LIGHTING PANELS ML-2 AND ML-3.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Fire Fighting
Issued 6 November 1996
Resolved
REPAIR/RENEW FOAM TANK RELIEF VALVE.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Fire Fighting
Issued 6 November 1996
Resolved
SUBMIT COPIES OF FIRE SERVICE AND FOAM ANALYSIS REPORTS.
Condition: Unknown
Due 6 November 1996
Resolved 6 November 1996
Lifesaving
Issued 6 November 1996
Resolved
COMPLETE EMERGENCY DRILL OPERATIONS SHUTDOWN.
Condition: Unknown
Due 6 November 1996
Resolved 6 November 1996
Lifesaving
Issued 6 November 1996
Resolved
MAKE DRILL FLOOR AIR RECEIVER AND RELIEF VALVE AVAILABLE FOR INSPECTION.
Condition: Unknown
Due 6 November 1996
Resolved 6 November 1996
Electrical
Issued 6 November 1996
Resolved
SUBMIT UPDATED ELECTRICAL PLANS SHOWING THE INSTALLATION OF THE UPS UNIT AND ANY OTHER ELECTRICAL MODIFICATIONS SINCE PREVIOUS SUBMITTAL FOR APPROVAL.
Condition: Unknown
Due 6 November 1996
Resolved 6 November 1996
Lifesaving
Issued 6 November 1996
Resolved
RENEW BOTH LIFERAFT DAVIT FALLS AND PROVIDE RIG SUPERINTENDENT CERTIFICATION OF PROPER INSTALLATION AND SATISFACTORY WEIGHT TEST.
Condition: Unknown
Due 6 November 1996
Resolved 6 November 1996
Lifesaving
Issued 6 November 1996
Resolved
PROVIDE DOCUMENTATION OF TEST TO 225 PSI ON F.O. TRANSFER HOSE.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Lifesaving
Issued 6 November 1996
Resolved
REPAIR OR RENEW SPRUNG STOREROOM DOOR.
Condition: Unknown
Due 6 November 1996
Resolved 6 November 1996
Electrical
Issued 6 November 1996
Resolved
REMOVE OR PROPERLY DEAD END CONTROLLER WIRING AT DISTILLING UNIT.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Lifesaving
Issued 6 November 1996
Resolved
PROVIDE MORE LEGIBLE COPY OF FIRE AND ABANDON SHIP BILL IN CHANGE ROOM.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Lifesaving
Issued 6 November 1996
Resolved
RENEW ESCAPE ROUTE SIGNS ON WALK FROM HELIDECK TO HOUSE.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Fire Fighting
Issued 6 November 1996
Resolved
RENEW DAMAGED FOG APPLICATOR LOCATED AT FIRE PUMP #1.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Lifesaving
Issued 6 November 1996
Resolved
RENEW TEMPORARILY PATCHED DRAIN LINE BETWEEN GENERATORS #3 AND #4.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Electrical
Issued 6 November 1996
Resolved
REBAND FEEDER CABLES AT GENERATORS #4 AND #5.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Fire Fighting
Issued 6 November 1996
Resolved
REPAIR OR RENEW PORT AND STBD FIRE PUMP RELIEF VALVES.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Fire Fighting
Issued 6 November 1996
Resolved
LABEL MANUAL FIRE PULL OUTSIDE CHANGE ROOM.
Condition: Unknown
Due 13 November 1996
Resolved 26 November 1996
Documentation
Issued 5 November 1996
Resolved
SUBMIT PROPOSAL FOR PERMANENT REPAIRS TO FRACTURES NOTED ON BOW LEG, PORT LEG AND STBD LEG SHEER PLATES DURING SPECIAL UNDERWATER EXAMINATION IN LIEUOF DRYDOCKING.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Construction/Loadline
Issued 5 November 1996
Resolved
PERFORM ANNUAL SERVICING ON ALL PRE-LOAD TANK DUMP VALVES (GATE AND CHECK) TO INCLUDE RENEWAL OF SEA CAP SEALS.
