MAURY USCG vessel records Sign in
← All vessels

USNS COMFORT

USNS COMFORT is a 1987 public vessel, unclassified. The Coast Guard has recorded 191 inspections since 1987, most recently in April 2026, along with 332 deficiencies — 5 with no resolution recorded — and 2 operational controls.

Records from 1987 to 2026. Most recent: inspection, 8 April 2026.

Built
1987
Last inspected
8 April 2026
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

7390478 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
271430
Flag
UNITED STATES
—
Maury page id
psix-271430

Inspections, by type

…with no type recorded33
…past their stated due date1
Years with a record 37 calendar years (1987–2026)
The 191 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Miscellaneous Vessel class in Maury's sources begin in 1979.

Documentation record

Tonnage as PSIX records it63527 - Convention (Subpart B), Gross Ton
54367 - Regulatory (Subpart C or D), Gross Ton
19058 - Convention (Subpart B), Net Ton
35958 - Regulatory (Subpart C or D), Net Ton
44578 - Dead Weight, Ton
69360 - Displacement, Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

Inspection history · 191

8 April 2026 Type not recorded
No type recorded · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8352686
24 March 2026 Damage Survey
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8332653
17 November 2025 Periodic Inspection · Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8269527
25 September 2025 Examination of Repairs · Damage Survey · In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8241338
27 August 2025 Damage Survey
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8219260
4 June 2025 Administrative Inspection · In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8151901
13 May 2025 Deficiency Check · Damage Survey · Examination of Repairs
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8135038
22 August 2024 In-Service Inspection · Administrative Inspection · Examination of Repairs
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7991832
17 July 2024 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7960303
20 June 2024 Damage Survey
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7938495
9 June 2024 Type not recorded
No type recorded · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7970333
9 May 2024 Annual Inspection · Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7909595
29 January 2024 Administrative Inspection · In-Service Inspection · Examination of Repairs
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7857393
18 September 2023 Administrative Inspection · In-Service Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7796028
24 May 2023 Deficiency Check · Damage Survey
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7695767
23 May 2023 Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7694780
24 January 2023 Damage Survey · Deficiency Check · In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7626299
9 January 2023 Deficiency Check · In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7618343
4 November 2022 Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7589484
18 October 2022 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7579560
14 September 2022 COI Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7563870
3 March 2022 Examination of Repairs · Administrative Inspection · In-Service Inspection · Drydock Exam
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7409380
22 February 2022 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7400546
8 February 2022 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7394987
18 January 2022 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7381990
10 December 2021 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7367323
3 December 2021 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7362939
16 November 2021 Annual Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7344574
3 November 2021 In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7344871
26 October 2021 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7339898
21 July 2021 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7263578
23 April 2021 In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7181556
22 April 2021 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7180713
15 April 2021 Deficiency Check · Administrative Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7175365
30 March 2021 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7165357
30 March 2021 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7166040
4 January 2021 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7119405
29 December 2020 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7117325
18 December 2020 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7113830
7 December 2020 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7107770
2 December 2020 Periodic Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7106530
4 November 2020 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 7089746
7 October 2020 Administrative Inspection · In-Service Inspection · Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 7080399
9 May 2020 Type not recorded
No type recorded · Sector Virginia · USCG East District (CGD-E) · Activity 6970917
15 April 2020 Damage Survey
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6939516
1 April 2020 Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6934067
10 March 2020 Administrative Inspection · Annual Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6923608
20 November 2019 In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6860716
7 September 2019 Type not recorded
No type recorded · Sector Virginia · USCG East District (CGD-E) · Activity 6898898
18 July 2019 Deficiency Check · Damage Survey · Administrative Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6755094
18 July 2019 Type not recorded
No type recorded · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6776046
9 June 2019 Damage Survey
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6710263
9 June 2019 Type not recorded
No type recorded · Sector Virginia · USCG East District (CGD-E) · Activity 6710919
24 May 2019 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6692508
11 April 2019 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6661433
8 January 2019 Administrative Inspection · Special · Examination of Repairs · Annual Inspection · Spot Check · Deficiency Check
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 6625789
19 October 2018 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 6564601
18 October 2018 Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6563911
28 September 2018 Deficiency Check · Administrative Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6550868
24 September 2018 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6548892
10 September 2018 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6537860
16 August 2018 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6514707
3 August 2018 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6511963
16 July 2018 In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6482529
5 July 2018 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6469783
3 May 2018 Deficiency Check · In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6405907
15 December 2017 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6326549
27 November 2017 COI Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6312796
29 September 2017 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 6278099
27 September 2017 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6276361
20 March 2017 Hull Examination · In-Service Inspection
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6110055
1 March 2017 In-Service Inspection · Damage Survey
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6097217
28 February 2017 Type not recorded
No type recorded · Sector Virginia · USCG East District (CGD-E) · Activity 6097433
16 December 2016 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6063436
14 November 2016 Annual Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 6040335
4 November 2016 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 6035517
2 November 2016 Plan Review (Other than "T")
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 6076157
15 March 2016 In-Service Inspection · Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 5834384
22 February 2016 Annual Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 5811992
19 February 2016 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 5826604
16 February 2016 In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 5816480
9 October 2015 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 5741849
21 August 2015 Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 5222686
26 March 2014 In-Service Inspection · Deficiency Check
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 4823780
25 July 2012 Damage Survey
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 4390851
28 February 2012 Internal Structural Exam · Drydock Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 4253598
23 February 2012 In-Service Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 4249754
16 February 2012 In-Service Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 4245615
15 September 2011 In-Service Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 4143116
9 November 2010 Construction Oversight
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3887968
14 October 2010 Periodic Inspection · In-Service Inspection · Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3869852
13 September 2010 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3848875
17 February 2010 Administrative Inspection
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3680983
20 July 2009 Excursion Permit
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 3540617
23 January 2009 Type not recorded
No type recorded · Commandant (CG-5P-TI) · Activity 3403742
4 December 2008 Deficiency Check · Annual Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3373893
14 August 2008 Administrative Inspection
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3298117
19 November 2007 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3097531
23 October 2007 Plan Review (Other than "T")
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 3087663
12 June 2007 Administrative Inspection
Administrative · Sector Virginia · USCG East District (CGD-E) · Activity 2960186
8 June 2007 Damage Survey
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 2977586
23 May 2007 Administrative Inspection
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 2953089
14 May 2007 Hull Examination
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 2883294
9 April 2007 Administrative Inspection
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 2904321
8 November 2005 Periodic Inspection · MTSA Verification
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 2565655
23 September 2005 Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2511814
19 October 2004 MTSA/ISPS Verification · Annual Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 2268661
10 September 2004 Type not recorded
No type recorded · MSO PORTLAND MAINE · USCG Northeast District (CGD-NE) · Activity 2238884
2 September 2004 Damage Survey
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 2216840
31 August 2004 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 2182004
19 August 2004 Type not recorded
No type recorded · MSO PROVIDENCE · USCG Northeast District (CGD-NE) · Activity 2170807
23 June 2004 MTSA/ISPS Verification
Physical examination · Commandant (CG-CVC) · Activity 2108088
9 February 2004 Annual Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1949187
29 January 2004 Security Plan Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 1997065
3 December 2002 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1712954
26 June 2002 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1636897
7 May 2002 Hull Examination · Internal Structural Exam · COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1613910
1 June 2001 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1065502
15 July 2000 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1365865
14 December 1999 Administrative
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 813862
14 December 1999 Examination of Repairs · COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1372855
13 January 1999 Administrative
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 810479
8 December 1998 Re-Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1388667
22 June 1998 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 793547
14 April 1998 Administrative
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 788467
8 December 1997 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1364483
15 July 1997 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1413207
27 June 1997 Damage Survey
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1113503
26 June 1997 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 161311
3 June 1997 Hull Examination
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1375027
22 January 1997 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1099695
23 December 1996 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1094931
4 November 1996 Re-Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1453300
24 October 1996 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1161491
30 April 1996 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 88752
14 December 1995 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 879042
13 December 1995 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1084202
22 March 1995 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 961952
16 February 1995 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 865656
16 February 1995 Administrative
Administrative · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1189755
3 August 1994 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1442168
6 July 1994 Administrative
Administrative · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1171771
28 May 1994 Hull Examination
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1462394
7 February 1994 Examination of Repairs · Damage Survey · Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1326462
21 December 1993 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 853540
13 August 1993 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 846512
5 May 1993 Examination of Repairs · Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1428204
21 December 1992 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 830098
13 June 1992 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1449549
3 June 1992 Hull Examination
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 950781
20 April 1992 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 117243
24 January 1992 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1435312
30 August 1991 Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 935003
9 August 1991 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1248664
8 July 1991 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 934748
28 May 1991 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1224857
23 May 1991 Type not recorded
No type recorded · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 1243166
14 May 1991 Type not recorded
No type recorded · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 1215213
8 May 1991 Type not recorded
No type recorded · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1206397
7 May 1991 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 918725
2 May 1991 Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 934189
27 March 1991 Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 998994
8 January 1991 COI Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 910859
3 January 1991 Type not recorded
No type recorded · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 901786
19 December 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1223065
14 September 1990 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1227826
14 August 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1238522
13 August 1990 Deficiency Check
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 918880
10 August 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 904121
30 July 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1215710
27 April 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1235899
23 April 1990 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 924121
13 April 1990 COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1228993
13 February 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 911114
5 February 1990 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1286324
26 January 1990 Examination of Repairs
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1212796
5 January 1990 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 909207
21 November 1989 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1228237
8 November 1989 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 912129
25 October 1989 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1222750
20 October 1989 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1200607
3 October 1989 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1329650
29 September 1989 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1322864
28 July 1989 Hull Examination
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1196587
27 July 1989 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1037906
11 May 1989 Deficiency Check
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1194649
9 May 1989 Type not recorded
No type recorded · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1038852
31 March 1989 Drydock Extension · COI Inspection
Physical examination · Sector Maryland-National Capital Region · USCG East District (CGD-E) · Activity 1348711
11 January 1989 Type not recorded
No type recorded · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 1196978
9 February 1988 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1018822
1 December 1987 COI Inspection · Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1030269

Deficiency record · 332

07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 21 November 2025 Resolved
The fire detection and alarm system must be capable of immediate operation at all times that the vessel is in service. The fire control panel was not alarming when heat detection and manual pull stations were tested. 46CFR76.27-5(b)
Action required: 60 - Rectify deficiencies prior to movement
Resolved 11 December 2025
Resolution: Fire detection panel repaired by Hiller.Tested the following: Zone 42, Zone 32, Zone 23
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 21 November 2025 Resolved
Each liferaft or group of liferafts must be arranged for float-free launching. The arrangement must ensure that the liferaft or liferafts, when released and inflated, are not dragged under by the sinking vessel. A hydrostatic release unit used in a float-free arrangement must be approved under approval series 160.162. Inflatable life rafts were rigged with wire that was not float free. 46CFR199.130(c)(7)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 January 2026
Resolution: Weak links installed
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 21 November 2025 No resolution recorded
Each vessel must carry a lifejacket for each person on board. All kapok style lifejackets on board were found deteriorated and unserviceable. Persons on board will be reduced by 683 persons. Total persons allowed on board is 1,482. 12JAN26: Revised to the following- Persons on board will be reduced by 195 persons. Total persons allowed on board is 1,970. 46 CFR 199.70(b)(1)
Action required: 705 - Other - as specified
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 21 November 2025 Resolved
For each watertight door which is in a required subdivision bulkhead, an indicator light must be installed in the pilothouse and at each other vessel operating station from which the door is not visible. The indicator must show whether the door is open or closed. WTD indicator on the bridge has multiple inoperable lights. 46CFR170.270(e)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 December 2025
Resolved 12 January 2026
Resolution: Corrected lights
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 21 November 2025 Resolved
