ALBION is a 1988 passenger vessel (inspected). The Coast Guard has recorded 50 inspections since 1988, most recently in April 2026, along with 40 deficiencies.

Records from 1988 to 2026. Most recent: inspection, 30 April 2026.

Built
1988
Last inspected
30 April 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WBZ8305
313007
Flag
UNITED STATES
367363710
Maury page id
psix-313007

Inspections, by type

…with no type recorded1
Years with a record 34 calendar years (1988–2026)
The 50 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)40.0 ft × 12.0 ft × 3.0 ft
Registered tonnagegross 6 / net 5
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderCORINTHIAN YACHTS · TARPON SPRINGS, FL, UNITED STATES · built 1988
Hull materialFRP (Fiberglass)
PropulsionGasoline Outboard
Hull shapeNot recorded
Hull configurationTwin Hull
Hailing portST PETE BEACH, FL
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 21 August 2026 · expires 31 August 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it5 - Simplified, Net Ton
6 - Simplified, Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WBZ8305MMSI 367363710 · active · compulsorily equipped · granted 19 July 2018, expires 15 September 2028
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.

Inspection history · 50

30 April 2026 Annual Inspection · Administrative Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8355430
30 April 2025 Annual Inspection · Deficiency Check
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8111214
12 September 2024 Internal Structural Exam · Hull Examination
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7977352
29 February 2024 Deficiency Check · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7850961
3 February 2023 Deficiency Check · COI Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7623916
22 September 2022 Hull Examination · Deficiency Check · Internal Structural Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7503886
3 February 2022 Deficiency Check · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7380351
1 February 2021 Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7121150
23 September 2020 Drydock Exam · Internal Structural Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 7032030
10 February 2020 Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6889956
14 January 2020 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6890326
11 February 2019 Administrative Inspection · Deficiency Check · DAPI Audit · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6610560
5 September 2018 Deficiency Check · Drydock Exam · Internal Structural Exam · Administrative Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6488994
12 February 2018 COI Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6345969
6 March 2017 Administrative Inspection · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6086218
30 August 2016 Hull Examination · Internal Structural Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 5986203
19 February 2016 DAPI Audit · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 5818405
8 May 2012 Annual Inspection · Administrative Inspection · DAPI Audit
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 4305507
14 September 2010 Administrative Inspection · Examination of Repairs · Hull Examination
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 3849105
28 July 2009 Simplified Stability Test · Administrative Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 3549312
16 July 2009 Administrative Inspection
Administrative · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 3547952
20 April 2009 Hull Examination · DAPI Audit · Internal Structural Exam · Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 3457992
16 April 2008 COI Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 3184076
17 April 2007 COI Inspection · Hull Examination
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 2905925
24 April 2006 Annual Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 2629350
3 May 2005 Hull Examination
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 2348073
18 April 2005 Annual Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 2334258
4 May 2004 Examination of Repairs · Hull Examination
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 2049141
26 April 2004 Annual Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 2048087
6 May 2002 Hull Examination · COI Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1605853
25 May 2001 Deficiency Check
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1063827
8 May 2001 Re-Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1462949
1 May 2000 Hull Examination · Re-Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1395458
14 May 1999 COI Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1386575
4 May 1998 Re-Inspection · Hull Examination
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1372294
21 April 1997 Re-Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1371771
30 May 1996 COI Inspection · Hull Examination
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1390304
17 July 1995 Re-Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 880777
16 June 1994 Deficiency Check
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1171346
14 June 1994 Re-Inspection · Hull Examination
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 962821
30 August 1993 Deficiency Check
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 827216
27 July 1993 COI Inspection
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1158983
23 June 1992 Re-Inspection · Hull Examination
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1254807
17 May 1991 COI Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 933880
23 January 1991 Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1303719
9 May 1990 Hull Examination · Re-Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 902920
19 May 1989 Re-Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 890000
9 February 1989 Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 891161
12 August 1988 Deficiency Check
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1346425
28 July 1988 Initial Certification · Hull Examination
Physical examination · MSO TAMPA · USCG Southeast District (CGD-SE) · Activity 1346298