Condition: Unknown
Due 20 November 1996
Resolved 3 December 1996
Documentation
Issued 5 November 1996
Resolved
SUBMIT FOR REVIEW, ALL SUB-SEA NDT RESULTS TO INCLUDE DIVE VIDEOS AND DRAWINGS SHOWING LOCATION OF EXISTING AND NEW DEFECTS.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Documentation
Issued 5 November 1996
Resolved
PROVIDE FOR REVIEW, COPIES OF ALL NDT REPORTS ON VESSEL HULL, LEGS, HELIDECK, RAW WATER TOWERS, JACK HOUSE TO DECK WELDS AND CRANE PEDESTAL TO DECK WELDS.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Construction/Loadline
Issued 5 November 1996
Resolved
MAKE PERMANENT REPAIRS TO LADDER AT SPLASH ZONE ON STBD LEG AT NEXT RIG MOVE.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Construction/Loadline
Issued 5 November 1996
Resolved
MAKE SPUD CANS AVAILABLE FOR EXAMINATION AT SURFACE AT THE NEXT RIG MOVE, AND MAKE PERMANENT REPAIR TO ALL SPUD CAN ANAMOLIES NOTED DURING 1993, 1994, AND 1996 SUBSEA INSPECTIONS AS PER THE ABS REPORT #MO 17395 DATED 19SEPT96 AND ROWAN COMPANIES, INC. PROPOSAL DATED OCTOBER 24, 1996.
Condition: Unknown
Due 5 November 1996
Resolved 5 November 1996
Lifesaving
Issued 28 November 1995
Resolved
RENEW ALL OUTDATED PFD LIGHTS.
Condition: Unknown
Due 28 November 1995
Resolved 21 December 1995
Fire Fighting
Issued 28 November 1995
Resolved
RENEW EMERGENCY GENERATOR HALON SYSTEM PRESSURE SWITCH LOCATED ON EXTERIOR BULKHEAD OF EMERGENCY GENERATOR ROOM.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Unknown
Issued 28 November 1995
Resolved
PROVIDE COPIES OF THE FIRE SERVICE REPORT, LIFERAFT SERVICE REPORTS, FOAM ANALYSIS REPORT, CANADIAN COAST GUARD CERTIFICATE AND ABS CRANE CERTIFICATIONS.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Lifesaving
Issued 28 November 1995
Resolved
RENEW FLASH LIGHT BATTERIES IN ALL FOUR LIFEBOATS.
Condition: Unknown
Due 28 November 1995
Resolved 21 December 1995
Fire Fighting
Issued 28 November 1995
Resolved
REPLACE THE THREE (3) FIRE DOORS LEADING INTO AND FROM CHEMICAL ROOM.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Lifesaving
Issued 28 November 1995
Resolved
RESTENCIL ALL IMMERSION SUITS WITH PROPER RIG NAME.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Fire Fighting
Issued 28 November 1995
Resolved
RENEW PILOT HOSES ON RADIO ROOM AND MAIN ENGINE ROOM HALON SYSTEMS.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Fire Fighting
Issued 28 November 1995
Resolved
RENEW SUPPLY VALVE ON RADIO ROOM HALON SYSTEM.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Fire Fighting
Issued 28 November 1995
Resolved
PROVE PROPER OPERATION OF BOTH MAIN FIRE PUMP RELIEF VALVES.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Lifesaving
Issued 28 November 1995
Resolved
TOP OFF ALL LIFEBOAT EMERGENCY AIR BOTTLES TO BRING INTO COMPLIANCE WITH MANUFACTURERS SPECIFICATIONS.
Condition: Unknown
Due 28 November 1995
Resolved 28 November 1995
Lifesaving
Issued 17 November 1994
Resolved
REPLACED LIGHTS AND WHISTLES ON IMMERSION SUITS WHERE NECESSARY. ITEMS COMPLETED DURING INSPECTION.
Condition: Unknown
Due 17 November 1994
Resolved 21 December 1994
Lifesaving
Issued 17 November 1994
Resolved
COMPLETE MODIFICATION TO LIFEBOAT CANOPY TO ALLOW PROPER OPERATION OF LIFEBOAT RADIO ANTENNA.
Condition: Unknown
Due 2 December 1994
Resolved 19 December 1994
Navigation
Issued 17 November 1994
Resolved
REPAIR AND PROVE PROPER OPERATION OF SIGNAL LIGHT.
Condition: Unknown
Due 2 December 1994
Resolved 19 December 1994
Lifesaving
Issued 17 November 1994
Resolved
COMPLETE TEMPORARY REPAIRS TO PORT LIFEBOAT CANOPIES WHERE FRACTURED.
