SILVER WHISPER

SILVER WHISPER is a 2001 passenger vessel (inspected). The Coast Guard has recorded 19 inspections since 2016, most recently in July 2026, along with 24 deficiencies and 1 operational control.

Records from 2016 to 2026. Most recent: inspection, 17 July 2026.

Built
2001
Last inspected
17 July 2026
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 17 July 2026
…with no type recorded3
Operational controls None recorded without a removal date
Years with a record 8 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9192179
Flag
BAHAMAS, THE
Maury page id
psix-30799

Documentation record

Tonnage as PSIX records it28258 - Convention (Subpart B), Gross Ton
9144 - Convention (Subpart B), Net Ton
15728 - Displacement, Ton
3390 - Dead Weight, Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 19

17 July 2026 PSC B
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8440682
27 May 2026 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8382237
21 May 2026 Administrative Inspection
Administrative · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 8377934
21 May 2026 Deficiency Check
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 8382125
18 May 2026 PSC A · COC-CVE Annual
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 8381294
7 September 2023 COC-CVE Annual · PSC A
Physical examination · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 7785672
18 May 2023 PSC B · COC-CVE Quarterly
Physical examination · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 7687018
19 September 2022 PSC A · Deficiency Check · COC-CVE Annual
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7558712
2 December 2021 Administrative Inspection
Administrative · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 7361295
17 November 2021 COC-CVE Annual
Administrative · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 7352130
25 October 2021 Type not recorded
No type recorded · USCG Southeast District (dp) · USCG Southeast District (CGD-SE) · Activity 7339534
16 October 2019 Deficiency Check
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6835486
9 October 2019 COC-CVE Annual · Ballast Water Examination · ISPS III Exam
Physical examination · Sector Boston · USCG Northeast District (CGD-NE) · Activity 6824246
4 November 2018 Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6574007
31 October 2018 ISPS III Exam · COC-CVE Annual · Ballast Water Examination
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6574025
30 October 2018 Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6570941
14 October 2017 Administrative Inspection
Administrative · Marine Safety Unit Belfast · USCG Northeast District (CGD-NE) · Activity 6294197
16 September 2017 COC-CVE Annual · Ballast Water Examination · MARPOL Annex V Examination · MARPOL Annex VI Survey · ISPS II Exam · MARPOL Annex I Examination
Physical examination · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 6264110
30 September 2016 Ballast Water Examination · PII Safety Exam · ISPS II Exam · COC-CVE Annual
Physical examination · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 5999891

