07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 3 March 2026
Resolved
A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station: A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section. The stbd pre-engineered fixed gas fire extinguishing system reset device (override) failed preventing the engine from restarting. Prove proper operation as described by the regulation and manufacturer’s instructions in the presence of the attending marine inspector.
46 CFR 181.420(b)(3)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 4 March 2026
Resolution: Attended vessel for def check.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 3 March 2026
Resolved
At each initial and subsequent inspection for certification, the marine inspector may require that a fire drill be held under simulated emergency conditions to be specified by the inspector. Drill not conducted due to the failed stbd pre-engineered fixed gas fire extinguishing system reset device. Conduct a satisfactory man overboard drill in the presence of the attending marine inspector upon completing repairs to the failed stbd pre-engineered fixed gas fire extinguishing system reset device.
46 CFR 176.810(d)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 4 March 2026
Resolution: Attended vessel for def check.
04 - Emergency Systems › N/A - No Subsystem › Man Overboard Drill (MOB)
Issued 3 March 2026
Resolved
At each initial and subsequent inspection for certification, the marine inspector may require that an abandon ship or man overboard drill be held under simulated emergency conditions specified by the inspector. Drill not conducted due to the failed stbd pre-engineered fixed gas fire extinguishing system reset device. Conduct a satisfactory man overboard drill in the presence of the attending marine inspector upon completing repairs to the failed stbd pre-engineered fixed gas fire extinguishing system reset device.
46 CFR 176.808(g)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 4 March 2026
Resolution: Attended vessel for def check.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 March 2026
Resolved
The cognizant OCMI may require that a vessel and its equipment undergo any additional test or inspection deemed reasonable and necessary to determine that the vessel and its equipment are suitable for the service in which they are to be employed. Observed a suspected crack on the stbd crossbeam vertical station weld propagating to the end plate of the crossbeam. Remove paint to expose the aluminum for reinspection by the attending marine inspector by March 4, 2025.
46 CFR 176.840
Action required: 705 - Other - as specified
Due 4 March 2026
Resolved 4 March 2026
Resolution: Attended vessel for def check.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 3 March 2026
Resolved
A vessel of 12 meters or more in length shall be provided with a whistle. Vessel missing whistle. Provide a whistle with a range of 0.5 miles as described in Table 33 CFR 86.01(c) to the satisfaction of the attending marine inspector by March 4, 2025.
33 CFR 83.33(a)
Action required: 705 - Other - as specified
Due 4 March 2026
Resolved 4 March 2026
Resolution: Attended vessel for def check.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 3 March 2026
Resolved
An emergency instruction placard containing the following information will satisfy the requirements of § 185.510. Vessel emergency instructions missing flooding. Amend vessels emergency instructions to include flooding as described by the regulation to the satisfaction of the attending marine inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 March 2026
Resolved 11 March 2026
Resolution: received proof of def rectification
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 3 March 2026
Resolved
Fuses must be of the cartridge type only and be listed by Underwriters Laboratories or another independent laboratory recognized by the Commandant. The radio inline fuse is of a blade type. Replace with same amperage UL approved cartridge type fuse to the satisfaction of the attending marine inspector.
46 CFR 183.380(l)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 March 2026
Resolved 4 March 2026
Resolution: Attended vessel for def check.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 3 March 2026
Resolved
Except as noted in § 176.114 of this part, each vessel inspected and certificated under the provisions of this subchapter must, when any passengers are aboard during the tenure of the certificate, be in full compliance with the terms of the certificate. Vessel has Sector Honolulu WI-31 on the COI routes permitted and conditions of operation. The portable oxygen bottle required by WI-31 has passed its hydrostatic test date. 1) Replace with a new oxygen bottle or 2) Hydrostatic test the overdue oxygen bottle to the satisfaction of the attended marine inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 March 2026
Resolved 11 March 2026
Resolution: Received proofs of def rectification.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 3 March 2026
Resolved
Each rescue boat and ring life buoy must be marked with Type II retroreflective material approved in accordance with 46 CFR 164.018 or other standard specified by the Commandant. The ring life buoy has a strip of wasted retroreflective tape. Renew in-kind to the satisfaction of the attending marine inspector.