Condition: Unknown
Due 2 December 1994
Resolved 19 December 1994
Documentation
Issued 17 November 1994
Resolved
PROVIDE COPIES OF THE FOLLOWING CERTIFICATES: A) CCGSAFETY CERTIFICATE, B) FIRE FIGHTING EQUIP. SERVICE REPORT, C) FOAM ANALYSIS REPORT, D) LIST OF OUTSTANDING CLASS SURVEY RECOMMENDATIONS.
Condition: Unknown
Due 23 December 1994
Resolved 19 December 1994
Fire Fighting
Issued 17 November 1994
Resolved
REPAIR FIRE DAMPERS # 2,3, AND 12 LOCATED ON TOP OF 3RD LEVEL ACCOMMODATIONS AND DAMPER LOCATED ON TOP OF PRODUCTION OFFICE FOR HVAC.
Condition: Unknown
Due 23 December 1994
Resolved 19 December 1994
Electrical
Issued 17 November 1994
Resolved
EMERGENCY GENERATOR SHUT DOWN INOPERATIVE, WAS REPAIRED BY VESSEL CREW DURING INSPECTION.
Condition: Unknown
Due 17 November 1994
Resolved 21 December 1994
Fire Fighting
Issued 17 November 1994
Resolved
NOTED TWO HOLED FIRE HODES DURING HOSE HYDRO TEST, CREW REPLACED BOTH WITH NEW DURING INSPECTION.
Condition: Unknown
Due 17 November 1994
Resolved 21 December 1994
Accommodation/Occupational Safety
Issued 17 November 1994
Resolved
NOTED TWO GAS DETECTORS INOPERATIVE, CREW REPAIRED DURING INSPECTION.
Condition: Unknown
Due 17 November 1994
Resolved 21 December 1994
Fire Fighting
Issued 17 November 1994
Resolved
REPLACE DETERIORATED HALON PRESSURE SWITCH BOXES FOR THE EMERGENCY GENERATOR HALON SYSTEM.
Condition: Unknown
Due 23 December 1994
Resolved 9 January 1995
Fire Fighting
Issued 17 November 1994
Resolved
HYDRO TEST FIXED HALON FIRE SUPPRESION SYSTEM STORAGE CYLINDERS.
Condition: Unknown
Due 17 November 1994
Resolved 17 November 1994
Accommodation/Occupational Safety
Issued 17 November 1994
Resolved
INSTALL GRATING HOLD DOWNS ON OUTBOARD SIDE OF HVAC UNITS FOR INSTRUMNET SHOP AND TEST LAB.
Condition: Unknown
Due 2 December 1994
Resolved 19 December 1994
Electrical
Issued 17 November 1994
Resolved
REMOVE OR PROPERLY ENCLOSE IN PROPERLY CLASSED JUNCTION BOXES THE DEAD ENDED CABLES IN THE SHALE SHAKER ROOM AND AT THE CHEMICAL INJECTION SYSTEM.
Condition: Unknown
Due 2 December 1994
Resolved 19 December 1994
Accommodation/Occupational Safety
Issued 17 November 1994
Resolved
NOTED #2 RIG AIR RCVR R/V AND "PORT E" BULK TANK R/V NOT OPERATING PROPERLYAND WERE REPLACED WITH NEW DURING THIS INSPECTION.
Condition: Unknown
Due 17 November 1994
Resolved 21 December 1994
Lifesaving
Issued 17 November 1994
Resolved
MOVE INSTALLED RADIO'S IN PORT AND STBD 54 MAN LIFEBOATS TO ALLOW PROPER OPERATION OF EMERGENCY RELEASE.
Condition: Unknown
Due 2 December 1994
Resolved 19 December 1994
Deck/Cargo
Issued 17 November 1994
Resolved
TEST EMERGENCY DRILLING OPERATIONS SHUTDOWN LOCATED NEAR THE DRILLERS CONSOLE.
Condition: Unknown
Due 19 February 1995
Resolved 9 January 1995
Lifesaving
Issued 17 November 1994
Resolved
COMPLETE PERMENENT REPAIRS TO FRACTURES IN WAY OF PORT LIFEBOAT CANOPIES. REPAIRS TO BE COMPLETED BY AUTHORIZED LIFEBOAT REPAIR FACILITY.