All doors, except those that are kept normally closed, shall be of a type which are capable of release from the control station and from a position at the door. Fire screen door and ladder well doors not closing numbers,1-70-2. 46 CFR 72.05-25(b)(9)(ii)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 December 2025
Resolved 11 December 2025
Resolution: Fire screen door fixed. Closed properly
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 21 November 2025 Resolved
Doors, other than those which are normally locked, such as from staterooms, fan rooms, lockers, etc., shall be of the self-closing type capable of closing against a 3 1/2 degree list. Doors 1-59-1 and 4-68-2 did not self-close. 46 CFR 72.05-25(b)(9)(i)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 December 2025
Resolved 11 December 2025
Resolution: Doors fixed, close properly
04 - Emergency Systems › N/A - No Subsystem › Means of communication between safety centre and other control stations
Issued 21 November 2025 No resolution recorded
Each vessel must have a means of communication among the navigating bridge and the steering gear room, if outside the engine room. Vessels 1JV sound powered phone for the bridge and steering gear room was inoperable. The vessel has multiple redundant communication systems, including handheld radios and dial telephones, must be corrected by 28 FEB 2026. 46CFR 113.30-5
Action required: 705 - Other - as specified
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 21 November 2025 Resolved
Each lifeboat must be launched with its assigned operating crew aboard and maneuvered in the water at least once every 3 months during an abandon-ship drill. Port side lifeboats have not been launched in the last 3 months. 46CFR199.180(d)(4)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 January 2026
Resolution: Launching complete.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 21 November 2025 Resolved
As far as is reasonable and practicable, rescue boats, other than lifeboats which are also rescue boats, must be launched with their assigned crew aboard and maneuvered in the water each month. Such launching and maneuvering must occur at least once every 3 months. Port side rescue boat has not been launched in the last 3 months. 46CFR199.180(d)(7)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 January 2026
Resolution: Launching complete.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 21 November 2025 No resolution recorded
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. #5 life boat hook indicator panel was showing a fault. Lifeboat has been locked out. Repairs to be made prior to 28 FEB 2026 46 CFR 199.190(a)
Action required: 705 - Other - as specified
08 - Alarms › N/A - No Subsystem › General alarm
Issued 21 November 2025 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. General alarm bell was inoperable on flight deck. 46 CFR 199.190(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: General alarm fixed
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 November 2025 Resolved
Protection of passengers, crew, other persons, and the vessel from electrical hazards. Missing blanks on panel ELT-5, EP-607. Ground on Medical Equipment breaker on main deck IVO ICU STBD side. 46 CFR 111.01-1(a)(2)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 15 December 2025
Resolution: Received pictures of installed blanks
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 November 2025 Resolved
Illuminated exit signs are required and must be installed in accordance with subchapter J (Electrical Engineering Regulations) of this chapter. Emergency exit lights were inoperable at the following locations 4-68-1,3-81-1,2-71-01, third deck lounge (the village). 46 CFR 78.47-40(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Exit signs fixed
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 November 2025 Resolved
Electric installations on vessels must ensure: Protection of passengers, crew, other persons, and the vessel from electrical hazards. Multiple grounds & burnt-out bulbs were noted on ground indicators on AMR switchboard. 46CFR111.01-1(a)(2)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Grounds fixed
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 November 2025 Resolved
Electric installations on vessels must ensure: Protection of passengers, crew, other persons, and the vessel from electrical hazards. Ground was indicated on 120v Load Center Ground detection on ECR main control board. 46CFR111.01-1(a)(2)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Grounds fixed
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 21 November 2025 Resolved
Electric installations on vessels must ensure: Protection of passengers, crew, other persons, and the vessel from electrical hazards. A/C SW Pump switch was not properly installed into AMR board and open areas around switch were covered with electrical tape. 46CFR111.01-1(a)(2)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Corrected
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 21 November 2025 Resolved
Piping conveying oil must be run away from hot surfaces wherever possible. Where such leads are unavoidable, only welded joints are to be used, or alternatively, suitable shields are to be fitted in the way of flanged or mechanical pipe joints when welded joints are not practicable. Multiple lube oil flanges on ADGs were missing shields or improperly installed. 46CFR56.50-60(j)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Shields installed
09 - Working and Living Conditions › 092 - Working Conditions › Protection machines/parts
Issued 21 November 2025 Resolved
The applicable standards established by the ABS Marine Vessel Rules (incorporated by reference, see § 58.03-1), may be used as the standard for the design, construction, and testing of main and auxiliary machinery except as modified in this subchapter. SSDG was missing factory installed support bracket on fwd side of engine for high pressure fuel lines. 46CFR58.01-5
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Support bracket installed
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 November 2025 Resolved
Valves must be designed for the maximum pressure to which they may be subjected, but in no case must the design pressure be less than 50 psig. Fire Station No.33 had valve leaking by when system was energized. 46CFR56.20-9(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Valve replaced
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 November 2025 Resolved
Valves must be designed for the maximum pressure to which they may be subjected, but in no case must the design pressure be less than 50 psig. Fire Station 1-8-8 had valve leaking by when system was energized. 46CFR56.20-9(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Valve replaced
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 November 2025 Resolved
Valves must be designed for the maximum pressure to which they may be subjected, but in no case must the design pressure be less than 50 psig. Fire Station No. 46 had valve leaking by when system was energized. 46CFR56.20-9(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Valve replaced
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 November 2025 Resolved
Valves must be designed for the maximum pressure to which they may be subjected, but in no case must the design pressure be less than 50 psig. Fire Station 91 wye gate had valve leaking by when system was energized. 46CFR56.20-9(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 November 2025
Resolved 11 December 2025
Resolution: Valve replaced
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 November 2025 Resolved
Valves must be designed for the maximum pressure to which they may be subjected, but in no case must the design pressure be less than 50 psig. Fire Station 2-53-2 had valve leaking by when system was energized. 46CFR56.20-9(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Valve replaced
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 21 November 2025 Resolved
Valves must be designed for the maximum pressure to which they may be subjected, but in no case must the design pressure be less than 50 psig. Fire Station 3-67-1 had valve leaking by when system was energized. 46CFR56.20-9(c)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Valve replaced
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 21 November 2025 Resolved
Portable fire extinguishers and their stations must be numbered in accordance with 78.47-30. Extinguisher #264 in AMR was missing, a extinguisher was found nearby on deck that did not match number of this station. 46CFR76.50-10(e)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Fire extinguisher replaced
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 21 November 2025 Resolved
Portable fire extinguishers and their stations must be numbered in accordance with 78.47-30. Extinguisher #174 was missing in service area #1 & a CG unapproved extinguisher was found nearby on deck. 46CFR76.50-10(e)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 December 2025
Resolved 11 December 2025
Resolution: Replaced and removed
04 - Emergency Systems › N/A - No Subsystem › Emergency steering position com./ compass reading
Issued 21 November 2025 Resolved
Each vessel must have an illuminated repeater for the gyrocompass required under paragraph (b) that is at the main steering stand unless the gyrocompass is illuminated and is at the main steering stand. Gyrocompass repeater in the steering gear compartment reading was not the same as the reading from the gyrocompass on the bridge. Corrected on the spot. 46CFR96.17-1(c)
Action required: 10 - Deficiency Rectified
Resolved 21 November 2025
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 21 November 2025 Resolved
Each muster station and embarkation station must be adequately illuminated by lighting with power supplied from the vessel's emergency source of electrical power. Vessel has multiple embarkation lights out on both the port and stbd sides. Corrected on the spot. 46CFR199.110(c)
Action required: 10 - Deficiency Rectified
Resolved 21 November 2025
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 21 November 2025 Resolved
Each generator prime mover must have an overspeed device that is independent of the normal operating governor and so adjusted that the speed cannot exceed the maximum rated speed by more then 15 percent. Emergency diesel generator overspeed failed to function when tested. Corrected on the spot. 46CFR111.12(b)
Action required: 10 - Deficiency Rectified
Resolved 21 November 2025
09 - Working and Living Conditions › 092 - Working Conditions › Protection machines/parts
Issued 21 November 2025 Resolved
Suitable covers, guards, or rails shall be installed in way of all exposed and dangerous places such as gears, machinery, etc. Guard was missing that covers shaft on forward fire pump. Corrected on the spot. 46CFR72.40-20(a)
Action required: 10 - Deficiency Rectified
Resolved 21 November 2025
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 21 November 2025 Resolved
If mechanical ventilation is provided for in a protected space, the ventilation system must automatically shut down prior to discharge of the system to that space. Ventilation Fire Damper 01-24-4 would not close automatically as designed when fixed HALON system was tested in Flammable Supply Storage room. Corrected on the spot. 46CFR95.16-30 (a)
Action required: 10 - Deficiency Rectified
Resolved 21 November 2025
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 17 November 2025 Resolved
Each Class 3 WTD must be designed, constructed, tested and marked in according with ASTM 1196 and ASTM 1197. WTD at Frame 42, had gouge in the sealing edge of the frame, the door movement warning alarm was inop and the door could not be opened using the local hand pump. 46 CFR 170.270(c
Action required: 10 - Deficiency Rectified
Resolved 21 November 2025
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 1 October 2025 No resolution recorded
A survey shall be made every time an accident occurs or a defect is discovered which affects the safety of the vessel or whenever any important repairs are made. The port side Ballast Tank No. 6 has approx. 1/8" diameter through hole damage inboard side in way of the lower bilge. Rectify prior to using the ballast tank. 46 CFR 71.40-1(a)
Action required: 705 - Other - as specified
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 25 September 2025 No resolution recorded
A survey shall be made every time an accident occurs or a defect is discovered which affects the safety of the vessel or whenever any important repairs are made. The plating underneath the fire pump in Service Area #1 is wasted beyond 30% in several areas that is tank top of Ballast Tank #1. Rectify prior to 28FEB2026. 46 CFR 71.40-1(a)
Action required: 705 - Other - as specified
Due 28 February 2026 — due date passed with no resolution recorded
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 20 June 2024 Resolved
An inspection, either general or partial depending upon the circumstances, shall be made whenever any important repairs or alterations are undertaken. Vessel was removing floor tiles in the way of 03-53-0 passageway outside of lavatories and discovered a hole and wasted deck. Submit repair proposal.
Action required: 17 - Rectify deficiencies prior to departure
Due 20 June 2024
Resolved 12 July 2024
Resolution: Temporary repairs completed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 9 May 2024 Resolved
The Attending Marine Inspector is not limited from making tests or inspections as deemed necessary to be assured of the safety of the vessel. The MI requested to see operation of Boiler Safety-Valves. Crew was unable/unwilling to demonstrate operational test of boiler safety-valves. Vessel is not authorized to conduct missions prior to proving operation of safety valves to the Coast Guard.
Action required: 705 - Other - as specified
Due 15 July 2024
Resolved 21 November 2025
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 9 May 2024 Resolved
Doors in stairway enclosures and Main Vertical Zone bulkheads shall be of the self-closing type capable of closing against a 3.5 degree list. Fire door 01-42-1 failed to close completely.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 May 2024
Resolved 16 May 2024
Resolution: ABS witnessed during sea trial
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 9 May 2024 Resolved
The vessel's firefighting equipment is to be at all times ready for use. Portable extinguisher #17's discharge hose is wasted. Replace extinguisher.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 May 2024
Resolved 17 May 2024
Resolution: ABS witnessed during sea trial
01 - Certificates & Documentation › 011 - Ships Certificates › Minimum Safe Manning Document
Issued 9 May 2024 Resolved
The OCMI is responsible for properly prescribing manning on vessels. The machinery inspector noted that the engineering manning level is inadequate based on the age, required maintenance, crew and passenger count, and multiple engine room configuration of the ship. In order to address this issue fill out and return Manning proposal supplement
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 May 2024
Resolved 27 May 2025
Resolution: Verified Sector Mobile increased manning on the amended COI.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 23 May 2023 Resolved
Each passenger vessel of 500GT and over must carry on each side of the vessel at least one rescue boat. Vessel's stbd rescue boat davit is inoperable. Vessel submitted satisfactory repair plan and is permitted to operate with one rescue boat in accordance with MOU between MSC and USCG dated 30 May 2021. Due date is per repair plan submitted to USCG Sector Mobile on 18 May 2023.
Action required: 705 - Other - as specified
Due 30 September 2024
Resolved 27 May 2025
Resolution: Witnessed satisfactory rescue boat davit system test.
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 24 January 2023 Resolved
A survey, shall be made every time an accident occurs or a defect is discovered which affects the safety of the vessel or the efficacy or completeness of its equipment, or whenever any important repairs or renewals are made. UT Shots provided IVO STBD fuel storage tank 6-69-1 showed areas of wastage greater the 25% and a wasted/holed sounding tube pipe that was causing fuel to leak. Plate with wastage greater the 25% & sounding tube should be cropped and renewed
Action required: 17 - Rectify deficiencies prior to departure
Due 24 January 2023
Resolved 5 May 2023
Resolution: Temporary repairs were authorized by ABS & USCG [name withheld] repairs to take place at next dry dock. Repair procedure document was uploaded into this activity.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 9 January 2023 Resolved
Doors shall have a latch with a minimum throw of 3/4" which can be operated from either side of the door. Vessel self-reported the following fire doors FSD61 01-82-1, FSD60 01-80-1, FSD58 01-72-1, FSD52 01-66-1, FSD50 01-63-1, FSD46 01-54-1, FSD43 01-50-1, (not numbered) 01-42-1 & FSD68 1-29-0 have latches that will not secure or broken hardware for the doors that need replaced.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2023
Resolved 21 April 2023
Resolution: Cleared
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 18 October 2022 Resolved
Periodic Safety Test Procedures (PSTPs) for SSDG go against the recommendation of the Manufacturer according to [name withheld] and submit updated PSTPs to MSC for review and approval.
Action required: 705 - Other - as specified
Due 18 December 2022
Resolved 6 January 2023
Resolution: MI witnessed PSTP testing of SSDG as writtened & approved.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 23 September 2022 Resolved
Each passenger vessel must carry a combination of lifeboats and liferafts that have an aggregate capacity sufficient to accommodate the total number of persons on board. Vessel was missing one 25 man life raft. Vessel’s total passenger count is reduced by 25 persons until missing liferaft is replace. 46 CFR 199.201
Action required: 705 - Other - as specified
Resolved 14 October 2022
Resolution: Verified replaced missing liferaft and installed properly.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 23 September 2022 Resolved
Each passenger vessel of 500 tons gross tonnage and over must carry on each side of the vessel at least one rescue boat. Vessel’s stbd side rescue boat davit is inoperable. Vessel may operate as permitted in Sector Mobile issued in letter 22-319. 46 CFR 199.202
Action required: 705 - Other - as specified
Resolved 23 May 2023
Resolution: Received letter requesting extension. Approved, will issue new deficiency with updated verbiage.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 23 September 2022 Resolved
All automatically or remotely controlled or monitored vital systems addressed by part 62 of this subchapter must be subjected to tests and inspections to evaluate the operation and reliability of controls, alarms, safety features, and interlocks. Vessel was not able to demonstrate jacket water temp & low oil pressure (SSDG), low battery voltage(SSDG), high lube oil temp (EDG), high jacket water temp(EDG), Steering Gear Overload, Sitchboard interlocks, high lube oil temp (ADG) & Battery Charger Fail on ADG's). Vessel did not have means to test in presence of MI's during COI. Vessel must demonstrate tests in presence of MI's once they have the proper tools/equipment to do so IAW approved procedures. 46 CFR 61.40-1
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 October 2022
Resolution: Cleared to satisfaction of attending Marine Inspector.
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 23 September 2022 Resolved
In the event of alterations involving the safety of the vessel, the applicable plans shall be submitted for approval covering the proposed work, except as modified by § 71.55-1(b). The general scope of the plans shall be as noted in § 71.65-5. Vessel replaced some of the fire extinguishers onboard since the previous approved/stamped fire/safety plan. Contact cognizant OCMI to update plans to accurately reflect onboard arrangement and amend COI to reflect fire extinguisher weight based to performance based harmonization. 46 CFR 71.65-10
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 14 October 2022
Resolution: Verified changes made to the FCP, stamped and signed.