46 CFR 185.604(i)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 March 2026
Resolved 4 March 2026
Resolution: Attended vessel for def check.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 3 March 2026
Resolved
Except as noted in § 176.114 of this part, each vessel inspected and certificated under the provisions of this subchapter must, when any passengers are aboard during the tenure of the certificate, be in full compliance with the terms of the certificate. Vessel has Sector Honolulu WI-31 on the COI routes permitted and conditions of operation. The current WI-31company policy does not meet Sector Honolulu WI-31 policy requirements. Revise the current WI-31 company policy to include the specific information missing for review and approval by the attending marine inspector to retain the reduced manning endorsement.
46 CFR 176.100(b)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2026
Resolved 11 March 2026
Resolution: Received proofs of def rectification.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 3 March 2026
Resolved
The master of a vessel, except a vessel listed in § 185.502(a) of this part, shall keep a correct, written count of all passengers that embark on and disembark from the vessel. Prior to departing on a voyage, the passenger count must be communicated verbally or in writing, and available ashore at the vessel's normal berthing location or with a representative of the owner or managing operator of the vessel. The passenger count shall be available to the Coast Guard upon request. No process to meet the above regulation is implemented. Implement the above regulation as described to the satisfaction of the attending marine inspector.
46 CFR 185.504
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 March 2026
Resolved 11 March 2026
Resolution: Received proofs of def rectification.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 March 2026
Resolved
Spaces containing machinery shall be fitted with at least two ducts to furnish natural or mechanical sup-ply and exhaust ventilation. One duct shall extend to a point near the bottom of the compartment, so installed that the ordinary collection of water in the bilge will not trap the duct. Where forced ventilation is installed, the duct extending near the bottom shall be the exhaust. The total inlet area and the total outlet area of ventilation ducts shall each be not less than one square inch for each foot of beam of the vessel. These minimum areas shall be in-creased as necessary when such ducts are considered as part of the air supply to the engines. One of the two Stbd engine room intakes was decommissioned by blanking off with a piece of wood due to the vent being damaged. Restore this stbd engine intake back to original to the satisfaction of the attending marine inspector.
46 182.20-45(c)
Old "T"
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 March 2026
Resolved 11 March 2026
Resolution: Received proofs of def rectification.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 2 June 2025
Resolved
All vessels must have navigation lights that are in compliance with the applicable sections of the Navigation Rules. Vessel did not have operational anchor light. Provide navigation lights that are in compliance with the Navigation Rules.
46 CFR 183.420
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 June 2025
Resolution: Anchor light added to vessel.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 2 June 2025
Resolved
A visual indicator must be provided at the operating station to indicate when any automatic bilge pump is operating. Bilge pump visual indicators did not turn on when pump was active.
46 CFR 182.530(c)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 June 2025
Resolution: Bilge pump operational indicator repaired.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 2 June 2025
Resolved
Each life jacket must be marked with Type I retroreflective material approved in 46 CFR 164.018. Nine life jackets were not marked with appropriate retroreflective material. Provide appropriate markings to the satisfaction of the attending marine inspector. Passenger count reduced to 41.
46 CFR 185.604
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 June 2025
Resolved 5 June 2025
Resolution: Retroreflective tape added over existing tape.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 2 June 2025
Resolved
Machinery and fuel tank spaces must be separated by boundaries that prevent the passage of vapors. Penetrations in stbd deck, existing vent openings both sides, and port aft bulkhead allow passage of vapors. Provide a proper seal to prevent the passage of vapors.
46 CFR 177.405
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 June 2025
Resolved 9 July 2025
Resolution: Machinery space sealed to prevent pasage of vapors.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 2 June 2025
Resolved
Except as otherwise provided in this section, rails or equivalent protection shall be installed near the periphery of all weather decks accessible to passengers and crew. Stanchion on port forward deck rail is loose at deck mounting. Secure stanchion deck mounting point.
46 CFR 177.35-1(a)
OLD T
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 June 2025
Resolved 1 July 2025
Resolution: Stanchion mounting secured at deck.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 2 June 2025
Resolved
Each vessel inspected and certificated under the provisions of this subchapter must, when any passengers are aboard during the tenure of the certificate, be in full compliance with the terms of the certificate. Vessel's required deckhand enters the water during in water snorkeling activities and the vessels AED pads are expired IAW Work Instruction 31. Replace AED pads IAW Work Instruction 31.