Condition: Unknown
Due 17 November 1994
Resolved 17 November 1994
Documentation
Issued 24 November 1993
Resolved
Unknown Component - Unknown Cause/Condition
Condition: Unknown
Due 26 December 1993
Resolved 2 December 1993
Documentation
Issued 24 November 1993
Resolved
AS PER U. S. COAST GUARD MSC-2 LETTER E-20372 OF 07 MAY 1992, PARAGRAPH 3, SUBMIT THE REQUIRED INFORMATION FOR APPROVAL, PRIOR TO OPERATING THE INSTALLED SOLAR GAS TURBINE GENERATOR IN PARALLEL WITH SHIPS SERVICE GENERATORS.
Condition: Unknown
Due 24 December 1993
Resolved 14 February 1994
Construction/Loadline
Issued 2 November 1993
Resolved
PROVIDE ALL STRUCTURAL ANALYSIS INFORMATION REGARDING REQUIREMENT E1 FROM AMERICAN BUREAU OF SHIPPING(ABS) AND RIG MANUFACTURER MARATHON-LETOURNEAU INC.,INCLUDING HISTORICAL DATA AS APPLICABLE. THIS REQUIREMENT IS TO BE METWITHIN 30 DAYS.
Condition: Unknown
Due 2 November 1993
Resolved 2 November 1993
Construction/Loadline
Issued 2 November 1993
Resolved
PERFORM SEMI-ANNUAL MONITORING BY MPI OF ANOMALIES NOTED DURING UNDERWATER SURVEY CONDUCTED 30 OCT 1993. ANOMALIES ARE AS NOTED: 1) BOW LEG CHORD "A"-LOCATED AT TOP OF CAN AND BOTTOM OF T-BEAM GUSSET PLATE 25MM CRACK AT TOE OF WELD. 2) STBD LEG CHORD "F"-LOCATED AT TOP OF CAN AND ADJACENT SHEAR
Condition: Unknown
Due 2 November 1993
Resolved 2 November 1993
Fire Fighting
Issued 26 October 1993
Resolved
PROVIDE FOAM ANALYSIS REPORT.
Condition: Unknown
Due 25 November 1993
Resolved 1 December 1993
Unknown
Issued 26 October 1993
Resolved
PROVIDE SATISFACTORY ABS EXAMINATION REPORT OF CRANES.
Condition: Unknown
Due 25 November 1993
Resolved 1 December 1993
Lifesaving
Issued 26 October 1993
Resolved
CONDUCT EMERGENCY SHUT DOWN OF DRILL RIG.
Condition: Unknown
Due 25 November 1993
Resolved 1 December 1993
Lifesaving
Issued 26 October 1993
Resolved
STENCIL "EMERGENCY OUTFITS" OUTSIDE LOCKER.
Condition: Unknown
Due 25 November 1993
Resolved 1 December 1993
Documentation
Issued 26 October 1993
Resolved
PROVIDE VALID/ENDORSED LOADLINE CERTIFICATE.
Condition: Unknown
Due 25 November 1993
Resolved 1 December 1993
Documentation
Issued 26 October 1993
Resolved
PROVIDE U. S. COAST GUARD APPROVED FIRE CONTROL PLAN.
Condition: Unknown
Due 26 October 1993
Resolved 26 October 1993
Unknown
Issued 26 October 1993
Resolved
REPLACE FUEL IN LIFE BOAT CAPSULES.
Condition: Unknown
Due 25 November 1993
Resolved 7 January 1994
Documentation
Issued 26 October 1993
Resolved
PROVIDE, ONBOARD, APPLICABLE U. S. CODE OF FEDERAL REGULATION PUBLICATIONS AS APPLICABLE.
Condition: Unknown
Due 23 November 1993
Resolved 1 December 1993
Fire Fighting
Issued 26 October 1993
Resolved
REPLACE THREE (3) DEFECTIVE 2.5" FIRE HOSE.
Condition: Unknown
Due 25 November 1993
Resolved 7 January 1994
Fire Fighting
Issued 26 October 1993
Resolved
PROVIDE FIRE EXTINGUISHER SERVICE REPORT.
Condition: Unknown
Due 25 November 1993
Resolved 1 December 1993
Electrical
Issued 13 January 1993
Resolved
AS PER US COAST GUARD MSC-2 LETTER E-20372 OF 7MAY92 PARA. 1,c DETAILS MUSTBE SUBMITTED FOR THE PURGE AND PRESSURIZATION SYSTEM FOR THE GAS TURBINE GENERATOR ENCLOSURERS.