Deficiency record · 40

10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 30 April 2025 Resolved
All vessels must have navigation lights that are in compliance with the applicable sections of the International and Inland Navigation Rules. Marine Inspector (MI) observed that the vessels anchor light is inoperable. Vessel restricted to daytime operations only. 46 CFR 183.420 705c
Action required: 705 - Other - as specified
Due 30 April 2025
Resolved 2 May 2025
Resolution: Vessel replaced bulb in anchor light. All sat.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 30 April 2025 Resolved
Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10. MI observed vessel did not have procedures in place to conduct and record monthly portable fire extinguisher inspections. 46 CFR 176.810(b)(1)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 May 2025
Resolved 2 May 2025
Resolution: Provided photo of new inspection logs for fire extinguishers and EPIRB.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 29 February 2024 Resolved
At each initial and subsequent inspection for certification of a vessel, the owner or managing operator shall be prepared to conduct tests and have the vessel ready for inspection of lifesaving equipment and systems. MI observed an inoperable float light. Vessel is restricted to daylight operation until fixed. 46 CFR 176.808
Action required: 705 - Other - as specified
Due 29 February 2024
Resolved 18 April 2024
Resolution: Vessel sent video of light working.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 29 February 2024 Resolved
A vessel must carry either a first-aid kit that meets the requirements in 46 CFR 199.175(b)(10) or a kit with equivalent contents and instructions. MI observed that first aid kit was expired. Vessel shall replace first aid kit. 46 CFR 184.710
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 March 2024
Resolved 6 March 2024
Resolution: Received proof of new first aid kit
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 29 February 2024 Resolved
The EPIRB test required by paragraph (a) shall be logged or otherwise documented, as applicable. Vessel was unable to provide proof of EPIRB testing. 46 CFR 184.710
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 March 2024
Resolved 29 February 2024
Resolution: Tested EPIRB on request.
11 - Life Saving Appliances › N/A - No Subsystem › Marine Evacuation System
Issued 29 February 2024 Resolved
All vessels certificated for exposed or partially protected waters service must have a suitable motor rescue boat, except when a motor lifeboat is provided or when, in the opinion of the Officer in Charge, Marine Inspection, the vessel is of such design and operating characteristics that the vessel itself provides a satisfactory man overboard rescue platform. MI Observed no rescue platform on the vessel with a 2.5 foot free board. Vessel should provide a proposal for rectification within 30 days, IAW the attached work instruction. 46 CFR 169.517
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 April 2024
Resolved 22 April 2024
Resolution: Vessels freeboard at the side access was measured to be 2'. No rescue platform is required as this meets the local MMS policy.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 3 February 2023 Resolved
Each vessel certificated to operate on a limited coastwise route within three miles of land in warm water must either comply with regulation 1 or 2 or have on board a FCC Type Accepted Category 1 406 MHz EPIRB, installed to automatically float free and activate, and not be required to carry survival craft. The EPIRB was found inoperable when tested and the hydro release was found expired. Vessel is restricted to LBS routes until rectified. 46 CFR 180.205
Action required: 705 - Other - as specified
Due 3 February 2023
Resolved 3 February 2023
Resolution: The operator purchased a new EPIRB, registered it with NOAA, and mounted it using a new hydro release.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 3 February 2023 Resolved
At least one ring life buoy must be fitted with a lifeline. If more than one ring life buoy is carried, at least one must not have a lifeline attached. Each lifeline on a ring life buoy must be of at least 18.3 meters (60 feet) in length. The lifeline found onboard measured 40' in length. 46 CFR 180.70
Action required: 705 - Other - as specified
Due 10 February 2023
Resolved 3 February 2023
Resolution: The operator purchased 60' of lifeline that matches the regulatory specs.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 3 February 2023 Resolved