46 CFR 176.100(b)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 June 2025
Resolved 1 July 2025
Resolution: Valid AED pads on board.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 2 June 2025
Resolved
The name of the vessel must be marked on some clearly visible exterior part of the port and starboard bow and the stern of the vessel. The markings required by this section, which may be made by the use of any means and materials which result in durable markings, must be made in clearly legible letters of the Latin alphabet or Arabic or Roman numerals not less than four inches in height. Vessel's name and hailing port markings are less than four inches. Replace with markings of appropriate size.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 1 July 2025
Resolution: Name and hailing port lettering replaced with acceptable size.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 2 June 2025
Resolved
Fuel filter and strainer bowls must be highly resistant to shattering due to mechanical impact and resistant to failure due to thermal shock. Fuel filters fitted with bowls of other than steel construction must be approved by the Commandant and be protected from mechanical damage. Approval of bowls of other than steel construction will specify if a flame shield is required. Installed secondary port and stbd main engine fuel filters not an approved type. Replace with approved fuel filter.
46 CFR 182.455(b)(6)
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 5 June 2025
Resolution: Fuel filter replaced to acceptable type.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 2 June 2025
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 1 July 2025
Resolution: Evidence of training provided to MI.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 2 June 2025
Resolved
Drug testing programs required by this part must be conducted in accordance with 49 CFR part 40, Procedures for Transportation Workplace Testing Programs. Marine employer is DER and enrolled in the company's random testing program. A person subject to testing cannot receive their random selection notice and still meet the definition of “unannounced” as it pertains to random tests. Resolve by providing documentation on how the random testing process will work for the owner to the satisfaction of the attending MI.
46 CFR 16.113(a)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 1 July 2025
Resolution: Random testing progam documentation provided.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 2 June 2025
Resolved
Drug testing programs required by this part must be conducted in accordance with 49 CFR part 40, Procedures for Transportation Workplace Testing Programs. Vessel shares crew with another company, and no crew sharing agreement is in place. Provide evidence of crew sharing agreement to attending MI.
46 CFR 16.113(a)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 1 July 2025
Resolution: Shared crewmember no longer employed by vessel.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 2 June 2025
Resolved
A submersible electric bilge pump may be used as a power bilge pump provided that the pump is listed by an independent laboratory as meeting the requirements in UL 1113. Vessel was unable to prove that installed submersible electric bilge pumps are UL 1113 rated. Provide evidence of existing pump UL 1113 rating, or replace with approved bilge pumps.
46 CFR 182.520(e)(1)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 5 June 2025
Resolution: UL rated bilge pump installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 2 June 2025
Resolved
Vessels constructed of wood must provide bilge level alarms in all watertight compartments. Vessel did not have bilge level alarm in port forward space. Install bilge level alarm in port forward space.
46 CFR 182.530(b)
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 July 2025
Resolved 1 July 2025
Resolution: Alarm provided in port forward space.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 21 May 2024
Resolved
Suitable covers, guards, or rails shall be installed in a way of all exposed and hazardous places such as gears, machinery, etc. Port and Starboard Main Diesel Engines do not have guards over serpentine belts.
46 CFR 177.35-15 (a)
(Old T)
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 10 June 2024
Resolution: POC fabricated a guard and installed it in front of the serpentine belts on both engines.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 21 May 2024
Resolved
Each child size life jacket must be stowed in a location that is appropriately marked and separated from adult life jackets so the child size life jackets are not mistaken for adult life jackets. Number of child size life jackets are marked incorrectly.
46 CFR 180.78 (a) (5)
Condition: Invalid
Action required: 705 - Other - as specified
Resolved 10 June 2024
Resolution: POC installed a new life jacket placard with the proper number of child sized life jackets.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 21 May 2024
Resolved
A pre-engineered fixed gas fire extinguishing system must: Be installed in accordance with the manufacturer's instructions. Cable run between port and stbd engine room and port and stbd aft lazarette not properly sealed, allowing fixed fire extinguishing medium to communicate through bulkhead. Make vapor tight to ensure quantity of extinguisher is sufficient.
46 CFR 181.420 (a) (4)
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 10 June 2024
Resolution: POC used foam to seal up open cable penetrations in engine room.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 21 May 2024
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 10 June 2024
Resolution: POC had on board new pediatric pads for the AED.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 21 May 2024
Resolved
On a vessel of at least 7.9 meters (26 feet) in length, a visual and audible alarm must be provided at the operating station to indicate a high water level in each of the following normally unmanned spaces: A machinery space bilge, bilge well, shaft alley bilge, or other spaces subject to flooding from sea water piping within the space. Forward port compartment high bilge alarm inoperable.