Condition: Unknown
Due 13 January 1993
Resolved 13 January 1993
Lifesaving
Issued 20 November 1992
Resolved
Test releasing gear on life capsules #1, 2, and 4 by lowering capsules intothe water. These tests shall be done at the first opportunity in fair weather. Testing results shall logged and a copy of the entry forwarded toUSCG Marine Safety Office Boston.
Condition: Unknown
Due 20 November 1992
Resolved 20 November 1992
Lifesaving
Issued 20 November 1992
Resolved
Hold exposure suit drills monthly. As per 46CFR109.215 every member onboard shall don an exposure suit monthly and shall be instructed in its use. A copy of the results of drills held up through the end of CY 1992 shall be forwarded to USCG Marine Safety Office Boston.
Condition: Unknown
Due 31 December 1992
Resolved 13 January 1993
Electrical
Issued 20 November 1992
Resolved
Complete operational tests of the newly installed turbine generators and fixed CO2 systems prior to placing them into operation. These tests shall be witnessed by a USCG marine inspector.
Condition: Unknown
Due 20 November 1992
Resolved 20 November 1992
Fire Fighting
Issued 20 November 1992
Resolved
Provide currrent copy of fixed fire fighting servicing reports.
Condition: Unknown
Due 9 December 1992
Resolved 9 December 1992
Engineering
Issued 20 November 1992
Resolved
Provide documentation on the newly installed control air reciever in the cement room.
Condition: Unknown
Due 9 December 1992
Resolved 9 December 1992
Lifesaving
Issued 20 November 1992
Resolved
Renew rusted line throwing gun canister.
Condition: Unknown
Due 31 December 1992
Resolved 13 January 1993
Deck/Cargo
Issued 11 November 1991
Resolved
PROVIDE MECHANICAL PROTECTION SHIELDS FOR ALL APPLETON CABLE TRANSIT DECK PENETRATIONS PRIOR TO DEPARTURE FROM THE PORT OF DARTMOUTH NOVA SCOTIA.
Condition: Unknown
Due 2 December 1991
Resolved 2 December 1991
Electrical
Issued 11 November 1991
Resolved
ALL ELECTRICAL CABLE GLANDS AND FIXTURES IN NEWLY RECLASSIFIED HAZARDOUS AREAS (MAIN DECK SKID, MUD PUMP ROOM, INJECTOR WATER PUMP ROOM AND CHEMICALSTORE ROOM) MUST BE UPGRADED TO THE PROPER CLASSIFICATION FOR EXPLOSION PROOF EQUIPMENT AS SHOWN ON THE REVISED HAZARDOUS LOCATION DRAWINGS.
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Lifesaving
Issued 11 November 1991
Resolved
NEWLY RECLASSIFIED HAZARDOUS AREAS MAIN DECK, MUD PUMP ROOM, INJECTOR WATERPUMP ROOM, AND CHEMICAL STORE ROOM MUST BE PROVIDED WITH HYDROGEN SULPHIDE H2S AND GAS INDICATOR ALARMS.
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Lifesaving
Issued 11 November 1991
Resolved
RESTENCIL NEWLY RECLASSIFIED HAZARDOUS AREAS AT EACH ENTRANCE.
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Fire Fighting
Issued 11 November 1991
Resolved
TRANSFORMER SWITCH ROOM LOCATED ON THE MAIN DECK MUST BE EQUIPPED WITH A FIXED GASEOUS FIRE PROTECTION SYSTEM. SUBMIT PLANS TO THE USCG MARINE_x001C_ SAFETY CENTER WASHINGTON PRIOR TO INSTALLATION
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Electrical
Issued 11 November 1991
Resolved
PROVIDE A PROPER BREAKAWAY TYPE PORTABLE PLUG FOR CHARGING THE RIGS FORK LIFT (46 CFR 108.615)
Condition: Unknown
Due 2 December 1991
Resolved 2 December 1991
Documentation
Issued 11 November 1991
Resolved
POST UPDATED FIRE SAFETY AND ESCAPE PLANS INDICATING MODIFIED MAIN DECK SKID AND NEWLY ADDED CONFERENCE ROOM AREAS - PRIOR TO UNIT DEPARTING THE PORT OF DARTMOUTH NOVA SCOTIA.
