SATISFACTION II

SATISFACTION II is a 1978 passenger vessel (inspected). The Coast Guard has recorded 46 inspections since 1991, most recently in October 2025, along with 55 deficiencies.

Records from 1991 to 2025. Most recent: inspection, 16 October 2025.

Built
1978
Last inspected
16 October 2025
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WDI8187
320421
Flag
UNITED STATES
366001040, 367033490, 367736110 (licence lapsed)
Maury page id
psix-320421

Inspections, by type

…with no type recorded2
Years with a record 32 calendar years (1991–2025)
The 46 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)82.0 ft × 20.0 ft × 8.2 ft
Registered tonnagegross 99 / net 67
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderKELLY SHOP INC · JEFFERSONVILLE, IN, UNITED STATES · built 1978
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portCINCINNATI, OH
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 11 July 2025 · expires 31 July 2026
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it99 - Regulatory (Subpart C or D), Gross Ton
67 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDI8187MMSI 367736110 · expired · compulsorily equipped · granted 24 May 2016, cancelled 27 June 2026
WDC4960MMSI 367033490 · expired · compulsorily equipped · granted 14 April 2005, cancelled 20 June 2015
WAB3851MMSI 366001040 · expired · compulsorily equipped · granted 6 April 1994, cancelled 22 August 2004
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.

Inspection history · 46

16 October 2025 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 8254460
16 July 2024 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 7959612
13 June 2023 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 7714182
7 July 2022 Deficiency Check · COI Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 7499275
15 June 2021 Hull Examination · Deficiency Check
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 7226033
28 April 2021 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 7185475
13 July 2020 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 7005219
26 June 2019 Annual Inspection · Deficiency Check · Administrative Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 6727672
9 October 2018 Deficiency Check
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 6557689
12 July 2018 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 6476986
18 April 2017 COI Inspection · DAPI Audit · Deficiency Check
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 6128141
14 July 2016 DAPI Audit · In-Service Inspection · Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 5944628
9 June 2016 Internal Structural Exam · Hull Examination
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 5905914
16 July 2015 Internal Structural Exam · Deficiency Check · In-Service Inspection · Administrative Inspection · Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 5186363
20 May 2014 Annual Inspection · Deficiency Check · DAPI Audit
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 4837082
29 November 2010 Drydock Extension
Administrative · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 3911681
6 May 2009 DAPI Audit · Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 3468737
28 May 2008 Deficiency Check
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 3220524
17 April 2008 DAPI Audit · Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 3186319
10 April 2007 Administrative Inspection
Administrative · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 2904859
5 April 2007 COI Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 2902080
12 April 2006 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 2622296
26 July 2005 Hull Examination
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 2466810
13 April 2005 Deficiency Check
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 2432009
8 April 2005 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 2327540
29 April 2004 Annual Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 2049089
15 April 2003 Re-Inspection
Physical examination · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 1774856
17 April 2002 Type not recorded
No type recorded · Marine Safety Detachment Cincinnati · USCG Heartland District (CGD-H) · Activity 1605961
11 April 2001 Re-Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1471251
7 July 2000 Hull Examination
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1451575
25 May 2000 Re-Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1381960
7 March 2000 Drydock Extension
Administrative · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1046392
29 April 1999 Deficiency Check
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 806773
19 March 1999 COI Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1450252
26 March 1998 Re-Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1424568
10 April 1997 Re-Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1364107
29 March 1996 COI Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1081664
22 March 1995 COI Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 836385
14 February 1995 Hull Examination
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 851320
7 April 1994 COI Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1167342
30 April 1993 Deficiency Check
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1142038
21 April 1993 COI Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 834297
28 April 1992 COI Inspection
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 959872
21 May 1991 Type not recorded
No type recorded · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1228621
4 May 1991 Initial Certification · Inclining Experiment · Plan Review "T" Boat
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1227837
22 March 1991 Hull Examination
Physical examination · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 1231877