46 CFR 182.530 (a)
Action required: 10 - Deficiency Rectified
Due 21 May 2024
Resolved 21 May 2024
Resolution: POC installed new high water bilge alarm. Alarms operated properly.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 8 March 2022
Resolved
Marine employers shall establish programs for the chemical testing for dangerous drugs on a random basis of crewmembers on inspected vessels who occupy a position or perform the duties and functions of a position, required by the vessel's COI. Marine employers may form or otherwise use sponsoring organizations, or may use contractors to conduct the random chemical testing programs. Vessel's consortium enrollment paperwork outdated and missing pre-employment drug testing.
46 CFR 16.230(a)
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 22 March 2022
Resolution: Received email from vessel owner with a copy of the Confirmation of Enrollment for their DAPI program. Cleared corresponding CG-835.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 8 March 2022
Resolved
Each item of lifesaving equipment determined by the marine inspector to not be in serviceable condition must be repaired or replaced. Vessel's life ring buoy reflective tape is worn. Replace life ring buoy reflective tape. 46 CFR 176.808(b)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 March 2022
Resolved 31 March 2022
Resolution: Life ring buoy reflective tape renewed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 8 March 2022
Resolved
An adult life jacket must be provided for each person carried on board a vessel. Vessel had 7 life jackets not in serviceable condition. Vessel is restricted to 43 persons total due to lack of properly outfitted life jackets. 46 CFR 180.71
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 March 2022
Resolved 31 March 2022
Resolution: 7 new life jackets were provided and properly outfitted. Vessel has 52 adult life jackets on board.
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 8 March 2022
Resolved
Vessels operated solely within 20 nautical miles of land must be equipped with a VHF-DSC radiotelephone installation meeting the requirements of § 80.1101(c)(2). VHF radio missing correct MMSI for DSC operation. Update MMSI number in accordance with FCC Radio Station Authorization certificate. 47 CFR 80.905
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 March 2022
Resolved 31 March 2022
Resolution: MMSI number was programmed into the VHF-DSC radio.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 8 March 2022
Resolved
Inspect all railings and bulwarks and their attachment to the hull structure. Two fractured welds on fwd upper stanchions for the canopy. Two fractured welds on the port and stbd passenger seating stanchions. Scarf and reweld fractures to the satisfaction of Marine Inspector. 46 CFR 176.25-10
Old-T
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 March 2022
Resolved 31 March 2022
Resolution: Welds satisfactorily repaired.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 8 March 2022
Resolved
In general, compliance with the standards established by a recognized classification society will be considered satisfactory evidence of the structural adequacy of a vessel. The vessel has a fracture where the transverse frame meets the inboard bulkhead in the aft portion of the engine compartment and at the transverse frame that meets the outboard bulkhead in the battery compartment. Submit a repair proposal to be reviewed and approved by the attending USCG Marine Inspector. 46 CFR 177.10-1(a)
Old-T
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 March 2022
Resolved 31 March 2022
Resolution: The fracture was gouged, scarfed and filled with Knytex and West systems epoxy. Additionally, the transverse frame was provided with a sister. Repair complete.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 28 December 2020
Resolved
Provision shall be made for closing all supply duct cowls or scoops and exhaust duct discharge openings for a space protected by a fixed gas extinguishing system. All closure devices must be readily available and mounted in the vicinity of the vent. Vessel has no means of securing intake or exhaust ventilation.