Condition: Unknown
Due 2 December 1991
Resolved 2 December 1991
Engineering
Issued 11 November 1991
Resolved
RENEW FLEXIBLE FUEL HOSE FROM THE HELICOPTER FUEL TANK TO THE PUMPING STATION WITH A PROPER HOSE AND CONNECTIONS. ITEM TO BE COMPLETED PRIOR TO DEPARTING THE PORT OF DARTMOUTH NOVA SCOTIA.
Condition: Unknown
Due 2 December 1991
Resolved 2 December 1991
Electrical
Issued 11 November 1991
Resolved
CORRECT IMPROPER RADIUS BENDS OF CABLES (DIA 5 TIMES INNER BEND) AND IMPROPER CABLE TRAYS AND STACKING OF CABLES IN THE TRANSFORMER SWITCH GEAR ROOM. ITEM MUST BE COMPLETED PRIOR TO UTILIZING THIS ROOM FOR THE HYDORCARBON PRODUCTION EQUIPMENT.
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Electrical
Issued 11 November 1991
Resolved
PROVIDE ONE LINE ELECTRICAL DRAWING OF THE TWO NEW TURBINE GENERATORS WHICHHAVE BEEN TIED INTO THE MAIN SWICHBOARD. GENERATORS ARE NOT BE USED PRIOR TO REVIEW, INSTALLATION, AND OPERATIONAL TEST. A FIXED GASEOUS FIRE EXTINGISHING SYSTEM AND TWO ADDITIONAL B-II FIRE EXT. MUST ALSO BE PROVIDED
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Accommodation/Occupational Safety
Issued 11 November 1991
Resolved
UPDATE ACCOMODATION DRAWINGS FOR PROPOSED INCREASE FROM 86-92 TOTAL PERSONSALLOWED. PLANS SHOULD BE SENT TO THE MARINE SAFETY CENTER IN WASHINGTON DCFOR APPROVAL.
Condition: Unknown
Due 11 February 1992
Resolved 7 January 1992
Engineering
Issued 11 November 1991
Resolved
CONDUCT OPERATIONAL TEST OF GLYCOL BOILER PRIOR TO OPERATING AS A HYDROCARBON PRODUCTION UNIT.
Condition: Unknown
Due 11 November 1991
Resolved 11 November 1991
Electrical
Issued 13 December 1990
Resolved
REPAIR OR REPLACE DEFECTIVE GENERAL ALARM BELLS ON 2ND AND 3RD ACCOMODATIONS DECK.
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Engineering
Issued 13 December 1990
Resolved
PROVIDE INFO ON CLAYTON PACKAGE BOILERS AND CONDUCT HYDRO TEST IF DEEMED NECESSARY.
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Electrical
Issued 13 December 1990
Resolved
PROVE OPERATION OF PURGE AIR SYSTEM ON DRILL FLOOR.
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Engineering
Issued 13 December 1990
Resolved
PROVIDE FLAME SCREENS TO VENTS ON DAY TANK STBD SIDE GENERATOR ROOM.
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Deck/Cargo
Issued 13 December 1990
Resolved
PROVIDE WARNING DEVICE FOR FORKLIFT
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Lifesaving
Issued 13 December 1990
Resolved
PROVIDE ADDITIONAL 240 BAGS WATER FOR #4 L/B AND 50 BAGS FOR #3 L/B
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Lifesaving
Issued 13 December 1990
Resolved
PROVIDE ADDITIONAL 69 EXPOSURE SUITS
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Electrical
Issued 13 December 1990
Resolved
RENEW ALL WASTED WIRE CLIPS ON NL/B DAVITS AND SHAKER HOUSE
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Engineering
Issued 13 December 1990
Resolved
REPAIR HOLES IN DIESEL FUEL LINE IN STBD P. TANK ROOM.
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Lifesaving
Issued 13 December 1990
Resolved
PROVIDE INFO ON LAST L/B FALL RENEWAL
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Fire Fighting
Issued 13 December 1990
Resolved
MAKE PERMANENT REPAIR IN WAY TEMP REPAIR TO FIRE MAIN IN HALIBURTION ROOM.