10 - Safety of Navigation › N/A - No Subsystem › Other (navigation)
Issued 23 September 2022 Resolved
Tests required before entering or getting underway;primary and secondary steering gear; to include the full movement of the rudder to the required capabilities of the steering gear. Vessel unable to achieve left/right 35 degrees. Helm indicates 35 degrees however rudder only achieves 33 degrees. Vessel to provide objective evidence from troubleshooting attesting to satisfactory operation of full steering capabilities prior to departing Norfolk, VA. 33 CFR 164.25(a)(1)(vii)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 October 2022
Resolution: Conducted Satisfactory Steering tests.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 18 November 2021 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Lifeboat 10 stbd long rail and aft top grab rail found wasted. Reduce total persons allowed on board by 115 until repaired or replaced to satisfaction of attending CGMI.46 CFR 199.190(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 18 December 2021
Resolved 18 January 2022
Resolution: Stbd long rail and aft top grab rail were replaced with new stainless steel rails.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 16 November 2021 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Lifeboat 8 stbd long rail and fwd bottom grab rail found wasted. Reduce total persons allowed on board by 230 until repaired or replaced to satisfaction of attending CGMI. 46 CFR 199.190(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 December 2021
Resolution: Replaced wasted railings.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 16 November 2021 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Lifeboat 5 port long rail was found wasted. Repair or replace to satisfaction of attending CGMI. 46 CFR 199.190(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 December 2021
Resolution: Replaced wasted railing.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 16 November 2021 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Found unserviceable litter support systems on lifeboats 3, 4, 5, 7, 8, 9, and 10. Litter support systems are not to be used until repaired, replaced, or removed to satisfaction of CGMI.46 CFR 199.190(a). Will be repaired at next scheduled drydock in March 2022.
Action required: 705 - Other - as specified
Resolved 26 May 2022
Resolution: Litter support systems have been repaired by third party vendor.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 16 November 2021 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. In lifeboat 4, found fiberglass damage to the area surrounding boatplug. Repair fiberglass to satisfaction of attending CGMI.46 CFR 199.190(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 December 2021
Resolution: OEM repaired fiberglass.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 16 November 2021 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. In lifeboat 8, found fiberglass damage in the exterior of the bilge. Repair fiberglass to satisfaction of attending CGMI.46 CFR 199.190(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 December 2021
Resolution: OEM repaired fiberglass.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 16 November 2021 Resolved
All passenger vessels shall have efficient guard rails.Found wasted top rail on O1 deck below lifeboat 10, wasted top rail near Purser's Office at O1-85-1, wasted bottom rail on fantail in port and stbd quarters, wasted bottom rail FR 67 port side and FR 80 on O2 deck in vicinity of lifeboat 8. Repair or replace to satisfaction of attending CGMI. 46 CFR 72.40-5
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 December 2021
Resolution: Replaced wasted railings.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 16 November 2021 Resolved
The inspection shall ensure structure, piping, and other equipment is in satisfactory condition and fit for the service for which it is intended. The exhaust pipes above O2N2 station on stbd side, labeled #5 and #1 were found unserviceable. Repair or replace to satisfaction of attending CGMI.46 CFR 91.25-10. 18Jan22 This has been added to the vessels drydock repair plan for the upcoming drydock scheduled for 18Jan22.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 1 July 2022
Resolution: Attended and visually inspected replaced exhaust piping
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 16 November 2021 Resolved
The inspection shall ensure structure, piping, and other equipment is in satisfactory condition and fit for the service for which it is intended. Bottom support for drain pipe found wasted on O2 deck, port side, in vicinity of Frame 65 and rescue boat. Repair or replace to satisfaction of attending CGMI.46 CFR 91.25-10
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 December 2021
Resolution: Replaced wasted drain pipe support.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 November 2021 Resolved
When more than 12 nm from the nearest land, any discharge of oil or oily mixtures into the sea from a ship is prohibited except when the ship has in operation oily water separating equipment as required by part 46 CFR 155 subpart B. The vessel’s oily water separating equipment is inoperative.33 CFR 151.10(a)(6)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 December 2021
Resolved 22 February 2022
Resolution: Witnessed operation of the oily water separating equipment and 15 ppm OCM. Verified calibration of OCM by certificate.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 November 2021 Resolved
The spring in a relief valve in service for up to and including 250 psi shall not be reset for any pressure more than 10 percent above or 10 percent below that for which the relief valve is marked. The SSDG air receiver Nos. 1 and 2’s relief valves setting are marked 145 and 150 psi respectively and have been adjusted down to 110 psi.46 CFR 54.15-10(g)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 December 2021
Resolved 18 January 2022
Resolution: Valves were replaced with new valves tested and verified to operate at 145psi.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 November 2021 Resolved
Cylinders containing hazardous ships’ stores that are compressed gases must be filled, marked and inspected in accordance with 49 CFR 173.301 through 173.308. Engine room oxygen compressed gas cylinder is out of its hydro-static test date. Remove cylinder from vessel or hydro-statically test IAW 49 CFR 173.46 CFR 147.60(a)(3)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 3 December 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 November 2021 Resolved
Cylinders containing hazardous ships’ stores that are compressed gases must be filled, marked and inspected in accordance with 49 CFR 173.301 through 173.308. Disposable compressed gas cylinders containing refrigerant were found in the A/C flat. Remove disposable compressed gas cylinders from vessel.46 CFR 147.60(a)(3)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 December 2021
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 16 November 2021 Resolved
Each hand portable fire extinguisher shall be marked with a corresponding number. Machinery space fire extinguishers and locations are numbered incorrectly.46 CFR 78.47-30(a)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 December 2021
08 - Alarms › N/A - No Subsystem › General alarm
Issued 16 November 2021 Resolved
All general alarm bells shall be identified by red lettering at least ½ inch high: “GENERAL ALARM-WHEN BELL RINGS GO TO YOUR STATION”. The general alarm beacon at the pump room IWO watertight door has no placard. 46 CFR 78.47-7(a)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 December 2021
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 15 April 2021 Resolved
Port rescue boat is inoperable. Tests and inspections shall be carried out to demonstrate the proper condition and operation of rescue boats. Provide proof of proper operation to attending USCG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 29 April 2021
Resolution: Port rescue boat is operating as required to satisfaction of OCMI.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 18 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Both lifeboat Nos. 6 and 9 are out of service for repairs. Passenger count reduced by 115 until lifeoboat repairs have been effected and both are back in service.
Action required: 705 - Other - as specified
Resolved 1 April 2021
Resolution: Witnessed 1.1 test of the #6 Lifeboat and #9 Lifeboat handrails were satisfactorily repaired.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 4 December 2020 Resolved
Doors in stairway enclosures & double swing doors shall be of the self closing type. FSD Nos. 78, 97, 98, & 109 and FSD Fr. 42 don't latch close.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 December 2020
Resolved 22 July 2021
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Lifeboat Nos. 1 and 2 had electric submersible bilge pumps that were broken off their mounts and with one broken discharge line.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: Electric submersible bilge pumps replaced in kind and mounted.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Fantail ring life buoy found with water inside the body of the buoy.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: Ring life buoy replaced in kind.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Numerous ring life buoy water lights were found with batteries the water lights were not approved to use.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: All waterlights had been replaced with new CG-approved ACR waterlights with correct batteries.
11 - Life Saving Appliances › N/A - No Subsystem › Thermal Protective Aids
Issued 4 December 2020 Resolved
Each life boat must carry the equipment specified for it in Table 199.175. Several thermal protective aids in inventory for the lifeboats were deteriorated.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 December 2020
Resolved 21 January 2021
Resolution: Coast Guard approved TPAs were provided for all lifeboats and rescue boats.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Lifeboat Nos. 6 and 9 had wasted and broken grab rails on the hull of the boat. Repair to the satisfaction of OEM and OCMI.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 December 2020
Resolution: Lifeboat Nos. 6 and 9 are out of service. Amended deficiency to reduce passenger count by 115 untile repairs have been effected and lifeboats are back in service.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Lifeboat No. 9's winch has a wasted mount for the weight on the dead man brake. Repair to the satisfaction of OEM and OCMI.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 December 2020
Resolution: Lifeboat Nos. 6 and 9 are out of service. Amended deficiency to reduce passenger count by 115 untile repairs have been effected and lifeboats are back in service.
11 - Life Saving Appliances › N/A - No Subsystem › Embarkation arrangement survival craft
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Deck attachments for survival craft embarkation ladders use stainless steel shackles attaching the ladders to the vessel. Provide OEM certification this arrangement is suitable for use in this service.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 December 2020
Resolution: OEM approved shackles were installed at all embarkation ladders.
11 - Life Saving Appliances › N/A - No Subsystem › Embarkation arrangement survival craft
Issued 4 December 2020 Resolved
Each muster station and embarkation station must be adequately illuminated by lighting. Numerous lights at port and starboard embarkation stations were not illuminated.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: All embarkation and muster lighting is operational.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 4 December 2020 Resolved
The annual inspection shall include an examination of the structure to ensure it is satisfactory and fit for the service for which it is intended. Found two wasted kick pipes iwo liferaft Nos. 7 and 9. Found one wasted ship's service air line iwo of 01 level at stern house starboard side. Fantail natural ventilation closure for aft steering gasket is wasted. Starboard DFM shore fill connection at fantail has small discharge containment that is wasted. Fantail distilled water TLI MCT firestop found improperly maintained.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 February 2021
Resolved 21 January 2021
Resolution: Small discharge containment for stbd DFM shore tie was replaced and wasted air line was cropped and renewed.
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 4 December 2020 Resolved
In all ventilation systems, manually operated dampers shall be provided in accessible locations outside the space served to shut off the passage of air in the event of fire. Found ventilation dampers Nos. 01-64-9 and 2-43-5 frozen and inoperable.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: Witnessed proper operation of ventilation dampers.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 4 December 2020 Resolved
Each panel board must have the rating of setting of the overcurrent protection device for each circuit. The main machinery space main panel board has a breaker labeled for 30amps that has a 40amp breaker, and a breaker labeled for 40a that has a 30a breaker. Confirm with drawings the correct breaker amperage and make repair to the satisfaction of attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 December 2020
Resolution: Verified breakers on the machinery space main panel board were labelled correctly.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 4 December 2020 Resolved
A relief valve shall not be reset for any pressure more than 10% above or below that which the relief valve is marked. Relief valves for pressure vessels 1,2 and 3 in main machinery space have data-plates stamped at 145psi, but are readjusted as indicated by a hanging tag at 110, 125 and 110psi respectively. Repair or replace to the satisfaction of attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 29 December 2020
Resolution: Inspected valves and setting (new) prior to installation. Vessel provided pictures of valves installed on 12/29/2020. Def cleared.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 4 December 2020 Resolved
Dampers shall be designed to close. The supply vent damper in the Aux Generator space was not closing properly. Repair to the satisfaction of attending Marine Inspector.
Action required: 10 - Deficiency Rectified
Resolved 4 December 2020
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 4 December 2020 Resolved
The annual inspection shall include an examination of fire detecting equipment to ensure it is satisfactory and fit for the service for which it is intended. Call box in Fire Zone 38 for service area number 2 was inoperable.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: Witnessed proper operation of call box in fire zone 38.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boat inventory
Issued 4 December 2020 Resolved
Each passenger vessel of 500 gross tonnage and over must carry on each side of the vessel at least one rescue boat that is equipped as specified in table 46 CFR 199.175. The starboard rescue boat's inventory in not complete.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 December 2020
Resolution: Starboard rescue boat inventory inspected complete.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Port and starboard smoke signal jerk lines were not the length specified by manufacturer.
Action required: 10 - Deficiency Rectified
Resolved 4 December 2020
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 4 December 2020 Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Starboard side liferaft's weak link not attached.
Action required: 10 - Deficiency Rectified
Resolved 4 December 2020
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboat inventory
Issued 4 December 2020 Resolved
Each life boat must carry the equipment specified for it in Table 199.175. Several provisions had lost their vacuum seal.
Action required: 10 - Deficiency Rectified
Resolved 4 December 2020
08 - Alarms › N/A - No Subsystem › General alarm
Issued 4 December 2020 Resolved
Each general alarm contact maker must be marked "GENERAL ALARM" in red letters on a corrosion resistant plate or on a sign. The wheelhouse general alarm markings were missing.
Action required: 10 - Deficiency Rectified
Resolved 4 December 2020
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 2 December 2020 Resolved
Each fire hydrant must have at least one length of fire hose, a spanner, and a hose rack or other device for stowing the hose. Fire station number 13 was missing a spanner wrench.
Action required: 10 - Deficiency Rectified
Resolved 4 December 2020
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 7 October 2020 Resolved
Manually operated dampers or other suitable means shall be provided in accessible locations for shutting off air in the event of a fire. Damper in O2N2 compressor room exhaust was not functioning. Make permanent repairs prior to operation of the O2N2 compressors. 46 CFR 72.05-50(i)
Action required: 705 - Other - as specified
Resolved 30 October 2020
Resolution: Repaired.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 20 March 2020 Resolved
Provide repair proposal for crack in anti roll tank port side approximately 5 feet above the water line to the satis faction of the OCMI. 46CFR 72.01-15
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Due 20 March 2020
Resolved 23 March 2020
Resolution: Temporary repairs made to the satisfaction of [name withheld] Note.
