THE HOLLAND PRINCESS

THE HOLLAND PRINCESS is a 1987 passenger vessel (inspected). The Coast Guard has recorded 16 inspections since 2016, most recently in May 2026, along with 19 deficiencies.

Records from 2016 to 2026. Most recent: inspection, 26 May 2026.

Built
1987
Last inspected
26 May 2026
Documentation
Case Pending · documentation file of 10 August 2026
Controls
None recorded without a removal date

Identity

WDQ5139
279417
Flag
UNITED STATES
Maury page id
psix-279417

Inspections, by type

Years with a record 11 calendar years (2016–2026)
The 16 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Documentation record

Registered dimensions (L × B × D)64.0 ft × 20.0 ft × 3.4 ft
Registered tonnagegross 36 / net 36
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderSKIPPERLINER INDUSTRIES · LA CROSSE, WI, UNITED STATES · built 1987
Hull materialSteel
PropulsionInboard/Outboard
Hull shapeBox
Hull configurationMonohull
Hailing portHOLLAND, MI
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationCase Pending · issued 30 June 2004
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it36 - Simplified, Gross Ton
36 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.

Inspection history · 16

26 May 2026 Annual Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 8370845
17 July 2025 Administrative Inspection · Annual Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 8186275
25 April 2024 COI Inspection · Deficiency Check
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7889340
29 February 2024 Deficiency Check
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7870933
30 October 2023 Internal Structural Exam · Drydock Exam
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7821585
18 May 2023 Annual Inspection · In-Service Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7691514
14 November 2022 Internal Structural Exam · Drydock Extension · Administrative Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7619527
1 June 2022 Deficiency Check · Annual Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7478232
17 June 2021 Annual Inspection · DAPI Audit
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 7231404
4 June 2020 Annual Inspection · DAPI Audit
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 6969007
30 April 2019 COI Inspection
Physical examination · Sector Lake Michigan · USCG Great Lakes District (CGD-GL) · Activity 6656218
10 April 2018 DAPI Audit · Annual Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 6388569
19 October 2017 Drydock Exam · Internal Structural Exam
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 6295083
20 June 2017 Deficiency Check
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 6181630
9 May 2017 DAPI Audit · Annual Inspection
Physical examination · Detached Duty Office Grand Haven · USCG Great Lakes District (CGD-GL) · Activity 6142038
3 May 2016 Annual Inspection
Physical examination · Sector Lake Michigan · USCG Great Lakes District (CGD-GL) · Activity 5873934

Deficiency record · 19

05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 17 July 2025 Resolved
One ship station license will be granted for operation of all maritime services transmitting equipment onboard a vessel. FCC station license is expired. 47 CFR 80.13
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 July 2025
Resolved 25 July 2025
Resolution: Vessel got station license.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 17 July 2025 Resolved
If a garden hose is used [] shall be fitted with a commercial grade bronze or equivalent metal hoze nozzle. Hose nozzle is not metal. 46 CFR 181.15-10(e) Old T
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 July 2025
Resolved 25 July 2025
Resolution: Vessel got new metal hose nozzle
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 17 July 2025 Resolved
The waterlight which is to be attached for night time operations shall be stowed close to the ring life bouy. Waterlight battery is not approved for waterlight. 46 CFR 180.30-10(c) Old T
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 July 2025
Resolved 31 July 2025
Resolution: Purchased new waterlight.
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 25 April 2024 Resolved
The person in command of a documented vessel must produce the original Certificate of Documentation currently in effect for that vessel upon the demand of any person acting in an official public capacity. COD is expired, provide a valid COD as required.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 April 2024
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 25 April 2024 Resolved
A vessel on a lakes, bays, and sounds route must carry Three hand red flare distress signals approved in accordance with § 160.021; and Three hand orange smoke distress signals approved in accordance with § 160.037 in subchapter Q.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 April 2024
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 25 April 2024 Resolved
Electrical breaker panel boards shall be of the safety type. The originally installed cover for the breaker panel is missing. Replace cover as designed for the existing breaker panel.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 17 July 2025
Resolution: Cover was installed
14 - Pollution Prevention › 145 - MARPOL Annex V › Placards
Issued 25 April 2024 Resolved
The master or person in charge of a vessel, shall ensure that one or more garbage placards is posted as required.
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 April 2024
11 - Life Saving Appliances › N/A - No Subsystem › Operation of Life Saving Appliances
Issued 25 April 2024 Resolved
A vessel must carry at least one floating water light. Found life light not illuminating. Vessel is restricted to day time operations until evidence is provided of a working water light.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 April 2024
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 18 May 2023 Resolved
Visual and audible alarms were not all labled for the correct space location.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 June 2023
Resolved 19 May 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 1 June 2022 Resolved
Observed leaking fuel injector on starboard main diesel engines. Conduct repairs and provide objective evidence of leak free diesel injector condition.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 June 2022
Resolution: Received objective evidence of correction.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 1 June 2022 Resolved
Annual servicing of portable fire extinguishers on board was not completed. Provide portable extinguisher required servicing documentation.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 June 2022
Resolution: Received objective evidence of correction.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 1 June 2022 Resolved
Grab line around life ring buoy located on upper deck is wasted. Renew or provide new life ring buoy grab line.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 June 2022
Resolution: Received objective evidence of correction.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 10 April 2018 Resolved
Attached line was not UV resistant and had deteriorated.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 May 2018
Resolved 7 May 2018
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 10 April 2018 Resolved
First aid kit not available
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 May 2018
Resolved 7 May 2018
Operations/Management › Lifesaving › Op Readiness/Maintenance/Inspection
Issued 10 April 2018 Resolved
Vessel not ready to perfor drills.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 May 2018
Resolved 7 May 2018
Fire Fighting › Fire Pumps › Pressure
Issued 10 April 2018 Resolved
Fire pump will not prime.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 May 2018
Resolved 7 May 2018
Electrical › Electrical Distribution System (service) › Metallic Enclosure/Frame
Issued 9 May 2017 Resolved
Motor controllers for HVAC system were missing covers.
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 22 June 2017
Engineering › Lubricating Oil Service System › Gauge
Issued 9 May 2017 Resolved
Oil pressure gauge at operating station was not operable.
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 22 June 2017
Fire Fighting › Ventilation Systems › Ducts
Issued 9 May 2017 Resolved
No way to close engine room supply ventilation
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 22 June 2017

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.