Deficiency record · 55

11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 16 October 2025 Resolved
Vessel was missing 13 life jackets. Failure to ensure enough life jackets were onboard. Provide 13 life jackets onboard vessel to the satisfaction of the attending Coast Guard marine inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 January 2026
Resolution: 13 Life jackets onboaord and in sat conditions.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 16 October 2025 Resolved
Two Fire hoses had holes and were leaking. Failure to comply with fire fighting appliance requirements. Replace fire hoses to the satisfaction of the attending Coast Guard marine inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 January 2026
Resolution: Fire hoses onboard in good condition.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 16 October 2025 Resolved
Distress flares were expired. Failure to comply with distress flare requirements. Provide distress flares to the satisfaction of the attending Coast Guard marine inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 January 2026
Resolution: New Flares onboard.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 16 October 2025 Resolved
Two life buoys were sun bleached and worn. Water light battery was dead and lifeline broke when pulled upon. Failure to maintain life buoy and appliances. Provide 2 life buoys, water light and lifeline to the satisfaction of the attending Coast Guard marine inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 January 2026
Resolution: Life buoy onbaord in good condition.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Sewage discharge connection
Issued 16 July 2024 Resolved
Type III MSD discharge valve was not secured. Failure to secure each Type III MSD prior to operating vessel in an area where the discharge of untreated sewage is prohibited by the EPA. Valve was secured during inspection.
Action required: 10 - Deficiency Rectified
Due 16 July 2024
Resolved 16 July 2024
Resolution: Valve was secured during inspection.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 13 June 2023 Resolved
Fire hose nozzles were a plastic unapproved type. Fire hose nozzle shall be of brass or other corrosion resistant material that comply with NFPA 1963. Replace three fire hose nozzle with correct type to the satisfaction of the attending Coast Guard marine inspector.
Action required: 10 - Deficiency Rectified
Resolved 13 June 2023
Resolution: Corrected on the spot. Crew had approved brass type in locker.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 7 July 2022 Resolved
Vessel's pre-engineered fixed gas fire extinguishing system was found in the override position on the helm and the green light for for ready and the red light for discharged were extinguished leaving operator unsure of the operational status of the pre-engineered fixed gas fire extinguishing system. A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station: (1) A light to indicate discharge; (2) An audible alarm that sounds upon discharge; and (3) A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section. Provide service tech report that the pre-engineered fixed gas fire extinguishing system has been serviced and is fully operational.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 July 2022
Resolution: New switch was installed and tested with satisfactory results.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 28 April 2021 Resolved
During the fire drill there was confusion on the order and process to deploy the agent of the fixed fire fighting system. The directions on the pull box was incorrect. Crew unable to explain if engines are shut down by means of electrical, air intake or fuel shut out. Crew was unsure of the override/reset switch on the helm. Complete but simple instructions for the operation of a fixed gas fire extinguishing system must be located in a conspicuous place at or near each pull box and stop valve control and in the space where the extinguishing agent cylinders are stored. If the storage cylinders are separate from the protected space, the instructions must also include a schematic diagram of the system and instructions detailing alternate methods of releasing the extinguishing agent should the local manual release or stop valve controls fail to operate. Provide written procedures and diagram that explain the specific function and operation of the make/model fixed fire fighting system for the Satisfaction II, to the satisfaction of the attending Coast Guard Marine Inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 May 2021
Resolved 4 May 2021
Resolution: Received adequate documentation of written procedures and diagram that explain the specific function and operation of the make/model fixed fire fighting system
10 - Safety of Navigation › N/A - No Subsystem › Bridge operation