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed ventilation closures.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 28 December 2020
Resolved
A pre-engineered fixed gas fire extinguishing system must be installed in accordance with the manufacturer's instructions. Holes in the forward engine room bulkhead on the port side and free communication between the port and starboard hulls allow the fixed fire extinguishing medium to communicate outside the space it is intended to protect. Submit repair proposal to be approved by the attending USCG marine inspector.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed bulkheads to seal both engine compartments.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 December 2020
Resolved
The COI issued to a vessel describes the vessels minimum manning requirements and any equivalences accepted or authorized by the cognizant OCMI. The vessels Master does not hold a valid MMC. Vessel is required to be operated by, and shall not operate without, a Master holding a valid MMC with applicable endorsements.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 March 2021
Resolution: Attended vessel and witnessed valid MMC
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 28 December 2020
Resolved
Each item of lifesaving equipment determined by the marine inspector to not be in serviceable condition must be repaired or replaced. All 5 of the required child size PFDs and 11 of the adult size life jackets are deteriorated and shall be replaced. The vessel is not to carry any children or more than 35 adult passengers until these PFDs are replaced.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 4 March 2021
Resolution: Attended vessel and witnessed new child size life jackets
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 December 2020
Resolved
Employers must maintain records of chemical tests as provided in 49 CFR 40.333 and must make these records available to Coast Guard officials upon request. These records shall identify the total number of individuals chemically tested annually for dangerous drugs in each of the categories of testing required by this part including the annual number of individuals failing chemical tests and the number and types of drugs for which individuals tested positive. Vessel was unable to provide a report for total number of employees tested.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 4 March 2021
Resolution: Attended vessel and witnessed valid DAPI program documentation.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 28 December 2020
Resolved
As appropriate for intended voyage, a vessel must carry adequate and up-to-date charts. Vessels charts have not been corrected since 2006.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed new charts.
14 - Pollution Prevention › 145 - MARPOL Annex V › Placards
Issued 28 December 2020
Resolved
The master shall ensure that one or more placards meeting the requirements of this section are displayed in prominent locations. Garbage placard is missing.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed new garbage placard.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 28 December 2020
Resolved
Except as otherwise allowed by this subpart, a vessel must comply with the structural design requirements of one of the standards listed below for the hull material of the vessel. Vessel has areas of angel hair wood rot in compartment aft of the starboard rudder. Remove loose angel hair to facilitate further inspection and submit repair proposal to be approved by attending USCG inspector.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed removed wood rot. Area inspected satisfactory.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 28 December 2020
Resolved
Vessel must be provided with satisfactory arrangement for draining any watertight compartment. Vessel was unable to demonstrate operation of the starboard fixed hand pump.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed functional test of starboard bilge pump.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 28 December 2020
Resolved
The cognizant OCMI may require that a vessel and its equipment undergo any additional test or inspection deemed reasonable and necessary to determine that the vessel and its equipment are suitable for the service in which they are to be employed. Vessel does not have an AED on board as required by Work Instruction 31. Operations under Work Instruction 31 are not to be carried out until an AED is on board the vessel.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 4 March 2021
Resolution: AED verified on baord by attending MI.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 28 December 2020
Resolved
In systems and applications where flexible hoses are permitted to be clamped: Double hose clamping is required where practicable. Missing double hose clamps on stbd MDE oil filter hose.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 4 March 2021
Resolution: Attended vessel and witnessed double hose clamps installed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 December 2020
Resolved
Remote fuel shutoff stations must be marked in clearly legible letters at least 1 inch high indicating purpose of the valve and direction of operation. Vessels remote fuel shutoff station not labeled.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed markings for emergancy fuel shutoffs.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 28 December 2020
Resolved
Each connection to a conductor must be made within an enclosure and have a proper connection. The positive DC cable for the starboard main diesel engine was secured with an improper conductor. Secure the cable in an enclosure with an approved conductor.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed terminal block.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 December 2020
Resolved
Electrical equipment on a vessel must be installed and maintained to provide services necessary for safety under normal and emergency conditions. The electrical connector controlling the port engine is damaged and shall be repaired to prevent loss of connection.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed electrical connectors.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 December 2020
Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. MI observed a temporary repair to the stbd MDE heat exchanger and determined there to be a leak at this location. Submit repair proposal to the satisfaction of attending inspector.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed heat exchanger.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 28 December 2020
Resolved
Vessel required to have one 20" or 24" ring lifebuoy fitted with 60' lifeline and floating water light attached with a corrosion resistant clip to allow quick disconnect. Ring lifebuoy’s water light no longer in serviceable condition. Provide proper serviceable water light.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed float light.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 28 December 2020
Resolved
A hatch cover must have securing devices and be attached to the hatch frame or coaming by hinges, captive chains, or other devices of substantial strength to prevent its loss. The lever securing the hatch cover on the port forward compartment is inoperable and shall be repaired.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed closure devices.