Condition: Unknown
Due 13 December 1990
Resolved 13 December 1990
Construction/Loadline
Issued 25 January 1990
Resolved
MAKE DOOR TO MUD PIT ROOM, PORT SIDE, AIRTIGHT IN WAY OF BULKHEAD.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Deck/Cargo
Issued 25 January 1990
Resolved
SECURE AIR CONTROL LINES TO FORWARD MUD PIT ROOM BULKHEAD.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Electrical
Issued 25 January 1990
Resolved
LABEL AND TEST EMERGENCY SHUTDOWNS ON DRILLERS CONSOLE.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Electrical
Issued 25 January 1990
Resolved
RE-STUFF OR RE-PACK ALL LOOSE WIRES IN WIRING BLOCK IN WAY OF BULKHEAD BEHIND DRILLERS CONSOLE.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Fire Fighting
Issued 25 January 1990
Resolved
PROVIDE ON BOARD TWO (02) APPROPRIATE 2 1/2"X50' FIRE HOSES.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Navigation
Issued 25 January 1990
Resolved
MAKE ALL OBSTRUCTION LIGHTS OPERATIONAL.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Fire Fighting
Issued 25 January 1990
Resolved
PROVIDE SERVICE REPORT OF FIRE FIGHTING EQUIPMENT TO MSO PORT ARTHUR, TX.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Electrical
Issued 25 January 1990
Resolved
REPAIR AND TEST REMOTE SHUTDOWNS FOR MACHINERY SPACE VENTILATION AND FUEL OIL TRANSFER PUMP.
Condition: Unknown
Due 25 January 1990
Resolved 25 January 1990
Lifesaving
Issued 2 March 1989
Resolved
MAKE PERMANENT REPAIRS TO THE #3 LIFEBOAT ENGINE.
Condition: Unknown
Due 2 March 1989
Resolved 2 March 1989
Engineering
Issued 10 December 1986
Resolved
PROVE PROPER OPERATION, UNDER STEAM PRESSURE, OF BOTH RELIEF VALVES ON EACHBOILER (4 VALVES) IN THE PRESENCE OF A COAST GUARD MARINE INSPECTOR.
Condition: Unknown
Due 10 December 1986
Resolved 10 December 1986
Fire Fighting
Issued 11 December 1985
Resolved
REPAIR AND DEMONSTRATE OPERATION FOAM SPRINKLERS FOR HELOCOPTER FUEL PUMP AND FUEL STORAGE BAY
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Electrical
Issued 11 December 1985
Resolved
PROVIDE DOCUMENTATION TO MSO MOBILE THAT THE FOLLOWING EXPLOSION PROOF FIXTURES ARE UL OR FM APPROVED OR EQUIVILENT, OR REPLACE THEM, OR PROVIDE AIR PURGE: VARIOUS FIXTURES IN MUD PIT ROOM, SHALE SHAKER ROOM, AND ON DRILL FLOOR.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Fire Fighting
Issued 11 December 1985
Resolved
PROVIDE PROPER LABELS AND INSTRUCTIONS FOR FIXED HALON SYSTEMS FOR ER & SCR RM, EMERGENCY GEN, ROOM, AND CONTROL.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
PROVIDE PROPER OIL TRANSFER PROCEDURES AS PER 33CFR 155.720
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Electrical
Issued 11 December 1985
Resolved
PROVIDE USCG OR ABS APPROVED HAZARDOUS AREA LOCATION PLAN TO VERIFY NEGATIVE PRESSURE IN MUD PIT RM, DEMONSTRATE LOSS OF NEGATIVE PRESSURE ALARM FOR MUD PIT ROOM (ON RIG FLOOR). PROPERLY LABEL DRILL FLOOR ALARM SIGNAL.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Electrical
Issued 11 December 1985
Resolved
PROPERLY LABEL LOSS OF PURGE AIR ALARM ON DRILL FLOOR
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Fire Fighting
Issued 11 December 1985
Resolved
PRESSURE UP ON TWO LOW PRESSURE HALON CYLINDERS FO ER/SCR RM AS REQUIRED BY HILLER REPORT OF 12-3-85, PAGE 3.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Construction/Loadline
Issued 4 July 1985
Resolved
MAKE DESIGN CHANGES AND REPAIRS TO THREE SPUD CANS USING GOOD MARINE PRACTICE.
Condition: Unknown
Due 4 July 1985
Resolved 4 July 1985