Issued 8 July 2019 Resolved
The master shall conduct sufficient drills and give sufficient instructions to make sure that all crew members are familiar with their duties during emergencies that necessitate abandoning ship or the recovery of persons who have fallen in the water. Conduct satisfactory man overboard and abandon ship drills in the presence of an attending CG Marine Inspector prior to carrying passengers.
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 11 July 2019
Resolution: Vessel provided properly licensed Master and crew who were able to prove capable shipboard recovery of a man in the water.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 8 July 2019 Resolved
Chemical testing of personnel must be conducted as required by 46 CFR 16 subpart B and in accordance with the procedures detailed in 49 CFR 40. Provide evidence of satisfactory chemical testing program to attending CG Marine Inspector prior to carrying passengers.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 12 July 2019
Resolution: Proved enrollment in DAPI program.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 8 July 2019 Resolved
A vessel must carry one floating water light approved in accordance with 46 CFR 161.010 unless limited to daytime operations. Prove proper operation of installed water light to attending CG Marine Inspector prior to night operations.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 July 2019
Resolved 12 July 2019
Resolution: Provided appropriate battery for water light.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 8 July 2019 Resolved
The operator of each vessel 12 meters or more in length shall carry, on board and maintain for ready reference, a copy of th Inland Navigation Rules as defined in 33 CFR Subchapter E. Provide evidence of a current copy of Inland Navigation Rules to attending CG Marine Inspector
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 July 2019
Resolved 11 July 2019
Resolution: Master provided vessel with updated copy of Nav Rules.
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 12 July 2018 Resolved
No valid COD on board.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 12 August 2018
Resolved 12 July 2018
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 12 July 2018 Resolved
Update emergency instructions to accurately reflect actual operations aboard vessel.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 August 2018
Resolved 9 October 2018
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 12 July 2018 Resolved
Replace fire extinguisher located in pantry indicated during inspection with USCG approved B-II or 2-A.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 August 2018
Resolved 9 October 2018
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 12 July 2018 Resolved
Replace smoke detectors where overnight accommodations are available to passengers.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 August 2018
Resolved 9 October 2018
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 12 July 2018 Resolved
If console on upper-deck is completely de-energized, remove 10-B:C or B-I and replace with a A-II or 2-A.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 August 2018
Resolved 9 October 2018
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 18 April 2017 Resolved
Due to the river conditions, a man overboard drill and fire drill were not conducted during your vessel’s COI. Please schedule a follow up with this office prior to the due date.
Condition: Invalid
Action required: 705 - Other - as specified
Due 18 May 2017
Resolved 15 May 2017
Documentation › Logs/Records › Drug Test Records
Issued 18 April 2017 Resolved
Contact your company’s drug program consortium to request proof of CY 2016 Management Information System (MIS) report submission.
Condition: Invalid
Action required: 705 - Other - as specified
Due 18 May 2017
Resolved 15 May 2017
Fire Fighting › Fire Pumps › Pressure
Issued 18 April 2017 Resolved
On a vessel of more than 19.8 (65’) in length, the minimum capacity of the fire pump must be 189 liters (50 gallons) per minute at a pressure of not less than 414 kPa (60 psi) at the pump outlet.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 May 2017
Resolved 15 May 2017
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 18 April 2017 Resolved
Each ring life buoy must be marked in clearly legible block capital letters with the vessel’s name.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 18 May 2017
Resolved 15 May 2017
Documentation › Markings/Placards › Lifejacket Placard
Issued 18 April 2017 Resolved
Placards containing instructions for the donning and use of the life jackets aboard the vessel must be posted in conspicuous places that are regularly accessible and visible to the crew and passengers.