A vessel on an oceans, coastwise, limited coastwise, or Great Lakes route must carry the amount of distress signals that comply with 46 CFR 180.68. The vessel operates on a LC route and had onboard 4 valid red hand flares. 46 CFR 180.68
Action required: 705 - Other - as specified
Due 3 February 2023
Resolved 3 February 2023
Resolution: The operator purchased eight red hand flares found to be valid.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 3 February 2023 Resolved
A vessel not required to have a power driven fire pump by § 181.300 must have at least three 9.5 liter (2 1/2 gallon) buckets, with an attached lanyard satisfactory to the cognizant OCMI, placed so as to be easily available during an emergency. The words “FIRE BUCKET” must be stenciled in a contrasting color on each bucket. The existing fire pump was found inoperable when tested. The operator elected to purchase 3 new fire buckets. 46 CFR 181.610
Action required: 705 - Other - as specified
Due 3 February 2023
Resolved 3 February 2023
Resolution: The operator purchased three new 2.5 gallon fire buckets and labelled them.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 3 February 2023 Resolved
The owner, managing operator, or a qualified servicing facility as applicable must conduct the following inspections and tests: (1) Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10. The portable fire extinguishers are due for inspection Feb 2023. 46 CFR 176.810
Action required: 705 - Other - as specified
Due 28 February 2023
Resolved 10 February 2023
Resolution: The operator contacted the MI and provided receipts for the third party inspection for portable fire extinguishers onboard the vessel.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 22 September 2022 Resolved
A hatch exposed to the weather must be watertight. The hatches that provide access to each hull of the catamaran are not watertight. 46 CFR 179.360(a)
Action required: 705 - Other - as specified
Due 22 September 2022
Resolved 25 October 2022
Resolution: MI completed inspection of work list item.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 22 September 2022 Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull. The fiberglass tabs holding the deck framing, and the bulkheads to the hull is separating in several areas within both the port and stbd hulls. 46 CFR 177.100
Action required: 705 - Other - as specified
Due 22 September 2022
Resolved 25 October 2022
Resolution: MI completed inspection of work list item.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 22 September 2022 Resolved
The weather deck on a flush deck vessel must be watertight. There is cracking on the port side aft deck near the rub rail. 46 CFR 178.410(a)
Action required: 705 - Other - as specified
Due 22 September 2022
Resolved 25 October 2022
Resolution: MI completed inspection of work list item.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 22 September 2022 Resolved
The weather deck on a flush deck vessel must be watertight. There is cracking on the STB side aft deck forward of the access hatch to the hull. 46 CFR 178.410(a)
Action required: 705 - Other - as specified
Due 22 September 2022
Resolved 25 October 2022
Resolution: MI completed inspection of work list item.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 3 February 2022 Resolved
A vessel must carry adequate and up-to-date charts of large enough scale to make safe navigation possible. Vessels chart were from 2016. 46 CFR 184.420(1) 16C
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 February 2022
Resolved 15 February 2022
Resolution: Vessel provided pictures and receipt of the new chart.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 3 February 2022 Resolved
Portable fire extinguisher must be inspected and maintained. 01 fire extinguisher was found not fully charged. 46 CFR 176.810(b)(1)
Action required: 10 - Deficiency Rectified
Due 3 February 2022
Resolved 3 February 2022
Resolution: Vessel replaced the fire extinguisher with a charged and currently serviced extinguisher.
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 11 February 2019 Resolved
A vessel must comply with applicable requirements for any radio installation. GPS and MMSI number not programmed into radio. 46 CFR 184.502
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 February 2019
Resolved 25 February 2019
Resolution: Verified GPS and MMSI numbers in radio.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 11 February 2019 Resolved
A submersible electric bilge pump may be used as a power bilge pump. A positive shutoff valve is installed at the hull penetration. Postive shutoff valves not installed on bilge pump discharge hose penetrating hull, port and starboard bilge pump. 46 CFR 182.520(e)(7)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 February 2019