11 - Life Saving Appliances › N/A - No Subsystem › Line-throwing appliance
Issued 10 March 2020 Resolved
Vessel missing 4 rockets and 1 shot of line 46 CFR 199.170a
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Rockets on board
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 10 March 2020 Resolved
Vessel missing auxilary line for line throwing gun 46 CFR 199.170c.2
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 April 2020
Resolved 1 April 2020
Resolution: Vessel aux line on order OCMI validated reciept
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 10 March 2020 Resolved
Davit #14 has inoperable brake, reducing passenger count by 25 persons 46 CFR 199.45b2
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Proved operation of brake
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 10 March 2020 Resolved
Port side tender unable to start without jump starting the battery. 46 CFR 199.45b2
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 13 April 2020
Resolved 12 March 2020
Resolution: Corrected the next day.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 10 March 2020 Resolved
Lifeboat #4 accumulator inoperable, reducing passenger count by 115. 46 CFR 199.45b2
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 April 2020
Resolved 20 March 2020
Resolution: Repaired accumulator
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 10 March 2020 Resolved
Lifeboat # 8 sheered pin on shaft that prevented the propeller to clutch into reverse. 46 CFR 199.45b2
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 13 April 2020
Resolved 11 March 2020
Resolution: Replaced pin immediately and lifeboat operated properly
02 - Structural Conditions › N/A - No Subsystem › Closing devices/watertight doors
Issued 10 March 2020 Resolved
At annual inspection the inspector shall conduct inspection on hull equipment. Found goose neck at port bow closure frozen; found JP5 containment on starboard side 01 deck, missing mechanical plug; found 01 goose neck on 01 deck at frame 42 missing pin. 46 CFR 71.25-25
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 25 March 2020
Resolution: corrected to the satisfaction of CG
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 10 March 2020 Resolved
Demonstrate and prove proper operation of the following equipment for your annual COI Inspection; Boiler Safeties ADG #2 and #3 PSTP's EDG PSTP's STG PSTP's Steam fire pump SSDG PSTP's Engineroom exhaust emergency stops and closures Sewage system AMR Halon Testing 46 CFR 91.25-10
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 12 March 2020
Resolved 25 March 2020
Resolution: Witnessed SAT test of equipment
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 10 March 2020 Resolved
Port incinerator foam supply head in need of replacement, Repair or replace to the satisfaction of the CGMI. 46 CFR 76.17-20
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 12 April 2020
Resolved 20 March 2020
Resolution: Foam head was replaced.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
Soft patch on pumproom ballast piping, make permanent repairs to the satisfaction of CGMI 46 CFR 96.03-1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 12 April 2020
Resolved 20 March 2020
Resolution: Permanent repairs were made to piping
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
Soft patch on pipe, 2nd deck engineroom @ frame 119, make permanent repairs to the satisfaction of CGMI. 46 CFR 96.03-1
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Permanent repairs were made to piping
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
Soft patch on #1 ASW pump piping, Make permanent repairs to the satisfaction of the CGMI.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 12 April 2020
Resolved 20 March 2020
Resolution: Permanent repairs were made to piping
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
Soft patch on #1 ASW pump piping, Make permanent repairs to the satisfaction of the CGMI. 46 CFR 96.03-1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 12 April 2020
Resolved 20 March 2020
Resolution: Permanent repairs were made to piping
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
Submit repair proposal for unauthorized repair to #2 ASW pump piping, the gauge insert has been moved down and the main pipe was repaired by clad welding.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Permanent repairs were made to piping
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
Install missing bolt on the steam return valve in the lower engineroom.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 26 March 2020
Resolved 20 March 2020
Resolution: Bolt was replaced
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 March 2020 Resolved
replaced and prove proper operation of the missing firemain valve handle in the engineroom machine shop. 46 CFR 95.10-15
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Valve handle was replaced and demonstrated to MI
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 10 March 2020 Resolved
The #1 firepump motor junction box cover is cracked, repair or replace to the satisfaction of the CGMI. 46 CFR 111.05-3
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Junction box cover was replaced
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 10 March 2020 Resolved
Port and stbd incinerator Exhaust flanges are missing insulation, Repair or replace to the satisfaction of the CGMI. 46 CFR 56.50-1 (k)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: exhaust lagging was replaced to the satisfaction of MI
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 10 March 2020 Resolved
Dead end wiring found in the engineroom above the head, remove or place in an enclosure to the satisfaction of the CGMI. 46 CFR 111.60-11
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 March 2020
Resolved 20 March 2020
Resolution: Dead end wires were verified to be dead, and properly terminated.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 10 March 2020 Resolved
Dead end wiring found iwo the engineroom portside ladder, remove or place in an enclosure to the satisfaction of the CGMI. 46 CFR 111.60-11
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Dead end wires were verified to be dead, and properly terminated.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 10 March 2020 Resolved
AMR miscellaneous alarm panel missing multiple knockouts, Repair to the satisfaction of the CGMI. 46 CFR 111.60-11
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 April 2020
Resolved 25 March 2020
Resolution: Knockout blank installed
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 10 March 2020 Resolved
Dead end wiring found in the engineroom machine shop, remove or place in an enclosure to the satisfaction of the CGMI. 46 CFR 111.60-11
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 20 March 2020
Resolution: Dead end wires were verified to be dead, and properly terminated.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 March 2020 Resolved
Temperatures exceeding 150'F shall be suitably insulated. The engineroom steam piping is missing lagging / insulation, Repair to the satisfaction of the CGMI. 46 CFR 56.50-1 (k)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 25 March 2020
Resolution: Vessel crew installed lagging
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 10 March 2020 Resolved
Make the following Marine Cable Transits (MCT's) Watertight and or fire-tight as appropriate; (MCT) above fire station 95 @ 2-44-1 (MCT) above fire station 127 @ 01-43-1 (MCT) in way of (IWO) frame 42 water tight door (MCT) @ WTBHD 84, AMR to Lower AMR (MCT) missing rox block in pump room (MCT) Engine room elevator shaft (MCT) Port side bridge IWO fire and smoke detection system. 46 CFR 92.07-10
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 April 2020
Resolved 25 March 2020
Resolution: All MCT's listed were corrected by crew
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 9 June 2019 Resolved
The propulsion steam plant's blowdown pipe which penetrates the hull below the waterline on the aft stbd side of the machinery space has a pin hole between the skin and the stop valve, as well as between the boiler isolation valve and the stop valve. Make repairs to the satisfaction of the USCG and Load Line issuing authority prior to departure.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 14 June 2019
Resolved 13 June 2019
Resolution: Operational test conducted of new piping.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 10 September 2018 Resolved
Demonstrate the launching, operation, and recovery of the four starboard open lifeboats to the satisfaction of the attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 October 2018
Resolved 24 September 2018
Resolution: Attending CG Marine Inspectors witnessed launching, operation, and recovery of the four starboard side open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #3, #4, #5, #6, #7, #8, #9, and #10 lifeboat tailshaft through hull penetration sealing system non-metallic hoses are no longer serviceable. Replace the non-metallic hoses with OEM specified or equivalent non-metallic hoses, and prove the proper operation of all four open lifeboats to the satisfaction of the attending Marine Inspector. The total persons allowed is reduced by 920 until the requirement is cleared.
Action required: 705 - Other - as specified
Resolved 10 September 2018
Resolution: Received a service report from an authorized OEM techinician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors witnessed an operational test of the four portside open lifeboats; all sat
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 25 July 2018 Resolved
The #8 lifeboat davit forward arm outboard sheave and the #6 lifeboat davit aft arm inboard outermost sheave are corroded. De-scale the sheaves, provide a gauging report and the davit manufacturers maximum wastage allowance to the satisfaction of the attending Marine Inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 January 2019
Resolved 22 May 2019
Resolution: All identified wasted sheaves have been replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #4, #6, and #9 lifeboats fiberglass is delaminating in differect locations in the fwd area of the interior hull. Repair the forward outboard bilge steps using OEM specified repair procedures to the satisfaction of the attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 25 August 2018
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #5 lifeboat's forward releasing gear keel plate's fiberglass is delaminating. Repair the fiberglass using OEM specified repair procedures to the satisfaction of the attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 25 August 2018
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #4, #5, #6, #7, #8 and #9 lifeboats hull grab rails are corroded in various locations. Repair or replace the corroded grab rails to the satisfaction of the attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 25 August 2018
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #9 lifeboat is missing its data plate. Replace teh data plate to the satisfaction of the attending Marine Inspector. 46 CFR 160.135-17
Action required: 50 - Rectify deficiencies w/in 30 days
Due 25 August 2018
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #3 lifeboat exhaust manifold riser has been repaired using a synthoglass type material. Provide documentation from the lifeboat OEM that the repair is authorized, repair the exhaust manifold riser assmebly in accordance with OEM repair procedures, or replace the exhaust manifold riser with OEM approved parts. Once repairs are complete prove the proper operation of the #3 lifeboat engine to the satisfaction of the attending Marine Inspector. The total persons allowed is reduced by 115 until the requirement is cleared.
Action required: 705 - Other - as specified
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #9 lifeboat forward releasing gear keel plate's fiberglass is delaminating and the plate is corroding. De-scale the plate, provide a gauging report and the lifeboat's OEM maximum wastage allowance, and repair the fiberglass using OEM specified repair procedures to the satisfaction of the attending Marine Inspector. The total persons allowed is reduced by 115 unitl the requirement is cleared.
Action required: 705 - Other - as specified
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 25 July 2018 Resolved
The #5 lifeboat fuel tank fill cap assembly is attached using an epoxy life substance. Provide documentation from the lifeboat OEM that the repair is authorized, repair the fuel tank fill cap assembly is accordance with OEM repair procedures, or replace the fuel tank full cap assembly with OEM approved parts to the satisfaction of the attending Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 25 August 2018
Resolved 10 September 2018
Resolution: Received a service report from an OEM service technician attesting to the proper operation of all open lifeboats and the attending Marine Inspectors conducted a material inspection of all open lifeboats; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 16 July 2018 Resolved
The #6 lifeboat radiator cap assembly has been repaired with an epoxy like substance. Provide documentation for the lifeboat OEM that the repair is authorized, repair the radiator cap assembly in accordance with OEM repair procedures, or replace the radiator with OEM approved parts. Once repairs are complete prove the proper operation of the #6 lifeboat engine to the satisfaction of the attending Marine Inspector. The total persons allowed is reduced by 115 until the requirement is cleared.
Action required: 705 - Other - as specified
Resolved 25 July 2018
Resolution: Verifed that the radiator had been replaced and witness the operation of the lifeboat in the water; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 16 July 2018 Resolved
The #8 lifeboat engine's salt water cooling system is not circulating water. Repair the salt water cooling system and prove the engine's proper operation including proper salt water circulation to the satisfaction of the attending Marine Inspector. The total persons allowed is reduced by 115 until the requirement is cleared.
Action required: 705 - Other - as specified
Resolved 25 July 2018
Resolution: Witnessed the operation of the lifeboats salt water cooling system; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 16 July 2018 Resolved
The #6 lifeboat releasing gear is not functioning properly. Repair the releasing gear and prove its proper operation to the satisfaction of the attending Marine Inspector. The total persons allowed is reduced by 115 until the requirement is cleared.
Action required: 705 - Other - as specified
Resolved 25 July 2018
Resolution: Witnessed the operation of the releasing gear and launching of the lifeboat; all sat.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 5 July 2018 Resolved
Cable and pipe penetrations in fire bulkheads and decks must maintain the proper classification as approved by Coast guard. Materials must meet CG approval as tested to IMO Res. A.754(18)and be installed to product manufacturer's instruction. Multiple A Class bulkheads have been penetrated with newly installed improper length penetrations. Make repairs to the satisfaction of CG Marine Inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 10 September 2018
Resolution: Verified all cable penetration seals were installed and tested in accordance with the manufacturers specifications; all sat.
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System › Piping
Issued 18 January 2018 Resolved
Vessel's water mist system's 1" piping was replaced with 1.25" piping. Provide Coast Guard Head Quarters approved plans of the modified water mist system to the local OCMI and demonstrate system operation to the satisfaction of the attending Coast Guard Marine Inspector.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 16 February 2018
Resolved 24 January 2018
Resolution: Vessel provided USCG Marine Safety Center Approval Letter for Drawing No. 8495253 Rev B that captured the pipe diameter increase; all sat.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 1 December 2017 Resolved
EDG fire damper did not close, repair and demonstrate satisfactory operation of EDG fixed firefighting systems in the presence of a CG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 9 February 2018
Resolution: Witnessed operational test of EDG fire damper; all sat
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 1 December 2017 Resolved
AMR fire damper did not close, repair and demonstrate satisfactory operation of AMR fixed firefighting systems in the presence of a CG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 15 December 2017
Resolution: Witnessed the operation of the fire damper.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 1 December 2017 Resolved
AMR 68 second time delay opened at 64 seconds, replace time delay and demonstrate satisfactory operation of AMR fixed firefighting systems in the presence of a CG Marine Inspector.
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 22 December 2017
Resolution: Witnessed operation of AMR time delay with Hiller Systems. Time delay actuated at 68 seconds as designed.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 1 December 2017 Resolved
AMR Engine Control Room ventilation did not shut down. Determine if ventilation is required to shutdown and demonstrate satisfactory operation of AMR fixed firefighting systems in the presence of a CG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 15 December 2017
Resolution: Witnessed the operation of the ventilation shutdown.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 1 December 2017 Resolved
O2N2 Producer Room 30 second time delay opened at 27 seconds, replace time delay and demonstrate satisfactory operation of O2N2 Producer Room fixed firefighting systems in the presence of a CG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 15 December 2017
Resolution: Witnessed the operation of the fixed fire extinguishing system; all sat.
Fire Fighting › Fixed Fire Detection System › Annual Inspection
Issued 1 December 2017 Resolved
Annual inspection of fire detection system and portable extinguishers incomplete. Schedule fire detection testing for CG attendance and provide servicing certificates.
Condition: Invalid
Action required: 705 - Other - as specified
Due 28 March 2018
Resolved 30 March 2018
Resolution: Vessel provided annual servicing report from Hiller Systems of portables extinguisers and the fire detection system. Coast Guard attended portions of the fire detection system testing.
Lifesaving › Launching Appliances › Winch
Issued 1 December 2017 Resolved
Lifeboat winch control switches for lifeboats 3, 5, 6, 8, & 10 are not of the spring type. Replace winch control switches with a spring type switch.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 January 2018
Resolved 15 December 2017
Resolution: Witnessed the operation of life boat winches 3, 5, 6, 8, and 10's spring loaded control swtiches; all sat.