Condition: Invalid
Action required: 705 - Other - as specified
Due 18 May 2017
Resolved 15 May 2017
Communications › Alarms/Indicators › Bilge Alarm
Issued 16 July 2015 Resolved
Replace bilge high level alarm located in the engine compartment IAW 46 CFR 182.115 (d) & 46 CFR 182.530.
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 6 August 2015
Fire Fighting › Remote Fuel Shutoff › General
Issued 16 July 2015 Resolved
Repair emergency fuel shut off on port MDE fuel tank.
Condition: Design Flaw
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 6 August 2015
Lifesaving › Hand Flares › Expired
Issued 16 July 2015 Resolved
Replace expired flares IAW 46 CFR 180.68 (b) or (c). Vessel is restricted to routes that are less than 30 minutes from the dock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 August 2015
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 16 July 2015 Resolved
At least on ring life buoy must be fitted with a lifeline IAW 46 CFR 180.70 (c)
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 16 August 2015
Resolved 6 August 2015
Lifesaving › Lifejacket/PFD (Type I) › Marking
Issued 16 July 2015 Resolved
Each life jacket must be marked with the vessel's name IAW 46 CFR 180.71 (e) and 46 CFR 185.604.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 16 July 2015
Documentation › Certificates/Documents › Certificate of Inspection
Issued 16 July 2015 Resolved
Due to high water conditions, was not able to complete underway portion of the inspection IAW 46 CFR 176.502, vessel must complete exam to maintain validity of COI.
Action required: 705 - Other - as specified
Due 16 August 2015
Resolved 6 August 2015
Electrical › Electric Generation Source (service) › Generator
Issued 16 July 2015 Resolved
An ammeter shall be provided that can be used for measuring current of each generator that is in operation IAW 46 CFR 183.10-5 (g)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 6 September 2015
Resolved 13 May 2016
Communications › Alarms/Indicators › Bilge Alarm
Issued 20 May 2014 Resolved
Properly label the bilge high level alarm panel located at the operating station to reflect each individual space.
Action required: 705 - Other - as specified
Due 20 June 2014
Resolved 29 July 2014
Resolution: All four spaces were properly identified on the bilge high level alarm panel at the operating station.
Electrical › Electrical Distribution System (service) › Wiring
Issued 20 May 2014 Resolved
Remove all twist type lug connections in way of the bow thruster panel in the machinery space and replace with compression type connections as required by 46 CFR 183.340(i).
Action required: 705 - Other - as specified
Due 20 June 2014
Resolved 29 July 2014
Resolution: All twist type lug connections were removed and replaced with compression type fittings.
Electrical › Electrical Distribution System (service) › Junction Box
Issued 20 May 2014 Resolved
Properly secure and cover the exposed junction box in way of the high water level alarm located in the machinery space.
Action required: 705 - Other - as specified
Due 20 June 2014
Resolved 29 July 2014
Resolution: Junction box was properly covered.
Electrical › Electrical Distribution System (service) › Wiring
Issued 20 May 2014 Resolved
Properly secure the loose rod and sensor in way of the rudder angle indicator located in the machinery space.
Action required: 705 - Other - as specified
Due 20 June 2014
Resolved 29 July 2014
Resolution: The rod was removed but the sensor remains in place but unable to get replacement rod. Operator was advised that rudder angle indicator is not required equipment and it was his decision as whether or not to replace it with a digital readout.
Electrical › Electrical Distribution System (service) › Wiring
Issued 20 May 2014 Resolved
Properly bundle and secure all hanging wiring in way of the forward generator with metallic supports spaced no more than 24 inches apart in accordance with 46 CFR 183.340(b)(4).
Action required: 705 - Other - as specified
Due 20 June 2014
Resolved 29 July 2014
Resolution: All plastic wire tie wraps used for securing were removed and replaced with metallic fasteners.
Electrical › Electric Generation Source (service) › Panelboard
Issued 20 May 2014 Resolved
Provide a means of measuring frequency in way of the A/C forward generator in accordance with 46 CFR 183.320(c)
Action required: 705 - Other - as specified
Due 20 June 2014
Resolved 29 July 2014
Resolution: Frequency meter was installed to the A/C generator and tested under load.
Lifesaving › Hand Flares › Expired
Issued 17 April 2008 Resolved
Replace expired flares.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 April 2008
Resolved 27 May 2008
Fire Fighting › Fixed Gas Fire Extinguishing System › Operating Controls
Issued 17 April 2008 Resolved