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 28 December 2020
Resolved
The discharge ends of fuel tank vent pipes must be fitted with removable flame screens or flame arresters. The flame screens must consist of a single screen of corrosion resistant wire of at least 30 × 30 mesh. The port and starboard fuel tank vents do not have the correct size flame screens installed.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed flame screens.
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 28 December 2020
Resolved
Where a flexible fill pipe section is necessary, suitable flexible tubing or hose having high resistance to salt water, petroleum oils, heat and vibration, may be used. When the flexible section is a nonconductor of electricity, the metallic sections of the fill pipe separated thereby must be joined by a conductor for protection against generation of a static charge when filling with fuel. The fuel fill hose on the port side is missing the required bonding wire.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 January 2021
Resolved 24 February 2021
Resolution: Attended vessel and witnessed installed bonding wires.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 22 July 2020
Resolved
The owner or managing operator shall make a vessel available for drydock examination. Vessel is overdue for a credit drydock.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 31 October 2020
Resolved 4 March 2021
Resolution: Vsl is overdue for drydock and operating due to no tourism and due to COVID pandemic. Vsl currently has 28 Oct 2020 for drydock. Earliest at Keehi Marine Center and waiting to hear from Phoenician.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 October 2019
Resolved
Independent fuel tanks must be designed and constructed as described in this paragraph (a). Aluminum diesel fuel tank has a hole on the weld due to corrosion.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 November 2019
Resolved 11 December 2019
Resolution: New tanks installed.
01 - Certificates & Documentation › 012 - Crew Certificates › Medical certificate
Issued 25 September 2019
Resolved
Each officer employed on any vessel subject this subchapter must have his or her license onboard and available for examination at all times when the vessel is operating. Vsl master did not have a medical certificate. Provide a current medical certificate.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 10 October 2019
Resolution: Provided valid medical certificate
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 25 September 2019
Resolved
An adult life jacket must be provided for each person carried on board a vessel. Vessel is restricted to 19 persons total due to lack of properly outfitted lifejackets. 16 L/J did not have required retroreflective tapes, 8 L/J were still inside the original packaging with no vessel name, and 7 were unservicable due to damages.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 10 October 2019
Resolution: Vsl provided required and compliant adult lifejackets.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 25 September 2019
Resolved
Child size life jackets equal to 10% of the number of persons permitted on board must be provided. Vessel needs provide required number of child size life jackets due to not being servicable.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 10 October 2019
Resolution: Vessel provided 5 lifejackets.
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 25 September 2019
Resolved
essels operated solely within 20 nautical miles of land must be equipped with a VHF-DSC radiotelephone installation meeting the requirements of § 80.1101(c)(2). VHF radio missing MMSI and LAT/LONG for DSC operation.
Condition: Placed in Improper Service
Action required: 701 - Prior to carriage of passengers/cargo
Due 17 October 2019
Resolved 11 October 2019
Resolution: Vessel has MMSI input but the LAT/Long input is not working
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 25 September 2019
Resolved
Every vessel must be
fitted with a suitable magnetic compass designed for
marine use, compass must be illuminated or restricted to
daytime operation. No light for the compass.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 10 October 2019
Resolution: Provided new magnetic compass with light.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 25 September 2019
Resolved
A visual and audible alarm must be provided at the operating station to indicate a high water level in each of the following normally unmanned spaces. Stbd aft bilge alarm light is not operational.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 10 October 2019
Resolution: Visual high bilge level alarm tested satisfactorily
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 25 September 2019
Resolved
A means to reset devices used to automatically shut down ventilation systems and engines. Stbd engine room Fireboy fixed system override switch does not operated as designed. To start the engine, override switch must be pressed during the engine start. The engine should start without holding the override switch.
Condition: Placed in Improper Service
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 October 2019
Resolved 10 October 2019
Resolution: Tested satisfactorily.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 25 September 2019
Resolved
Deck rails must be designed and constructed to withstand a point load of 91 kilograms (200 pounds) applied at any point in any direction, and a uniform load of 74 kilograms per meter (50 pounds per foot) applied to the top rail in any direction. Repair a fracture at the base of bow center stanchion.