Lifesaving › Launching Appliances › Falls
Issued 1 December 2017 Resolved
Stbd tender 1 wire falls come in contact with hydraulic hoses when falls are not under tension. Install permanent chaffing gear to protect hydraulic hoses from the wire falls.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 15 December 2017
Resolved 24 January 2018
Resolution: Inspected installation of metal plate zip tied onto hydraulic hose to prevent chaffing from the falls; all sat.
Communications › Public Address System › Loudspeaker
Issued 1 December 2017 Resolved
1MC inoperable from numerous locations throughout the ship. Identify and repair all inoperable 1MC speakers, submit report to USCG.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 28 March 2018
Resolved 30 March 2018
Resolution: Vessel provided ship's force report for all 481 1MC speakers 23 of which were inoperable and repaired.
Documentation › Manuals/Policy Documentation › Vessel Specific Watch Policy/Procedures
Issued 1 December 2017 Resolved
Vessel's CG approved Periodic Safety Test Procedures (PSTP) have been updated. Submit updated PSTP’s to CG Marine Safety Center for approval.
Condition: Invalid
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 27 March 2020
Resolution: Witnessed Approved PSTP's; all sat.
Engineering › Steam Turbine (propulsion) › Valve, Regulating
Issued 1 December 2017 Resolved
Vessel's stbd boiler #2 burner assembly fuel valve does not operate properly(sticking). Repair or replace to the satisfaction of CG Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 9 February 2018
Resolution: Witnessed operational test of vessel's stbd boiler #2 burner assembly fuel valves; all sat.
Electrical › Electric Generation Source (service) › Power Requirement
Issued 1 December 2017 Resolved
Vessel's #1, #2,& #3 ADG reverse power relays inoperable. Demonstrate operation of reverse power relays to the satisfaction of CG MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 9 February 2018
Resolution: Witness satisfactory test of vessel's reverse power relays; all sat.
Operations/Management › Vessel Safety Management › Company Responsibilities/Authority
Issued 1 December 2017 Resolved
Vessel currently has 03 CG 835's with a 03 DEC 2017 due date. Provide a written 835 extension request to include a detailed plan and time-line to USCG.
Condition: Invalid
Action required: 705 - Other - as specified
Due 28 March 2018
Resolved 9 February 2018
Resolution: Vessel demonstrated operation of the entire water mist system and provided documentation of Marine Safety Center approval of water mist modifications.
Fire Fighting › Structural - A Class Divisions › Machinery Spaces
Issued 1 December 2017 Resolved
Open penetration in O2 space fire boundary bulkhead and ventilation pull cable. Fill open penetrations to equivalent fire rating of the existing bulkhead to the satisfaction of CGMI.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 15 December 2017
Resolved 9 February 2018
Resolution: Inspected open penetration (corrected with threaded/capped pipe welded to bulkhead) and ventilation pull cable penetration (filled with fire stop); all sat.
Lifesaving › Launching Appliances › Winch
Issued 1 December 2017 Resolved
Port and Stbd tender hydraulic gauges inoperable. Repair or replace gauges to the satisfcation of CGMI.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 9 February 2018
Resolution: Inspected installation of new pressure gauges; all sat.
Lifesaving › Embarkation Appliances/Stations › Accessability
Issued 1 December 2017 Resolved
#2 tender launching instructions are not posted. Post instructions to the satisfaction of CGMI.
Condition: Invalid
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 3 May 2018
Engineering › Steam Boiler (propulsion) › Superheater Protection System
Issued 1 December 2017 Resolved
Vessel's port super heater safety valve is leaking. Identify and repair leak to the satisfaction of CG MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 9 February 2018
Resolution: Vessel identified port boiler economizer was leaking. Replaced economizer and hydrostatically tested port super heater safety valve to 500psi to prove it was not leaking; all sat.
Engineering › Steam Boiler (auxiliary/waste heat) › Piping
Issued 1 December 2017 Resolved
Vessel's auxiliary steam line to the reducing station is leaking in the lower engine room, adjacent to the water tight door. Identify and repair leak to the satisfaction of CGMI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 January 2018
Resolved 15 December 2017
Resolution: Verfied a new gasket was installed; all sat.
Engineering › Diesel Engine (propulsion/auxiliary-electric) › Exhaust Manifold
Issued 1 December 2017 Resolved
ADG #2 & #3 exhaust piping is exposed and lagging is deteriorated. Replace lagging to the satisfaction of CG MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 20 January 2018
Resolved 9 February 2018
Resolution: Inspected lagging; all sat.
Electrical › Electric Generation Source (service) › Power Requirement
Issued 1 December 2017 Resolved
SSDG low system voltage warning alarm does not activate at engine monitoring display. Demonstrate operation to the satisfaction of CG MI
Condition: Invalid
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 22 May 2019
Resolution: This was written in error, SSDG has air starting and revers power relay with parallel.
Engineering › Bilge Water Management System › Pump
Issued 27 November 2017 Resolved
Ballast pump mechanical seal is leaking. Replace seal to satisfaction of CG MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 22 May 2019
Resolution: Replaced seal
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System › Piping
Issued 14 June 2017 Resolved
Issued 835 to submit plans to MSC for approval for re-programing of water mist system circuit PLC, demonstrate spray pattern test of zones 10 and 11 and proper designed operation to Coast Guard Marine Inspector.
Action required: 705 - Other - as specified
Due 3 December 2017
Resolved 9 February 2018
Resolution: Vessel provided MSC approved plans and demonstrated operation of the entire watermist system to USCG and ABS.
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System › Piping
Issued 14 June 2017 Resolved
Issued 835 to conduct spray pattern test of water mist system zone 1 SSDG to Coast Guard Marine Inspector.
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 3 December 2017
Resolved 9 February 2018
Resolution: Witnessed spray pattern test of water mist system zone 1 SSDG; all sat.
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System › Piping
Issued 14 June 2017 Resolved
Issued 835 to conduct flow test of water mist system zones 4, 5, 6 (=/+ 750 psi) and spray pattern test to Coast Guard Marine Inspector.
Action required: 705 - Other - as specified
Due 3 December 2017
Resolved 9 February 2018
Resolution: Witnessed satisfactory test of water mist system zones 4, 5, and 6 at greater than 750 psi.
Fire Fighting › Combustible Materials › Paints/Varnishes/Other Finishes
Issued 14 June 2017 Resolved
Issued 835 to remove from ship or properly store in designated paint lockers pallets of paint temporarily stored in helo hanger.
Action required: 705 - Other - as specified
Due 3 December 2017
Resolved 27 September 2017
Resolution: Paint pallets were removed from the helo hangar and relocated in paint lockers.
Engineering › Steam Turbine (propulsion) › Casing
Issued 8 March 2017 Resolved
L.P. has damage to out casing. Make repairs to the satisfaction of the attending CG Marine Inspector. Vessel is permited to proceed directly to scheduled shipyard in Boston MA. under her own power.
Condition: Damaged By Earlier Event
Due 8 June 2017
Resolved 14 June 2017
Resolution: VSL LP turbine casing was inspected NDT, GE report on condition RCV, sentinal valve overhauled.
Engineering › Feedwater/Condensate Water System › Pump
Issued 1 March 2017 Resolved
Vessel's #1 condensate pump motor for the main condenser is inoperable. Two means shall be provided for discharging condensate from the main condenser. Make repairs to the motor iaw manufacturer's specifications or renew as original, to the satisfaction of the [name withheld] operational testing of the pump/motor to the satisfaction of the attending CG MI.
Condition: Invalid
Action required: 705 - Other - as specified
Resolved 8 March 2017
Engineering › Steam Turbine (propulsion) › Casing
Issued 1 March 2017 Resolved
Vessel's low pressure turbine casing was damaged during maintenance. Conduct NDT on casing and provide report to attending CGMI. Provide turbine technician's survey report to attending CGMI prior to operating turbine.
Action required: 705 - Other - as specified
Due 3 March 2017
Resolved 8 March 2017
Fire Fighting › Fire Main › Material
Issued 17 November 2016 Resolved
MI found temp repair of FM piping to fire station #51. Repair of piping system done under cognizance of OCMI. C/R damaged pipe to original, conduct final weld test to 1.5x MAWP in presence of CG MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 17 December 2016
Resolved 16 December 2016
Resolution: The holed fire line outside the mess deck was found repair by inserting an approx.16 in. section of pipe with welded in couplings on each end. Pipe was examined under full fire line pressure and was found with no leaks.
Pollution Prevention/Response › Prevention Equipment › Sewage System Piping
Issued 17 November 2016 Resolved
MI found temp repair of sewage piping: Zone 2, below down pipe. Zone 5, 4" Raw sewage X-FER sewage side, 4" Drain to sewage tank. Repair of piping system done under cognizance of OCMI. C/R damaged pipe to original, conduct final weld test to MAWP to the satisfaction of the attending CG MI prior to next Drydocking or 30 May 2017, whichever is sooner.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 May 2017
Resolved 14 June 2017
Resolution: Sewage piping in Zone 2 and Zone 5 were replaced during D/D 2017, witnesed weld inspections and hydro's prior to placing into service.
Fire Fighting › Fire Pumps › Arrangement
Issued 17 November 2016 Resolved
MI found #1 F/P OOC. Repair of piping system done under cognizance of OCMI. C/R damaged pipe to original, conduct opp test in presence of CG MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 17 December 2016
Resolved 16 December 2016
Resolution: Examination of the No. 1 Pump under operating conditions was found satisfactory, no leaks, bearing temperature within normal range, good pump discharge pressure. ABS will be crediting the pump to the vessel's status.
Lifesaving › Lifeboat › Propulsion Engine
Issued 17 November 2016 Resolved
The stbd engine for the port-side enclosed lifeboat (tender vessel) has been rebuilt. Lifeboat must be maneuvered in the water with the newly renewed engine to the satisfaction of the attending CG MI, prior to the completion of next drydock or 30 May 2017, whichever is sooner.
Action required: 705 - Other - as specified
Due 30 May 2017
Resolved 8 March 2017
Electrical › Electric Supply System (service) › Transformer
Issued 20 April 2016 Resolved
New refrigeration units were installed in main galley which required modification to the vessel's electrical system, two 440v to 220v transformers installed. Submit installation plans and gain approval from Marine Safety Center.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 April 2017
Resolved 14 June 2017
Resolution: Plans approved for refridgeration system and verified.
Engineering › Fuel Oil Storage/Transfer System › Tank
Issued 20 April 2016 Resolved
DFM fuel tank 6-87-1 has small fuel leak caused by weld defects. Make repairs, using CG or ABS certified welders, prior placing the fuel tank into service and to the satisfaction of the attending CG Marine Inspector. Permanently repair by next dry-dock
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 April 2017
Resolved 14 June 2017
Resolution: DFM fuel TK 6-87-1 was repaired during D/D 2017, 2PSI hydro conducted SAT.
Construction/Loadline › Structures › Deck Plating
Issued 15 March 2016 Resolved
Vessel has excessive wastage on the ballast tank top steel plating located on the tank top of service space #6. Vessel must provide additional UT shots in way of the piping located on the tank top and then crop and renew areas determined to be excessively wasted to the satisfaction of an attending Coast Guard Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 15 April 2016
Resolution: Recieved new ultrasonic testing report of service area #6; cleared 835. Informed port engineer after reviewing the new report, the Coast Guard is not requiring any steel repair in service area 6 at this time.
Electrical › Electric Generation Source (emergency) › Generator
Issued 24 February 2016 Resolved
The Emergency Diesel Generator was found to be inoperable. Make the EDG ready to demonstrate the safety shutdowns and alarms, including the automatic start. Vessel is required to have an appropriate tug escort during transit from Naval Station Norfolk to MHI.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 25 April 2016
Resolution: Witnessed satisfactory operation and testing of the EDG following repairs.
Engineering › Steam Boiler (propulsion) › Desuperheater
Issued 24 February 2016 Resolved
Found the Control Desuperheater Valve on the port boiler to be leaking. Repair or replace the valve.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 19 April 2016
Electrical › Electric Generation Source (service) › Generator
Issued 24 February 2016 Resolved
Found leaking non-metallic cooling water line on the ship's service diesel generator. Replace in kind.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 19 April 2016
Engineering › Diesel Engine (auxiliary) › Turbocharger
Issued 24 February 2016 Resolved
Found a lube oil leak on the Turbocharger Lube Oil piping of the #1 Auxiliary Diesel Generator. Repair or replace the flange.
Condition: Improper/Lack of Maintenance
Due 25 March 2016
Resolved 22 April 2016
Engineering › Fuel Oil Storage/Transfer System › Tank
Issued 24 February 2016 Resolved
Found fuel oil leak on the Starboard DFM Storage Tank, 6-87-1. Determine the source of the leak and provide a repair proposal.
Condition: Design Flaw
Action required: 703 - Prior to bunkering operations
Resolved 19 April 2016
Stability › Watertight Integrity › General
Issued 24 February 2016 Resolved
Found Watertight Door #2 operation to be excessively slow. Repair necessary components and demonstrate operation to the attending marine inspector.
Condition: Improper/Lack of Maintenance
Due 25 March 2016
Resolved 25 April 2016
Resolution: Witnessed satifactory operation of the watertight door following corrective maintenance.
Engineering › Engine Controls (Electric/Electronic) › Circuit Board
Issued 24 February 2016 Resolved
Found engine controls in the ECC to be inoperable. Make necessary repairs and prove proper operation to the attending marine inspector.
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Resolved 26 April 2016
Fire Fighting › Fixed Gas Fire Extinguishing System › Operating Controls
Issued 24 February 2016 Resolved
All firefighting annual servicing was overdue. Provide annual servicing certificate for all firefighing equiptment and conduct time delay, shut down, and alarm tests in the presence of a CG marine inspector.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 25 April 2016
Resolution: Received certificates of satisfactory servicing from BFPE International fire servicing company.