Correctly install new fixed system.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 April 2008
Resolved 27 May 2008
Lifesaving › Lifejacket/PFD (General) › Condition
Issued 12 April 2006 Resolved
Replace three PFDs that are badly faded.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 April 2006
Resolution: PFDs replaced during the course of the inspection.
Documentation › Certificates/Documents › FCC SSL
Issued 8 April 2005 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Action required: 705 - Other - as specified
Due 8 May 2005
Resolved 13 April 2005
Resolution: Completed FCC license application, temporary license on board.
Operations/Management › Drills/Instruction › Fire
Issued 8 April 2005 Resolved
Conduct fire, man overboard, and abandon ship drills prior to getting underway with passengers.
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Due 8 May 2005
Resolved 13 April 2005
Resolution: Drills conducted.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 8 April 2005 Resolved
Prove proper operation of waterlight on ring buoy.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 8 May 2005
Resolved 13 April 2005
Resolution: New light installed.
Accommodation/Occupational Safety › Medical/First Aid
Issued 29 April 2004 Resolved
Place first aid kit in water tight container and properly label. LEGACY COMPONENT DESC: Medicine Chest
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 7 May 2004
Resolved 30 April 2004
Resolution: First aid kit placed in water tight container and properly marked.
Navigation › Piloting/Steering
Issued 29 April 2004 Resolved
Provide current copy of Coast Guard Light List. LEGACY COMPONENT DESC: Coast Guard Light List
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 7 May 2004
Resolved 30 April 2004
Resolution: Current copy of CG light list placed onboard.
Lifesaving › Lifejacket/PFD (General)
Issued 29 April 2004 Resolved
Provide donning instructions at all life jacket lockers. LEGACY COMPONENT DESC: Storage
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 7 May 2004
Resolved 30 April 2004
Resolution: Instructions posted at all life jacket lockers.
Lifesaving › Lifebuoys
Issued 29 April 2004 Resolved
Remove floating line for ring buoys from rail, make ring buoy throwable. LEGACY COMPONENT DESC: Buoyant Lifeline
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 7 May 2004
Resolved 30 April 2004
Resolution: Floating line removed from hand rails making device throwable.
Operations/Management › Drug and Alcohol Testing
Issued 29 April 2004 Resolved
Provide proof of random drug testing. LEGACY COMPONENT DESC: Recordkeeping
Condition: Unknown
Action required: 17 - Rectify deficiencies prior to departure
Due 7 May 2004
Resolved 30 April 2004
Resolution: Received copy of current drug tests.
Lifesaving › Hand Flares
Issued 29 April 2004 Resolved
Provide flares in accordance with 46 CFR 180.68. LEGACY COMPONENT DESC: Quantity
Condition: Unknown
Action required: 17 - Rectify deficiencies prior to departure
Due 7 May 2004
Resolved 30 April 2004
Resolution: Proper flares placed onboard.
Construction/Loadline
Issued 19 March 1999 Resolved
INSTALL BILGE HIGH LEVEL ALARMS IN ACCORDANCE WITH 46.CFR182.530._x001C_
Condition: Unknown
Due 19 March 1999
Resolved 19 March 1999
Electrical
Issued 21 April 1993 Resolved
PROPERLY WIRE LIGHTING IN FOREPEAK, INCLUDING SUPPORT FOR CABLES AND COVERSFOR JUNCTION BOXES, NO LATER THAN THE COMPLIANCE DATE.
Condition: Unknown
Due 13 May 1993
Resolved 13 May 1993
Fire Fighting
Issued 21 April 1993 Resolved
COMPLETE SATISFACTORY ANNUAL SERVICING OF FIXED HALON FIRE EXTINGUISHING SYSTEM NO LATER THAN THE COMPLIANCE DATE.
Condition: Unknown
Due 13 May 1993
Resolved 13 May 1993
Documentation
Issued 28 April 1992 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Due 28 May 1992
Resolved 12 May 1992
Lifesaving
Issued 28 April 1992 Resolved
ATTACH WATERLIGHT TO LIFE RING BUOY PRIOR TO CARRYING PASSENGERS DURING NIGHTTIME OPERATION, BUT NOT LATER THAN THE COMPLIANCE DATE.
Condition: Unknown
Due 28 April 1992
Resolved 12 May 1992
Construction/Loadline
Issued 4 May 1991 Resolved
INSTALL VISIBLE ALARM FOR WATERTIGHT DOOR AT FRAME 45 WHICH INDICATES, AT BOTH OPERATOR CONTROL STATIONS, WHEN THE DOOR IS OPENED, NOT LATER THAN THECOMPLIANCE DATE
Condition: Unknown
Due 4 May 1991
Resolved 4 May 1991
Construction/Loadline
Issued 4 May 1991 Resolved
MARK VESSEL'S NAME AND HAILING PORT ON STERN IN CLEARLY LEGIBLE LETTERS NOTLESS THAN 4 INCHES IN HEIGHT, BY THE COMPLIANCE DATE.
Condition: Unknown
Due 4 May 1991
Resolved 4 May 1991
Construction/Loadline
Issued 4 May 1991 Resolved
INSTALL SIGN OUTSIDE AFT ENGINE ROOM DOOR AT FRAME 8, WHICH STATES: "KEEP DOOR CLOSED EXCEPT WHEN USED FOR TRANSIT", NOT LATER THAN THE COMPLIANCE DATE.
Condition: Unknown
Due 4 May 1991
Resolved 4 May 1991

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.