Deficiency record · 24

07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 18 May 2026 Resolved
The arrangements for the storage, distribution and utilization of oil used shall be such as to ensure the safety of the ship and persons onboard. PSCO observed three remote quick-closing valves did not operate upon activation. 74 SOLAS 01 II-2/15.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 May 2026
Resolution: PSCO observed acctuation of valves; all sat.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 18 May 2026 Resolved
Stairway enclosures shall have direct access to the corridors and be of a sufficient area to prevent congestion, having in view the number of persons likely to use them in an emergency. Within the perimeter of such stairway enclosures, only public toilets. lockers of non-combustible material providing storage for safety equipment and open information counters are permitted. Only public areas, corridors, public toilets. special category spaces, other escape stairways required by regulation 28.1.5 and external areas are permitted to have direct access to these stairway enclosures. PSCO observed unaffixed table and chairs in aft stairwell on deck four and table with alcohol on deck seven. 74 SOLAS 01 II-2/29.2
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 May 2026
Resolution: Cleared by class; all sat.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 18 May 2026 Resolved
Doorways and corridors and intermediate landings included in the means of escape shall be sized in the same manner as stairways. Shall not be less than 900 mm in clear width, the minimum clear width shall be increased by 10 mm for every one person provided for in excess of 90 persons. PSCO observed escape route obstructed by piano in theatre. 74 SOLAS 01 II-2/28.1.5.3
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 May 2026
Resolution: PSCO observed item moved; all sat.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 May 2026 Resolved
Fire doors in main vertical zone bulkheads and stairway enclosures shall satisfy the following requirements: The doors shall be self-closing and be capable of closing against an angle of inclination of up to 35 degrees opposing closure. PSCO observed fire doors A60 6.205 and A0 9.254 did not self-close. 74 SOLAS 01 II-2/30.4.1
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 May 2026
Resolution: Cleared by class; all sat.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 May 2026 Resolved
Fire doors in main vertical zone bulkheads, galley boundaries and stairway enclosures, other than power operated watertight doors and those which are normally locked, shall satisfy the following requirement: the approximate time of closure for hinged fire doors shall be no more than 40 s and no less than 10 s from the beginning of their movement with the ship in the upright position. The approximate uniform rate of closure for sliding fire doors shall be of no more that 0.2 m/s and lo less than 0.1 m/s with the ship in the upright position. PSCO observed fire doors A60 9.258, A0 9.254, A04.137, A01.1, and the door from ECR to ER did not self-close within allotted time frame. 74 SOLAS 01 II-2/30.4.2
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 27 May 2026
Resolution: Cleared by class; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance and inspections
Issued 18 May 2026 Resolved
Maintenance, testing and inspections of life-saving appliances shall be carried out in a manner having due regard to ensuring reliability of such appliances. PSCO observed starboard sides of lifeboats 5 and 6 being damaged with exposed FRP and evident delamination. Maintenance records do not reflect proper repair work completed. 74 SOLAS 20 III/20.3.1
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 27 May 2026
Resolution: Cleared by class; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 18 May 2023 Resolved
Every crew member with assigned emergency duties shall be familiar with these duties before the voyage begins. Crew member was unfamiliar with who the ship’s security officer was, and the procedures to following for a security incident. 74 SOLAS 20 III/19.2.1 (16c)
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 June 2023
Resolved 24 May 2023
Resolution: Vessel provided training, logs and photos conducted with crew to rectify deficiency and provide more throrough security training. Evidence uploaded into documents.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 May 2023 Resolved
Openings shall be provided with permanently attached means of closing which shall be at least as effective for resisting fires as the divisions in which they are fitted. FSD A0 4.120 was found to not fully close and latch. 74 SOLAS 01 II-2/30.1 (10c)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 18 May 2023
Resolved 18 May 2023
Resolution: FSD adjusted to close and latch.
07 - Fire Safety › N/A - No Subsystem › Personal equipment for fire safety
Issued 18 May 2023 Resolved
Fireman’s outfit shall consist of personal equipment comprising protective clothing of material to protect the skin from the heat radiating from the fire and from burns and scalding by steam. The outer surface shall be water-resistant. Fireman’s flash gear found with hole in it. 74 SOLAS 01 II-2/17.1.1.1 (10c)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 18 May 2023
Resolved 18 May 2023
Resolution: Flash gear removed from service and replaced
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 18 May 2023 Resolved
Only public toilets, lifts, lockers of non-combustible materials providing storage for safety equipment and open information counters may be located within the stairway enclosure boundaries. Nonafixed trashcans were located on ever deck of the cat 2 stairway. 74 SOLAS 01 II-2/41-2.4.4 (10c)
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 18 May 2023
Resolved 18 May 2023
Resolution: Items removed from space
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 19 September 2022 Resolved
The minimum integrity of all bulkheads and decks shall be as prescribed in tables 26.1 and 26.2. Foud 03 holes, deck thinning and excessive scale in an A)0 deck in the A/C Space (category 10). The A/C space is above the purifier room and evaporator room (category 12) 74SOLAS(01) II-2/26.1
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 19 September 2022
Resolution: Received and reviewed Class Survey attesting to the temporary repairs made to the deck. See attached
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 September 2022 Resolved