Lifesaving › Lifeboat Equipment › Hand Flare
Issued 24 February 2016 Resolved
Lifeboat flares and food were expired. Make all lifeboat provisions and equiptment ready for inspection prior to leaving MHI (dockside availibility).
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 April 2016
Resolution: Verified lifeboat provisions; all sat.
Personnel › Certificates/Documents/Licenses › Medical Fitness Document
Issued 16 February 2016 Resolved
Nine crew members could not provide valid medical certificates. Those nine crew members must produce valid medical certificates to an attending marine inspector prior to getting underway with the vessel.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 19 February 2016
Resolution: All nine crew memebers produced either a valid medical certificate or proof of that their appplications were submitted to the NDC for approval.
Engineering › Steam Boiler (propulsion) › Tube Sheet
Issued 9 October 2015 Resolved
Port Boiler economizer has temoporary repairs for leaks. Make permanent repair IAW boiler manufacture specifications and test to the satisfaction of CG Marine Inspector.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 November 2015
Engineering › Steam Boiler (propulsion) › Valve, Superheater Header Vent
Issued 9 October 2015 Resolved
Port boiler has steam leak on superheater vent nipple. Make permanent repair to superheater vent IAW boiler manufacture specifications to the satisfaction of CG Marine Inspector.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 November 2015
Engineering › Steam Boiler (propulsion) › Tube Sheet
Issued 9 October 2015 Resolved
Stbd boiler is leaking in way of economizer. Make permanent repairs to economizer IAW boiler manufacture specifications and test to the satisfaction of CG Marine Inspector.
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 November 2015
Electrical › Electric Supply System (service) › Transformer
Issued 25 July 2012 Resolved
Prove proper operation of cathodic protection system #1.
Action required: 705 - Other - as specified
Due 18 December 2012
Resolved 7 December 2012
Resolution: Cathodic Protection System (#1) was satisfactory tested in presence of Attending Marine Inspector and attending class surveyor.
Engineering › Steam Boiler (propulsion) › Automation Equipment
Issued 14 October 2010 Resolved
Provide " MarineSafety Center approved" Periodic Safety Tets Proceduresfor verification by local OCMI.
Action required: 705 - Other - as specified
Due 3 December 2012
Resolved 21 December 2012
Resolution: Witnessed satisfactory PSTP verification IAW MWSC Letter: E2-1202711 during COI exam.
Operations/Management › Vessel Safety Management › Maintenance of Ship/Equipment
Issued 14 October 2010 Resolved
Provide O2 sensors to monitor oxygen leaks in the O2 producing room.
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 16 March 2011
Resolution: new portable sensors provided.
Engineering › Compressed Air System (control) › Valve
Issued 14 October 2010 Resolved
Demonstrate proper operation or documentation of the testing of the pressure relief safety valve for the O2 accumulator in the O2 producing room.
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 16 March 2011
Resolution: Recieved test report of satisfactory testof the safety relief valve dated 17Feb11.
Accommodation/Occupational Safety › Other Accommodation Spaces › Laundry
Issued 14 October 2010 Resolved
Prior to operation of the dryers, remove and clean lint from from vents located in the 3rd deck Navy laundry.
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 4 March 2011
Resolution: dryer vents cleaned.
Electrical › Lighting (emergency) › Lighting Feeder
Issued 14 October 2010 Resolved
Repair or replace exit sign/light at aft port door of medical storage (the Barn).
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 13 June 2011
Resolution: Replaced with new.
Electrical › Lighting (service) › Conductor
Issued 14 October 2010 Resolved
Provide metal support for newly installed light cable and install lamp cover on fixture in 2nd isle from port, all located in medical storage (the Barn)
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 15 September 2011
Resolution: metal straps installed.
Personnel › Certificates/Documents/Licenses › License, Chief Mate
Issued 14 October 2010 Resolved
Provide all crew and officer documents and licenses prior to departing port.
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 16 March 2011
Resolution: Reviewed all crews documents.
Operations/Management › Drills/Instruction › Fire
Issued 14 October 2010 Resolved
Demonstrate satisfactory fire and abandon ship drills prior to departing port.
Action required: 705 - Other - as specified
Due 2 April 2011
Resolved 16 March 2011
Resolution: witnessed satisfactory drills.
Lifesaving › Lifeboat › Propulsion Engine
Issued 13 September 2010 Resolved
Water was identified in the engine crankcase and lube oil cooler in lifeboat motors 5 and 7. Vessel's total manning to be reduced by 230 persons until corrected.
Action required: 705 - Other - as specified
Due 13 October 2010
Resolved 10 January 2011
Resolution: witnessed operation of the #5 and #7 lifeboats.
Navigation › Collision/Grounding Avoidance › Radar
Issued 17 February 2010 Resolved
Make repairs to the Radar display unit to enable navigation using both 10 cm and 3 cm radars simultaneously. Provide the [name withheld] with technical report attesting to the proper operation of repaired unit.
Action required: 705 - Other - as specified
Due 17 March 2010
Resolved 1 March 2010
Resolution: Cleared def based on tech report attesting to the proper operation of the display unit.
Lifesaving › Launching Appliances › Winch
Issued 17 February 2010 Resolved
Vessel to make repairs to the over riding clutch for the #4 Life Boat.
Action required: 705 - Other - as specified
Due 18 March 2010
Resolved 15 April 2010
Resolution: Clutch repaired and tested satisfactory
Electrical › Lighting (emergency) › Lighting Fixture
Issued 4 December 2008 Resolved
Make repairs and demonstrate proper operation of exit lights throughout ship.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 25 February 2009
Resolution: cleared.
Electrical › Electrical Distribution System (service) › Ground Detection
Issued 4 December 2008 Resolved
Ground detection system showed full grounds on panels LC9 and LC4. Clear all grounds from system.
Action required: 705 - Other - as specified
Due 9 February 2009
Resolved 25 February 2009
Resolution: cleared.
Fire Fighting › Fixed Halon Fire Extinguishing System › Piping
Issued 4 December 2008 Resolved
Provide brackets for the piping to the time delay bottle for the Halon system for the Cat Scan room.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 6 March 2009
Resolution: new brackets installed.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Piping
Issued 4 December 2008 Resolved
Flex hose to the CO2 bottle for the hospital emergency generator needs to be replaced due to torn covering.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 6 March 2009
Resolution: hose replaced.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 4 December 2008 Resolved
Time delay on AMR fixed Halon system activates at 35 seconds, time delay bottle is designed for 60 seconds. Demonstrated proper operation of system.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 11 March 2009
Resolution: Installed new time delay bottle. Completed satisfactory test of time delay.
Pollution Prevention/Response › Prevention Equipment › Marine Sanitation Device, Type III
Issued 4 December 2008 Resolved
Sewage tank in engine room shall be repaired as orignal. Hole on back wall, gasket and bolting along the top inpoor condition. Sewage smell (H2S) is toxic and is emanating fromthe tank.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 25 February 2009
Resolution: repairs completed and air test sat.
Lifesaving › Lifeboat Equipment › Anti-seasickness Medicine
Issued 4 December 2008 Resolved
Make available all life boat equipment for inspection.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 6 March 2009
Resolution: inspection completed.
Lifesaving › Inflatable Liferafts › Servicing
Issued 4 December 2008 Resolved
Provide service reports for all life rafts and hydrostatic releases. Sevicing date has expired.
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 6 March 2009
Resolution: servicing completed.
Fire Fighting › Grease Extraction Hood › General
Issued 4 December 2008 Resolved
Demonstrate operation of all Gaylord hoods in both galleys.
Action required: 705 - Other - as specified
Due 9 February 2009
Resolved 18 August 2009
Resolution: Service report provided attesting to the proper operation fo the gaylord hoods.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Instructions
Issued 4 December 2008 Resolved
Provide operating instructions for fixed CO2 system for the flamable locker in the bio-hazzard space.
Action required: 705 - Other - as specified
Due 9 February 2009
Resolved 18 August 2009
Resolution: operating instructions posted.
Operations/Management › Drills/Instruction › Abandon Ship
Issued 4 December 2008 Resolved
Conduct fire and boat drills
Action required: 17 - Rectify deficiencies prior to departure
Due 9 January 2009
Resolved 11 March 2009
Resolution: Completed satisfactory fire and abandon ship boat drill.
Engineering
Issued 1 June 2001 Resolved
CONDUCT REPAIRS AND PROVE PROPER OPERATION OF NO.1 STEAM TURBINE FEEDWATER PUMP PRIOR TO DEPARTURE & TO THE SATISFACTION OF THE ATTENDING COAST GUARD MARINE INSPECTOR.
Condition: Unknown
Due 6 June 2001
Resolved 2 June 2001
Engineering
Issued 27 June 1997 Resolved
MAKE PERMANENT REPAIRS TO, AND CONDUCT OPERATIONAL TEST OF FWD HP TURBINE OIL SEAL DEFLECTOR. LOG RESULTS OF TEST IN MACHINERY LOG, AND MAKE LOG AVAILABLE TO CG MARINE INSPECTOR FOLLOWING SEA TRIALS.
Condition: Unknown
Due 27 June 1997
Resolved 27 June 1997
Lifesaving
Issued 23 December 1996 Resolved
Submit plan on modifications to starboard liferaft launching apparatus no later than 15JAN97 and prior to activation.
Condition: Unknown
Due 23 December 1996
Resolved 23 December 1996
Lifesaving
Issued 24 October 1996 Resolved
You are directed to remove from the vessel all 59 Seaco/Elliot life rafts. Until such time as the life rafts are satisfactorily tested, examined, and installed on the vessel to the satisfaction of the attending inspector, total persons allowed on the COI is reduced to 1,950 persons._x001C_
Condition: Unknown
Due 24 October 1996
Resolved 24 October 1996
Engineering
Issued 28 May 1994 Resolved
REPAIR LEAKY SUPERHEATER SAFETY VALVE AFTER SEA TRIAL AND DEMONSTRATE PROPER OPERATION OF SAME NO LATER THAN 01JUN94.
Condition: Unknown
Due 14 June 1994
Resolved 14 June 1994
Fire Fighting
Issued 28 May 1994 Resolved
DEMONSTRATE PROPER OPERATION OF THE PRESSURE TRANSDUCER AND THE ASSOCIATED DIGITAL PRESSURE GAUGE FOR THE NEWLY INSTALLED FORWARD STANDBY FIRE PUMP.
Condition: Unknown
Due 14 June 1994
Resolved 14 June 1994
Fire Fighting
Issued 28 May 1994 Resolved
SUBMIT TO THE COGNIZANT OCMI FOR REVIEW AND APPROVAL THE INSTALLATION PLANSFOR THE FWD STBY FIRE PMP IN SERVICE AREA #1. PLANS TO BE SUBMITTED SHALL INCLUDE OTHER AS-BUILT PLANS AFFECTED BY THIS NEW INSTALLATION.THIS REQUIREMENT SHALL BE COMPLIED WITH NO LATER THAN 30JUN94.
Condition: Unknown
Due 28 May 1994
Resolved 28 May 1994
Electrical
Issued 28 May 1994 Resolved
SUBMIT TO THE COGNIZANT OCMI FOR REVIEW AND APPROVAL, THE INSTALLATION PLANS FOR THE NEW AIR COMPRESSORS AND AIR DRYER IN THE ENGINE ROOM. THIS REQUIREMENT SHALL BE COMPLIED WITH NO LATER THAN 30JUN94.
Condition: Unknown
Due 28 May 1994
Resolved 28 May 1994
Construction/Loadline
Issued 28 May 1994 Resolved
INSTALL THE REQUIRED SHUT OFF VALVES AS CLOSE TO THE SHELL PENETRATIONS AS IS PRACTICABLE FOR THE SUCTION/DISC PIPES IN THE FOLLOWING LOCATIONS: P FR 80, P FR 15, S FR 40, S FR 60, S FR 51. INSTALLATION OF ABOVE REQUIRED VLVSWILL BE TO THE SATISFACTION OF THE COGNIZANT [name withheld].
Condition: Unknown
Due 28 May 1994
Resolved 28 May 1994
Lifesaving
Issued 21 December 1993 Resolved
PRIOR TO NEXT WEIGHT TEST OF LIFEBOAT #11; ESTABLISH TEST WATERLINE AS PERNVIC 6-81.
Condition: Unknown
Due 21 December 1993
Resolved 21 December 1993
Accommodation/Occupational Safety
Issued 21 December 1993 Resolved
RENEW THE RELIEF VALVE ON THE AFT AREA FRESH WATER TANK WITH ONE EQUIPPED WITH A HAND RELIEVING DEVICE.
Condition: Unknown
Due 21 March 1994
Resolved 6 April 1994
Engineering
Issued 21 December 1993 Resolved
RENEW THE STEAM RELIEF VALVE ESCAPE PIPING IN WAY OF THE PINHOLE IN THE "T"SECTION DIRECTLY OVER THE 135# REDUCING STATION.
Condition: Unknown
Due 21 December 1993
Resolved 21 December 1993
Electrical
Issued 21 December 1993 Resolved
MAKE PERMANENT REPAIRS TO THE BOILER ROOM CONSOLE "SHORE POWER AVAILABLE" INDICATOR LIGHT.
Condition: Unknown
Due 21 March 1994
Resolved 6 April 1994
Engineering
Issued 21 December 1993 Resolved
CONDUCT AN OPERATIONAL TEST OF THE RELIEF VALVES ON THE EMERGENCY DIESEL STARTING SYSTEM AIR RECEIVERS.
Condition: Unknown
Due 31 May 1994
Resolved 6 April 1994
Engineering
Issued 21 December 1993 Resolved
CONDUCT THE FOLLOWING INSPECTIONS ON THE STARBOARD BOILER: BOILER MOUNTINGS, FIRESIDE, WATERSIDE, AND HYDROSTATIC TEST.
Condition: Unknown
Due 21 December 1993
Resolved 21 December 1993
Lifesaving
Issued 21 December 1993 Resolved
OPEN ALL PRESURE VESSELS FOR INTERNAL AND OR HYDROSTATIC TESTING.