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 11 October 2019
Resolution: Forward rail stanchion was rewelded.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 25 September 2019
Resolved
A hatch cover must have securing devices and be attached to the hatch frame or coaming by hinges, captive chains, or other devices of substantial strength to prevent its loss.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 October 2019
Resolved 10 October 2019
Resolution: Manhole access covers has lines attached.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 25 September 2019
Resolved
Provide repair proposals for stbd fwd compartment with a diagonal longitudinal member with multiple location wood rot, below the hatch coaming facing forward wood rot.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 10 October 2019
Resolution: Repair completed per approved proposal.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 25 September 2019
Resolved
Provide repair proposals for port fwd compartment with a longitudinal stringer penetrating fwd bulkhead with multiple wood rot locations.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 10 October 2019
Resolution: Repairs completed per approved proposal.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 25 September 2019
Resolved
Nozzle, flanges, or other fittings for pipe connections to a metal tank must be welded or brazed to the tank. Properly install fuel return line to fuel tank for both port and stbd fuel tanks.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 11 December 2019
Resolution: Port fuel tank has hole on the weld due to corrosion and the fittings for supply and return are not welded or brazed at the tope of fuel tank.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 27 September 2018
Resolved
A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have a light to indicate discharge; Starboard visual indicator for FireBoy does not activate to indicate discharge. Repair visual indicator.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2018
Resolution: Proper operation of visual indicator was verified by attending MI
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 27 September 2018
Resolved
At least one ring life buoy must be fitted with a lifeline; Lifeline on ring buoy is wasted. Replace lifeline on ring buoy.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2018
Resolution: Verified lifeline was replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 27 September 2018
Resolved
An adult life jacket must be provided for each person carried on board a vessel; Vessel has 42 out of required 50 life jackets. Replace wasted life jackets. Total persons allowed on board reduced to 42 persons.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 October 2018
Resolved 4 December 2018
Resolution: Vessel purchased 8 new lifejackets.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 27 September 2018
Resolved
Each hydrostatic release unit, other than a disposable unit, must be service within 12 months of its manufacture and within 12 month of each subsequent servicing; Hydrostatic release unit has not been serviced since 2017. Replace hydrostatic release unit for EPIRB.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2018
Resolution: Verified Hydorstatic release unit was replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 27 September 2018
Resolved
Each ring life buoy must be marked in clearly legible block capital letters with the vessel's name; The markings on the vessel's ring life buoy are no longer legible. Add vessel's name to ring life buoy iaw 46 CFR 185.604.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 26 October 2018
Resolution: Verified new, legible markings replaced previous markings.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 27 September 2018
Resolved
When the operator is on duty and in charge of transmitting systems, or performing service, maintenance or inspection functions, the license or permit document, or a photocopy thereof, or a copy of the application and PPC(s) received by the FCC, must be posted or in the operator's personal possession, and available for inspection; Operators permit was not available on board vessel. Provide operators permit for inspection.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 October 2018
Resolved 4 December 2018
Resolution: Vessel emailed copy of FCC Radio Operators Permit.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 27 September 2018
Resolved
Repair rotted stringers in port and starboard aft compartments. Submit repair proposal for Coast Guard approval prior to commencing repair.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 13 November 2018
Resolution: Repair was completed and verified by attending MI.
Operations/Management › Drug and Alcohol Testing › Testing, Random
Issued 28 October 2017
Resolved
Provide proof that 50% of the number of covered employees were selected for random urinalysis. 46 CFR 16.230.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 February 2018
Resolved 15 February 2018
Operations/Management › Drug and Alcohol Testing › MIS Submission
Issued 28 October 2017
Resolved
Provide proof of MIS filing for 2016 IAW 46 CFR 16.500
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 2 December 2017
Resolved 31 January 2018
Resolution: Provided proof of MIS filing.
Operations/Management › Drug and Alcohol Testing › Recordkeeping
Issued 28 October 2017
Resolved
Provide proof of identification of designated employee representative (DEP) who is not also a covered employee IAW 49 CFR 40.3
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 February 2018
Resolved 14 February 2018
Resolution: Company provided proof of the Designated employee representative.
Operations/Management › Drug and Alcohol Testing › Collection Sites
Issued 28 October 2017
Resolved
Provide proof of 24/7 availability of drug/alcohol testing collection site IAW 46 CFR 4.06
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 February 2018
Resolved 15 February 2018
Resolution: Operator provided proof of collection site availability IAW 46 CFR 4.06.