The construction of all doors and door frames in "A" class divisions, with the means of securing them when closed, shall be resistance to fires as well as to the passage of smoke and flam. Daylight can be seen trough EDG room door gasket. 74SOLAS(01) II-2/30.2
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 19 September 2022
Resolution: Recieved and reviewed Class Report attesting to the repairs made to the door gasket in EDG room
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 19 September 2022 Resolved
The markings must enable passengers to idnetify all of the routes of escape and readily identify the escape exits. Escape exits in Panorama Lounge and Observation Deck were not marked. 74SOLAS(01) II-2/28
Condition: Design Flaw
Action required: 10 - Deficiency Rectified
Resolved 19 September 2022
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 17 November 2021 Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. A sprinkler head and its ampule located in a crew space corridor (adjacent to FSD5.162) had been painter over.
Action required: 10 - Deficiency Rectified
Due 17 November 2021
Resolved 17 November 2021
Resolution: The ampule was replaced by the ship's crew.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 November 2021 Resolved
Category 13 spaces are those where combustible materials can be used for storage. There was a substantial amount of air filters and cardboard boxes found within an A/C space and several other spaces (linen stores, paint locker, and boson stores) with combustible materials stored outside of the sprinkler system nozzle range.
Action required: 10 - Deficiency Rectified
Due 17 November 2021
Resolved 17 November 2021
Resolution: The combustible materials were removed from the space.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 17 November 2021 Resolved
Fire doors in "A" class divisions shall be self-closing. Fire screen door 5.162 would not self close after testing.
Action required: 10 - Deficiency Rectified
Due 17 November 2021
Resolved 17 November 2021
Resolution: Fire screen door 5.162 was adjusted to close as intended by the crew.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 17 November 2021 Resolved
Openings in "A" class divisions shall be provided with permanently attached means of closing which shall be at least as effective for resisting fires as the divisions in which they are fitted. Sliding fire screen doors 8.245 would not latch all the way and left a small gap at the closing point, door 7.227 would take too long to close (55 sec.) and door 5.477's safety bar would not work thus not reopening if an object was in its path.
Action required: 10 - Deficiency Rectified
Due 17 November 2021
Resolved 17 November 2021
Resolution: The fire screen doors were adjusted to meet requirements.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 17 November 2021 Resolved
Means of escape shall be marked by lighting or photoluminescent strip. There was a small section of low lighting of a about 3 feet on deck 9, at the boundary between MVZ 1 and 2 that was not illuminating.
Action required: 10 - Deficiency Rectified
Due 17 November 2021
Resolved 17 November 2021
Resolution: The vessel repaired the section of low level lighting that was not illuminating.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 9 October 2019 Resolved
Detectors shall be operated by heat, smoke or other products of combustion, flame or any combination of these factors. All detectors shall be of a type such that they can be tested for correct operation and restored to normal surveillance without the renewal of any component. PSCO observed no smoke detectors of the consillium type activate when tested. 74SOLAS(01) II-2/13.1.11 17(a)(c)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 9 October 2019
Resolved 9 October 2019
Resolution: Crew had spare detectors on board and replaced detectors that were faulty. PSCO's checked all consillium type detectors on deck 6 and 7, all worked satisfactory.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 9 October 2019 Resolved
The construction of all doors and door frames in "A" class divisions with the means of securing when closed, shall provide resistance to fire as well as the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. PSCO observed fire door 4.143 in the main galley is warped and doesn't provide A60 boundary. 74SOLAS(01) II-2/30.2 50(a)(c)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 October 2019
Resolved 16 October 2019
Resolution: Documentation was provided to attest that the deficiency was resolved.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 9 October 2019 Resolved
The minimum fire integrity of all bulkheads and decks shall be as prescribed in table 26.1. PSCO observed a hole cut out for cable penetration in the bulkhead between BOSN stores and a corridor. The penetration was not sealed. 74SLOAS(01) II-2/26.1 10(c)
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 9 October 2019
Resolved 9 October 2019
Resolution: Crew placed appropriated cable box in bulkhead.
07 - Fire Safety › N/A - No Subsystem › International shore-connection
Issued 9 October 2019 Resolved
At least one international shore connection shall be provided. The connection shall be kept aboard the ship with eight washers. PSCO observed the international shore connection was missing the washers. 74SOLAS(01) II-2/19.4 10(c)
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 9 October 2019
Resolved 9 October 2019
Resolution: Crew placed 08 washers with the international shore connection.
04 - Emergency Systems › N/A - No Subsystem › Low level lighting in corridors
Issued 31 October 2018 Resolved
Means of Escape shall be marked by lighting or photoluminescent strip. Marking must enable passengers to identify all routes of escape. PSCO observed areas throughout deck 3 that had various equipment stored in front of photoluminescent strip blocking the identification of escape routes. 74 SOLAS (01 cons) II-2/28.1.10
Condition: Invalid
Action required: 10 - Deficiency Rectified
Due 31 October 2018
Resolved 31 October 2018
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 31 October 2018 Resolved
"A" Class divisions are those divisions formed by bulkheads and decks that shall be constructed to be capable of preventing the passage of smoke and flame, PSCO observed that the roller shutter door creating the "A" class division on for the grill on deck 8 did not fully close. 74 SOLAS (01 cons0) II-2/3.3
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 November 2018
Resolved 20 November 2018
Resolution: Class report submitted for roller shutter stating it is working satisfactory