Condition: Unknown
Due 21 December 1993
Resolved 21 December 1993
Engineering
Issued 21 December 1993 Resolved
MAKE PERMANENT REPAIRS TO THE CONSOLE INDICATOR LIGHT FOR THE STARBOARD BOILER MAIN FUEL OIL CUTOUT OPEN POSITION INDICATOR.
Condition: Unknown
Due 21 March 1994
Resolved 6 April 1994
Engineering
Issued 21 December 1993 Resolved
RENEW THE BOILER ROOM ALARM CONSOLE HORN LOCATED AT THE 21'6" LEVEL.
Condition: Unknown
Due 21 March 1994
Resolved 6 April 1994
Engineering
Issued 21 December 1993 Resolved
CONDUCT THE FOLLOWING INSPECTIONS ON THE PORT BOILER: BOILER MOUNTINGS, FIRESIDE, WATERSIDE, AND HYDROSTATIC TEST.
Condition: Unknown
Due 21 December 1993
Resolved 21 December 1993
Lifesaving
Issued 21 December 1993 Resolved
PRIOR TO NEXT WEIGHT TEST OF LIFEBOAT #1; ESTABLISH TEST WATERLINE AS PER NVIC 6-81.
Condition: Unknown
Due 21 December 1993
Resolved 21 December 1993
Electrical
Issued 5 May 1993 Resolved
INSTALL GROUND FAULT PROTECTION FOR PATIENT PROTECTION IN VESSEL'S HEADS AND PATIENT TEATMENT AREAS (HYDROTHERAPHY SITZ BATHS/WHIRLPOOL TUBS).
Condition: Unknown
Due 5 May 1993
Resolved 5 May 1993
Electrical
Issued 5 May 1993 Resolved
INSTALL ELECTRICAL PANELS WITH VENT FANS/VENT OPENINGS TO PREVENT OVERHEATING OF THE MOTOR CONTROLLER COILS IN 02-62-0 COMP ROOM._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 5 May 1993
Resolved 5 May 1993
Electrical
Issued 5 May 1993 Resolved
PROPERLY ISOLATE LIGHTING AND POWER DISTRIBUTION CIRCUITS WITH LINE ISOLATION MONITORS FOR TRIAGE, OPERATING, RECOVERY, DENTAL, AND ALL ROOMS THAT HAVE ELECTRONIC EQUIPMENT ATTACHED TO OR IN CONTACT WITH PATIENTS._x001C_ _x001C_
Condition: Unknown
Due 5 May 1993
Resolved 5 May 1993
Engineering
Issued 21 December 1992 Resolved
DEMONSTRATE LOSS OF S/W COOLING TRIP FOR AMR GENERATORS_x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 24 November 1993
Resolved 24 November 1993
Accommodation/Occupational Safety
Issued 21 December 1992 Resolved
INSTALL A GUARD OVER THE FLYWHEEL OF THE ENGINEERING ELEVATOR MOTOR
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Lifesaving
Issued 21 December 1992 Resolved
REPAIR AND SHOW PROPER OPERATION OF LIFERAFT DAVIT #8
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Engineering
Issued 21 December 1992 Resolved
INSTALL APPROPRIATE SIZED SIGHT GLASS FOR DESUPERHEATER TANK
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Engineering
Issued 21 December 1992 Resolved
REMOVE JERRY RIGGED REGULATOR CONTROL PRE HEATER OF #4 EVAPORATOR
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Lifesaving
Issued 21 December 1992 Resolved
PROVIDE PROOF THAT 10 LIFERAFTS HAVE BEEN SERVICED AND PROPERLY INSTALLED ON THE VESSEL
Condition: Unknown
Due 24 November 1993
Resolved 24 November 1993
Deck/Cargo
Issued 21 December 1992 Resolved
INSTALL AN OIL CONTAINMENT UNDER THE COMPRESSOR LOCATED IN THE MEDICAL EMERGENCY GENERATOR RM
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Engineering
Issued 21 December 1992 Resolved
DEMONSTRATE LOSS OF LUBE OIL TRIP FOR AMR GENERATORS
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Accommodation/Occupational Safety
Issued 21 December 1992 Resolved
INSTALL TANK LEVEL GLASS FOR S/W FLUSHING HYDROSTATIC TANK
Condition: Unknown
Due 14 January 1993
Resolved 24 November 1993
Construction/Loadline
Issued 21 December 1992 Resolved
DFEMONSTRATE PROPER OPERATION OF BILGE ALARMS
Condition: Unknown
Due 24 November 1993
Resolved 24 November 1993
Documentation
Issued 21 December 1992 Resolved
INSTALL POLLUTION PLACARDS IN APPROPRIATE AREAS, INCLUDING MARPOL STICKERS
Condition: Unknown
Due 24 November 1993
Resolved 24 November 1993
Engineering
Issued 21 December 1992 Resolved
DEMONSTRATE PROPER OPERATION OF SALINITY SENSING/ALARM SYSTEM FOR ALL EVAPORATORS
Condition: Unknown
Due 24 November 1993
Resolved 24 November 1993
Lifesaving
Issued 24 January 1992 Resolved
SUPPLY EIGHT 25 MAN LIFERAFTS
Condition: Unknown
Due 31 March 1992
Resolved 27 March 1992
Electrical
Issued 24 January 1992 Resolved
REMOVE WIRENUT FROM ALL ELECTRICAL CIRCUITS THAT ARE EITHER EMERGENCY CIRCUITS OR LOCATED IN HAZARDOUS LOCATIONS.
Condition: Unknown
Due 24 January 1992
Resolved 24 January 1992
Lifesaving
Issued 24 January 1992 Resolved
PROVIDE ADDITIONAL RESCUE BOAT PRIOR TO THE CARRIGE OF PASSENGERS
Condition: Unknown
Due 31 March 1992
Resolved 27 March 1992
Fire Fighting
Issued 24 January 1992 Resolved
REPLACE SIGHT GLASS TUBE ON ENGINEROOM FOAM SYSTEM
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Deck/Cargo
Issued 24 January 1992 Resolved
INSTALL O2 CONTENT ALARM IN O2 CHARGING ROOM
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Documentation
Issued 24 January 1992 Resolved
UPDATE BALLAST CONTROL DIAGRAM T-AH-19, PROVIDE MSO BALTIMORE WITH COPY
Condition: Unknown
Due 24 January 1992
Resolved 24 January 1992
Engineering
Issued 24 January 1992 Resolved
SET MAIN BOILER SAFETY'S NOT TO EXCEED THE FOLLOWING: DRUM SAFETY 1100 PSI,SUPERHEATER SAFETY 1025 PSI, PILOT VALVE TO BE SET AT A PRESSURE WITN IN _x001C_ -2% OF SUPERHEATER RELIEF AND NO LESS THAT 75 PSI SHOULD BE BETWEEN DRUM SETTING AND SUPERHEATER SETTING.
Condition: Unknown
Due 24 January 1992
Resolved 24 January 1992
Engineering
Issued 24 January 1992 Resolved
HYDRO BOTH MAIN BOILERS
Condition: Unknown
Due 1 April 1992
Resolved 27 March 1992
Lifesaving
Issued 24 January 1992 Resolved
REMOVE EXCESS GAS BOTTLES IN O2 CHARGING SPACE OR INSTALL PERMANENT STORAGERACKS.
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Engineering
Issued 24 January 1992 Resolved
SET MAIN BOILER SAFETY'S
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Fire Fighting
Issued 24 January 1992 Resolved
REPAIR FIRE DOORS TO LATCH UPON CLOSING
Condition: Unknown
Due 30 April 1992
Resolved 27 March 1992
Lifesaving
Issued 24 January 1992 Resolved
SUBMIT FORMAL PROPOSAL TO APPROPRIATE USCG OFFICE IN REFERENCE TO VSL RESCUE BOATS AND LIFEBOATS 11 & 12
Condition: Unknown
Due 31 March 1992
Resolved 27 March 1992
Fire Fighting
Issued 24 January 1992 Resolved
CONDUCT TEST OF TURBIN FIRE PUMP (OVERSPEED AND PRESSURE RELIEF)
Condition: Unknown
Due 30 April 1992
Resolved 1 April 1992
Engineering
Issued 24 January 1992 Resolved
REPLACE FLEX COUPLINGS ON CIRC INTAKE OF MAIN CONDENSOR
Condition: Unknown
Due 24 January 1992
Resolved 24 January 1992
Fire Fighting
Issued 24 January 1992 Resolved
HYDRO SHIPS FIRE HOSES
Condition: Unknown
Due 31 March 1992
Resolved 27 March 1992
Fire Fighting
Issued 24 January 1992 Resolved
SERVICE SHIPS PORTABLE FIRE EXTINQUISHERS
Condition: Unknown
Due 31 March 1992
Resolved 27 March 1992
Engineering
Issued 24 January 1992 Resolved
REPAIR PRE-LUBE PUMP FOR #1 AUX GENERATOR
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Engineering
Issued 24 January 1992 Resolved
REPAIR #3 AUX GEN LLOP ALARM/SHUT DOWN
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Fire Fighting
Issued 24 January 1992 Resolved
REMOVE CO2 HOSE REEL FROM O2 CHARGING STATION AND INSTALL A FIXED CO2 FIREFIGHTING SYSTEM.
Condition: Unknown
Due 24 January 1992
Resolved 24 January 1992
Electrical
Issued 24 January 1992 Resolved
DEMONSTRATE PROPER OPERATION OF SHIPS EMERGENCY LIGHTING SYSTEM
Condition: Unknown
Due 24 January 1992
Resolved 24 January 1992
Documentation
Issued 24 January 1992 Resolved
PROVIDE SYSTEM INFORMATION FOR O2N2 PLANT. INDICATING TEST/INSPECTION PROCEDURES, DATES, AND NAVY REQUIREMENTS_x001C_ _x001C_ _x001C_
Condition: Unknown
Due 24 February 1992
Resolved 27 March 1992
Lifesaving
Issued 8 July 1991 Resolved
CONDUCT FIRE AND BOAT DRILL WITH FULL CREW PRIOR TO ACTIVATION.
Condition: Unknown
Due 8 July 1991
Resolved 8 July 1991
Fire Fighting
Issued 28 May 1991 Resolved
REPAIR ALL DAMAGED FIRE SCREEN DOORS TO ENSURE PROPER CLOSURE WITHOUT MANUAL ASSISTANCE
Condition: Unknown
Due 28 May 1991
Resolved 28 May 1991
Electrical
Issued 8 January 1991 Resolved
SHIP EMERGENCY SHIP DIESEL GENERATOR O/S TRIP DOES NOT WORK, WHEN GENERATORIS RUNNING IT MUST BE MANNED.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Fire Fighting
Issued 8 January 1991 Resolved
TEST IN PRESENCE OF U.S. COAST GUARD MARINE INSPECTOR FIRE DUMPERS AND _x001C_ SMOKE DETECTORS THROUGHOUT VESSEL.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Lifesaving
Issued 8 January 1991 Resolved
CONDUCT WEIGHT SUSPENSION TESTS OF LIFEBOAT AND LIFERAFT DAVITS AND FALLS IN PRESENCE OF USCG MARINE INSPECTOR.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Lifesaving
Issued 8 January 1991 Resolved
END FOR END LIFEBOAT AND LIFERAFT FALLS BY 30 APRIL 1991.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Fire Fighting
Issued 8 January 1991 Resolved
HYDROSTATICALLY TESTED ALL FIRE HOSES IN PRESENCE OF USCG MARINE INSPECTOR.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Fire Fighting
Issued 8 January 1991 Resolved
HAVE PORTABLE AND SEMI PORTABLE FIRE EXTINGUISHER OVER 5 YEARS OLD HYDROSTATICALLY TESTED AT APPROVED STATION BY 30 JUN 91.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Electrical
Issued 8 January 1991 Resolved
PROPERLY INSTALL ALL NEWLY INSTALLED DECK SECONDARY LIGHTS IN ACCORDANCE WITH 46 CFR 111. AT NEXT U.S. PORT OF CALL.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Documentation
Issued 8 January 1991 Resolved
OBTAIN FCC STATION LICENSE AND IOPP CERTIFICATE.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Accommodation/Occupational Safety
Issued 8 January 1991 Resolved
REPLACE IMPROPER SIZE RELIEF VALVE FOR FOLLOWING AIR RECEIVER I.D. NUMBER 75073 E/R, 75090 ENG. AM, 1255 AUX E/R, 1256 AUX E/R, EMER GEN SPACE, ALL HAVE SMALLER OPENING RELIEF VALVES THAN THERE ARE RECEIVERS. PLUS HAVE VARIOUS NIPPLE AND REDUCE TO MAKE UP SIZE DIFFERENCE.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Engineering
Issued 8 January 1991 Resolved
REPAIR OR REPLACE BOTH MAIN BOILERS SUPERHEATER SAFETY'S AND PILOT DRUM VALVE SAFETYS DUE TO EXCESSIVE BLOW DOWN OF VALVES.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Lifesaving
Issued 8 January 1991 Resolved
CONDUCT FIRE AND BOAT DRILL IN PRESENCE OF USCG APPROVED MARINE INSPECTOR.
Condition: Unknown
Due 8 January 1991
Resolved 8 January 1991
Lifesaving
Issued 13 August 1990 Resolved
PROVIDE 62 CERTIFIED LIFEBOATMEN.