Resolved 25 February 2019
Resolution: Verified installation of positive shutoff vavles.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 11 February 2019 Resolved
Batteries shall be secured against shifting with motion of boat. Battery boxes not secured from shifting. 46 CFR 183.05-20
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 February 2019
Resolved 25 February 2019
Resolution: Verified battery boxes secured to deck.
Engineering › Bilge Water Management System › Interface Detector
Issued 24 April 2006 Resolved
Repair high water level audible alarm. Audible alarm for the high water level alarm system did not work, but visual did.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 28 April 2006
Resolved 24 April 2006
Resolution: POC REPLACE ALARAM AND TESTED ALARM WHILE ON THE PHONE. ALL SAT.
Operations/Management › Drug and Alcohol Testing › Recordkeeping
Issued 18 April 2005 Resolved
HAVE ALL EMPLOYEES SIGNED CONTROLLED SUBSTANCE POLICY IAW 46 CFR 16.
Due 1 May 2005
Resolved 3 May 2005
Operations/Management › Drug and Alcohol Testing › EAP Display Requirements
Issued 18 April 2005 Resolved
POST EMPLOYEE ASSISTANCE POLICY IAW 46 CFR 16.401.
Due 1 May 2005
Resolved 3 May 2005
Lifesaving › Hand Flares › Expired
Issued 18 April 2005 Resolved
PROVIDE 3 HAND HELD FLARES.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 18 April 2005
Resolution: FAX RECEIPT.
Construction/Loadline › Structures › Transverse Bulkhead
Issued 18 April 2005 Resolved
REPAIR AREA OF ROT ABOVE WEEP HOLE IN AFT STARBOARD BULKHEAD 46 CFR 177.610.
Due 18 May 2005
Resolved 3 May 2005
Lifesaving › Lifejacket/PFD (Type I)
Issued 22 April 2002 Resolved
REPLACE RETROFLECTIVE MATERIAL ON LIFEJACKETS AS NECESSARY. LEGACY COMPONENT DESC: Retroreflective Material
Condition: Improper/Lack of Maintenance
Due 29 April 2002
Resolved 31 May 2002
Resolution: CLEARED VIA FAXED STATEMENT FROM OWNER.
Stability › Watertight Integrity
Issued 22 April 2002 Resolved
Penetrations through transom not adequately sealed. LEGACY COMPONENT DESC: Bulkhead penetrations
Condition: Improper/Lack of Maintenance
Due 6 May 2002
Resolved 6 May 2002
Resolution: 3M 5200 used to seal penetrations.
Stability › Watertight Integrity
Issued 22 April 2002 Resolved
Through hull spool piece on inboard side of port hull missing. LEGACY COMPONENT DESC: Spool Piece
Condition: Improper/Lack of Maintenance
Due 6 May 2002
Resolved 6 May 2002
Resolution: New spool piece installed.
Stability › Weathertight Integrity
Issued 22 April 2002 Resolved
Gaskets for deck hatches need to be replaced. LEGACY COMPONENT DESC: Deck Hatch Gaskets
Condition: Improper/Lack of Maintenance
Due 6 May 2002
Resolved 6 May 2002
Resolution: New gaskets were installed.
Construction/Loadline
Issued 8 May 2001 Resolved
INSTALL VISUAL INDICATOR LIGHTS FOR BILGE PUMPS.
Condition: Unknown
Due 8 June 2001
Resolved 30 May 2001
Construction/Loadline
Issued 8 May 2001 Resolved
CORRECT/REPAIR INDICATOR LIGHT FOR HIGH WATER BILGE ALARM ON PORT SIDE.
Condition: Unknown
Due 8 June 2001
Resolved 30 May 2001
Unknown
Issued 21 April 1997 Resolved
PROVIDE MIS REPORT FROM/VIA CONSORTIUM.
Condition: Unknown
Due 22 April 1997
Resolved 22 April 1997
Accommodation/Occupational Safety
Issued 14 June 1994 Resolved
Install locking device on holding tank overboard valve.
Condition: Unknown
Due 29 June 1994
Resolved 29 June 1994
Documentation
Issued 27 July 1993 Resolved
Post COI, stability letter & emergency check off list.
Condition: Unknown
Due 27 July 1993
Resolved 27 July 1993
Navigation
Issued 27 July 1993 Resolved
Provide suitable bell of 8 inches minimum in diameter.
Condition: Unknown
Due 27 July 1993
Resolved 27 July 1993
Lifesaving
Issued 9 May 1990 Resolved
PROVIDE PLACARD FOR STOWAGE OF 10 ADULT LIFE PFD'S UNDER PILOT SEATING AREA.
Condition: Unknown
Due 9 May 1990
Resolved 9 May 1990
Fire Fighting
Issued 9 May 1990 Resolved
PROVIDE SUCTION LINE FOR HAND HELD BILGE/FIRE PUMP.
Condition: Unknown
Due 9 May 1990
Resolved 9 May 1990
Documentation
Issued 9 May 1990 Resolved
PROVIDE COPY OF CURRENT RADIO SAFETY CERTIFICATES.
Condition: Unknown
Due 9 May 1990
Resolved 9 May 1990
Fire Fighting
Issued 12 August 1988 Resolved
PROVIDE AN EXTRA B-II FIRE EXTINGUISHER AS A SUBSTITUTE FOR REQUIRED FIRE PUMP ON FERRY VESSEL. A TOTAL OF 1 B-I AND 3 B-II EXTINGUISHERS WILL BE REQUIRED.
Condition: Unknown
Due 12 August 1988
Resolved 12 August 1988
Fire Fighting
Issued 28 July 1988 Resolved
IN ACCORDANCE WITH 46CFR 181.10-1 A POWER FIRE PUMP SATISFACTORY TO THE COGNIZANT OCMI IS TO BE INSTALLED, CHECKED AND TESTED PRIOR TO THE VESSEL BEING PLACED INTO FERRY SERVICE.
Condition: Unknown
Due 28 July 1988
Resolved 28 July 1988