Engineering › Fuel Oil Storage/Transfer System › Valve
Issued 24 August 2017
Resolved
Repair remote fuel shutoff valve.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 8 September 2017
Resolved 5 September 2017
Resolution: Renewed fuel shut off valve IAW 46 CFR 182.455(b)(4).
Engineering › Fuel Oil Service System › Filter
Issued 24 August 2017
Resolved
Install drip pan on fuel filter.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 8 September 2017
Resolved 5 September 2017
Resolution: Recieved photo evidence of fuel pan.
Electrical › Electrical Distribution System (service) › Cable
Issued 24 August 2017
Resolved
Install metal support on electrical cabling located in Port Engine Space IAW 46 CFR 183.340(b)(4).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 8 September 2017
Resolved 5 September 2017
Resolution: Recieved photo evidence of metal brackets.
Communications › Radio Communications › EPIRB
Issued 24 August 2017
Resolved
Log EPIRB tests.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 August 2017
Resolved 24 August 2017
Resolution: Logged EPIRB Testing IAW 46 CFR 185.728.
Personnel › Manning/Qualifications › Medical Fitness
Issued 24 August 2017
Resolved
Complete DAPI Audit IAW 46 CFR 16.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 September 2017
Resolved 2 November 2017
Resolution: Conducted DAPI Audit. Issued 04 defs. See activity 6296544. Vessel given 30 days to become compliant
Operations/Management › Drug and Alcohol Testing › Testing, Equipment
Issued 12 October 2016
Resolved
Alcohol test kits not onboard due to being expired. Provide new un-expired alochol test strips. 46CFR16.240
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 October 2016
Resolution: new test kits onboard
Operations/Management › Drug and Alcohol Testing › Recordkeeping
Issued 12 October 2016
Resolved
Company policy statement not onbaord. Place policy statement onboard per 46 CFR 16.401
Condition: Invalid
Due 26 October 2016
Resolved 26 October 2016
Resolution: policy placed onboard.
Lifesaving › Lifejacket/PFD (Type I) › Condition
Issued 12 October 2016
Resolved
02 lifejackets not serviceable, provide 02 lifejackets for inspection. Passenger count limited to 44 until lifejackets replaced as new.
Condition: Invalid
Due 26 October 2016
Resolved 26 October 2016
Resolution: 02 new lifejackets purchased and placed onboard.
Navigation › Piloting/Steering › Local Notices to Mariners
Issued 12 October 2016
Resolved
Up to date charts and or new notice to mariners need to be placed onboard in addition to current coast pilot and light list. 46 CFR 184.420
Condition: Invalid
Due 26 October 2016
Resolved 26 October 2016
Resolution: Updated notice to mariners, coast pilot and light list placed onboard.
Communications › Public Address System › Announcing Station
Issued 12 October 2016
Resolved
Emergency broadcast placard illegible, replace as new. 46CFR184.506
Condition: Invalid
Due 26 October 2016
Resolved 26 October 2016
Resolution: New laminated Emergency Broadcast Placard placed onboard at console.
Documentation › Certificates/Documents › FCC Safety Radiotelephony Certificate
Issued 12 October 2016
Resolved
Safety certificate expired 06OCT16. Renew and provide proof to Marine Inspector. Operators permit also required to be provided to Marine Inspector. 47CFR13
Condition: Invalid
Due 12 November 2016
Resolved 26 October 2016
Resolution: New FCC Safety license onboard.
Electrical › Electrical Distribution System (service) › Outlet Box
Issued 12 October 2016
Resolved
Remove all plastic boxes in interior spaces that enclose electrical wiring/connections.
Condition: Invalid
Due 19 October 2016
Resolved 26 October 2016
Resolution: Plastic boxes replaced w/ heavy duty waterproof outlets.
Construction/Loadline › Structures › Machinery Space Opening
Issued 12 October 2016
Resolved
Fwd of port amidships hatch in machinery space, a pipe drain fitting contains an unknown liquid. Identify liguid and dispose of properly and cap off fitting to the satisfaction of attending marine inspector.
Condition: Invalid
Due 12 November 2016
Resolved 26 October 2016
Resolution: pipe drain fitting capped off.
Construction/Loadline › Hull › Longitudinal Frame
Issued 29 June 2016
Resolved
Repair cracked frame for Port Hull engine access opening at next drydock due 31 Jul 18 IAW 46 CFR 177.300
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 July 2018
Resolved 1 June 2018
Resolution: Def cleared