Condition: Unknown
Due 13 August 1990
Resolved 13 August 1990
Lifesaving
Issued 10 August 1990 Resolved
DEMONSTRATE SATISFACTORY "COLD START" OF #7 & #8 LIFEBOATS. UNTIL THIS REQUIREMENT IS DONE TO THE SATISFACTION OF THE ATTENDING CG MARINE IN- SPECTOR, THE TOTAL PERSONS ALLOWED ON BOARD IS LIMITED TO 2,378
Condition: Unknown
Due 10 August 1990
Resolved 10 August 1990
Fire Fighting
Issued 10 August 1990 Resolved
UNTIL THE STEAM FIRE PUMP IS OPERATING PROPERLY, IT IS TO BE MANNED DURING ALL EMERGENCIES
Condition: Unknown
Due 10 August 1990
Resolved 10 August 1990
Engineering
Issued 10 August 1990 Resolved
ADJUST #2 MAIN FEED PUMP LOW LUBE OIL PRESSURE ALARM TO ABOUT 25 PSI(+/-3)
Condition: Unknown
Due 10 August 1990
Resolved 10 August 1990
Engineering
Issued 10 August 1990 Resolved
ADJUST MAIN FEED LOW PRESSURE ALARM TO ACTIVATE AT 50 TO 75 PSI DIFFEREN- TIAL
Condition: Unknown
Due 10 August 1990
Resolved 10 August 1990
Unknown
Issued 10 August 1990 Resolved
DEMONSTRATE PROPER OPERATION OF ALL SHIPS LIFEBOAT ENGINES AT OR ABOUT 20 DEGREES F. ENGINE START SHALL NOT UTILIZE ETHER ASSIST COMPONENT ORIGINAL REQUIREMENTS ISSUED 21NOV89
Condition: Unknown
Due 10 August 1990
Resolved 10 August 1990
Unknown
Issued 13 April 1990 Resolved
PROVIDE UPDATED GENERAL ARRANGEMENT, STRUCTURAL FIRE PROTECTION, CAPACITY PLANS AND RECORD OF SIGNIFICANT WEIGHT CHANGES TO USCG MARINE SAFETY CENTERAS PER MSC LTR 16710, SER H2/E-00304 DTD 2APR90
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Electrical
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF EMERGENCY GENERATOR LOW LUBE OIL PRESSURE ALARM AND SHUTDOWN
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Fire Fighting
Issued 13 April 1990 Resolved
DEMONSTRATE LOSS OF L/O PRESS SHUTDOWN ON STEAM TURBINE GENERATOR
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Fire Fighting
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF STEAM FIRE PUMP
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Electrical
Issued 13 April 1990 Resolved
REPLACE MISSING PORTABLE FIRE EXTINGUISHERS AT STA 211, 267
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Engineering
Issued 13 April 1990 Resolved
DEMONSTRATE OVERSPEED TRIP ON ENGINE ROOM DIESEL
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
INSTALL HYDRAULIC STARTING SYSTEM IN LIFEBOAT #1,2,4,6,8,10. TOTAL PERSONSLIMITED TO 1048
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Engineering
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF ENGINE ROOM STARTING AIR RECEIVER RELIEF VALVE (2) #2 133/120 #1 135/118
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Construction/Loadline
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF BALLAST SYSTEM
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Engineering
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF BILGE SYSTEM AND BILGE ALARMS IN ENGINEROOM(3)
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Engineering
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF OILY WATER SEPARATOR
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Engineering
Issued 13 April 1990 Resolved
DEMONSTRATE AUTOMATION TEST PROCEDURES SECTION B, C AND D
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
PLACE HANDLES ON BOTH SIDES OF DOOR TO THE FOC'SLE DECK MAINTENANCE STEP
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
REMOVE MEANS OF LOCKING DOORS TO THE 02/N2 PLANT, FROM THE OUTSIDE. IF LOCKS DESIRED ON DOORS, THEY SHALL BE OF THE TYPE TO ALLOW THE DOOR TO BE OPENED FROM THE INSIDE WHEN LOCKED
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
GRIND OUT IMPERFECTIONS ON FOUNDATION OF LIFERAFT DAVIT #12 AT POINT WHERE ARC WELDER GRAND WAS CONNECTED. REPAINT
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
REPAIR BROKEN LOWER RAIL COURSE BY LIFERAFT #14
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
INSTALL DOOR KNOB TO FIRE SCREEN DOOR TO FORKLIFT STORAGE ROOM (02-69-2)
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
REPAIR WORN LABELING ON THE BRIDGE THROTTLE POSITIONAL CONTROL
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
PROVIDE SOLAS COVER TO LIFE BOAT #2
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
REPAIR FIRE DAMPER 01-42-7
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Unknown
Issued 13 April 1990 Resolved
ADDRESS ISSUES IN USCG MARINE SAFETY CENTER HR 16710 SER H2/E-00304 DTD 2APR90. PARA 1C,1D,1E,1F,1G,1H,1I,1J,1K,1L NO LATER THAN 15MAY90
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Electrical
Issued 13 April 1990 Resolved
DEMONSTRATE PROPER OPERATION OF NEW SHORE TIE INSTALLATION AND PROVIDE APPROVED PLANS
Condition: Unknown
Due 13 April 1990
Resolved 13 April 1990
Construction/Loadline
Issued 5 February 1990 Resolved
EFFECT REPAIRS TO WASTED TANK TOPS IN SERVICE AREAS 2 & 4 AS OUTLINED BY ABS REPORT NUMBER BA8027. PRIOR TO BEGINNING REPAIRS, A COAST GUARD MARINE INSP. IS TO CONDUCT AN ON-SITE INSPECTION W/THE ATTENDING ABS SURVEYOR TO AGREE ON REPAIR SPECIFICS (I.E. EPOXY/STEEL FILLER VICE WELD BUILD UP)
Condition: Unknown
Due 5 February 1990
Resolved 5 February 1990
Lifesaving
Issued 21 November 1989 Resolved
PLACE LIFEBOAT ENGINES #1,3,11 & 12 INTO PROPER OPERATING CONDITION. DEMONSTRATE OPERATION OF ENGINES. TOTAL PERSONS ALLOWED ON BOARD LIMITED TO 2039
Condition: Unknown
Due 21 November 1989
Resolved 21 November 1989
Lifesaving
Issued 21 November 1989 Resolved
DEMONSTR4ATE PROPER OPERATION OF ALL SHIPS LIFEBOAT ENGINES AT OR ABOUT 20 DEGREES F. ENGINE START SHALL NOT UTILIZE ETHER ASSIST COMPONENT
Condition: Unknown
Due 21 November 1989
Resolved 21 November 1989
Lifesaving
Issued 8 November 1989 Resolved
PLACE LIFEBOATS #5,7&8 INTO OPERATION. DEMONSTRATE PROPER OPERATION OF ENGINES. TOTAL PERSONS ALLOWED ON BOARD LIMITED TO 23443 UNTIL ABOVE REQUIREMENT IS COMPLETE
Condition: Unknown
Due 8 November 1989
Resolved 8 November 1989
Lifesaving
Issued 25 October 1989 Resolved
PLACE ENGINES BACK IN LIFEBOATS #3 AND #5. DEMONSTRATE PROPER OPERATION OF ENGINES
Condition: Unknown
Due 25 October 1989
Resolved 25 October 1989
Deck/Cargo
Issued 25 October 1989 Resolved
PLACE FLAMMABLE LIQUIDS IN STORAGE ROOM 02-69-01 IN A SPACE DESIGNATED AS A FLAMMABLE STOWAGE SPACE
Condition: Unknown
Due 25 October 1989
Resolved 25 October 1989
Unknown
Issued 29 September 1989 Resolved
PROVIDE AN UPDATED TRIM & STABILITY BOOKLET TO THE COGNIZANT OCMI
Condition: Unknown
Due 29 September 1989
Resolved 29 September 1989
Lifesaving
Issued 28 July 1989 Resolved
VSL PERMITTED TO SAIL TO ANNAPLOIS, MD AND ONWARD TO BALTIMORE, MD FROM NORFOLK, VA WITH NOT MORE THAN 204 PERSONS ONBOARD AT ANY TIME WHILE UNDER-WAY. VSL PERMITTED TO USE #1 & #2 LIFEBOATS WITH 10 CERT. LIFEBOATMEN. THIS CG-835 TERMINATES WHEN VSL REACHES BALTIMORE.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Construction/Loadline
Issued 28 July 1989 Resolved
CROP & RENEW BY INSERTS THE WASTED TANK TOP AREAS IN WAY OF SERVICE AREAS #2 AND #4 AS IDENTIFIED BY MARKED NORSHIPCO CONDITION REPORT NUMBER 109 DTD27JUN89.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Documentation
Issued 28 July 1989 Resolved
PROVIDE AN UPDATED TRIM & STABILITY BOOKLET TO THE COGNIZANT [name withheld] TO THE CHESAPEAKE BAY UNTIL THIS REQUIREMENT IS MET.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Unknown
Issued 28 July 1989 Resolved
PROVIDE EVIDENCE OF COMPLIANCE WITH PARAGRAPH 2 OF USCG MARINE SAFETY CENTER LETTER 16710/T-AH20, SERIAL #H2-90812, DTD 24JUL89 TO COGNIZANT OCMI.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Construction/Loadline
Issued 28 July 1989 Resolved
PROVE WATERTIGHT CAPABILITY OF 2 NEW QAWT DOORS AT FRAMES 84 & 95. GUAGINGSTOLERANCE TO BE .003 OR LESS.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Construction/Loadline
Issued 28 July 1989 Resolved
AS PER USCG MARINE SAFETY CENTER LETTER 16710/T-AH 20, SERIAL #H2-90791 DTD18JUL89, PROVIDE EVIDENCE OF ABS APPROVAL OF THE DRAWINGS FOR THE QUICK- ACTING HORIZONTAL WATERTIGHT DOORS (NORSHIPCO DRAWING #67-1014, SHEETS 1 & 2) TO THE COGNIZANT OCMI.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Unknown
Issued 28 July 1989 Resolved
PROVIDE EVIDENCE OF COMPLIANCE WITH FOLLOWING USCG MSC LTRS 16710/T-AH20: (A)SERIAL# H2-90792 DTD 19JUL89-STBD RAMP/CRANE/CAMEL.
Condition: Unknown
Due 28 July 1989
Resolved 28 July 1989
Electrical
Issued 11 May 1989 Resolved
LOCATE AND REMOVE ALL WIRE NUTS USED IN ELECTRICAL WIRING THROUGH-OUT VESSEL. WIRE NUTS WERE FOUND IN EMERGENCY LIGHTING FIXTURES. ALL CONNECTIONS SHALL BE IN ACCORDANCE WITH 46 CFR SUBPART 111.60-17.
Condition: Unknown
Due 11 May 1989
Resolved 11 May 1989
Fire Fighting
Issued 31 March 1989 Resolved
PROVIDE RESULTS OF TEST OF FOAM PROPORTIMER FOR AFFF AND PROTEIN FOAM SYSTEM
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
CONDUCT FIRE AND ABANDON SHIP DRILLS IN PRESENCE OF USCG MARINE INSPECTOR
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
RENEW STARTER CRANK INTO NR3 LIFE BOAT
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Fire Fighting
Issued 31 March 1989 Resolved
RENEW SOLID ELECTRICAL WIRE (JUMPERS) IN PANEL BOARD FOR SMOKE/FIRE DETECTION SYSTEM LOCATED ON BRIDGE
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
RENEW OTHER PUMP IN NR3 LIFE BOAT AND CONDUCT OPERATIONAL TEST
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
RENEW CRANK ENGAGING GEAR TO FLYWHEEL IN NR7 LIFE BOAT. CONDUCT OPERA- TIONAL TEST OF LIFE BOAT PROPULSION
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
PROVIDE 87 ADULT AND 48 CHILDREN'S TYPE I LIFE JACKETS WITH LIGHTS AND WHISTLES
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
REPAIR SEVENTH RUNG ON EMBARKATION LADDER IN WAY OF NO. 3 LIFE BOAT
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Engineering
Issued 31 March 1989 Resolved
CONDUCT SUCCESSFUL HYDROSTATIC TEST OF RECENTLY ALTERED DIESEL TANK IN AMR SPACES
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
PROVIDE 4-5' PADDLES FOR EACH LIFEFLOAAT
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Deck/Cargo
Issued 31 March 1989 Resolved
DEMONSTRATE OPERATION OF PATIENT HOIST. PROVIDE RECORDS OF PROOF LOAD TESTOR THAT HOISE IS CURRENTLY ENROLLED IN ABS INSPECTION PROGRAM
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
PROVIDE SOLAS COVER AND FRAME FOR NR11 LIFE BOAT
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Fire Fighting
Issued 31 March 1989 Resolved
PROVIDE MEANS OF SECURING VENTILATION FAN TO CAT SCAN ROOM IN THE EVENT OF HALON DISCHARGE. MANUAL SWITCH TO SECURE VENTILATION SHALL BE LOCATED ADJACENT TO HALON CONTROLS WITH PLACARD INDICATING SEQUENCE OF OPERATION
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Deck/Cargo
Issued 31 March 1989 Resolved
PROVIDE VALID ABS INSPECTION CERTIFICATE FOR ALL ELEVATORS
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Electrical
Issued 31 March 1989 Resolved
DEMONSTRATE OPERATION OF GENERAL ALARM BELLS/LIGHTS AS PER ATTACHED LIST
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Accommodation/Occupational Safety
Issued 31 March 1989 Resolved
PROPERLY SECURE COMPRESSED GAS CYLINDERS IN UTILITY ROOMS 5-43-3 AND 5-50-3
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Lifesaving
Issued 31 March 1989 Resolved
DEMONSTRATE ALL LIFE BOAT ENGINES CAN BE STARTED WITHOUT ANY STARTING AIDS AT APPROXIMATELY 20DEGREES(F) USING CURRENTLY INSTALLED CRANKING SYSTEM
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Electrical
Issued 31 March 1989 Resolved
DEMONSTRATE EMERGENCY LIGHTING IN CREW AND PASSENGER SPACES
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Electrical
Issued 31 March 1989 Resolved
RENEW CRACKED LENS ON EMBARKATION LIGHT IN WAY OF NR 7 LIFE BOAT
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989
Fire Fighting
Issued 31 March 1989 Resolved
REPAIR FIREMAIN VALVES WHERE LEAKING IN AFT HOUSE. APPLY PRESSURE TO FIRE-MAIN TO DEMONSTRATE
Condition: Unknown
Due 31 March 1989
Resolved 31 March 1989

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.