Records from 2016 to 2026. Most recent: inspection, 29 July 2026.
Inspection history · 22
29 July 2026
Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8449926
29 April 2026
COI Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8353589
30 April 2025
Annual Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8126823
14 November 2024
Internal Structural Exam · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 8034914
14 May 2024
Annual Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7903919
21 December 2023
Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 7850901
18 May 2023
Internal Structural Exam · Annual Inspection · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7692063
17 August 2022
Annual Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7535183
12 May 2022
In-Service Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7444033
15 June 2021
COI Inspection · Deficiency Check · DAPI Audit
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7197049
20 April 2021
Internal Structural Exam · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 7156736
27 May 2020
Annual Inspection · Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6960474
4 November 2019
Administrative Inspection
Administrative · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6848759
24 April 2019
Hull Examination · Internal Structural Exam
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6669508
27 September 2018
Internal Structural Exam · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6550057
9 July 2018
Deficiency Check · Annual Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6474585
10 August 2017
Deficiency Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6236015
2 August 2017
Spot Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6228543
6 July 2017
Deficiency Check · Annual Inspection · Spot Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6199974
8 September 2016
Internal Structural Exam · Hull Examination
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 6000006
21 July 2016
Spot Check
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5949633
7 July 2016
Deficiency Check · COI Inspection
Physical examination · Sector Long Island Sound · USCG Northeast District (CGD-NE) · Activity 5921250
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 29 April 2026
Resolved
Type I Personal Flotation Devices required for each adult, meeting marking and stowage standards. COI requires 14 adult PFD's, vessel equipped with 12. Provide 2 additional PFD's.
Action required: 705 - Other - as specified
Resolved 4 May 2026
Resolution: Received photographic evidence of compliance.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 29 April 2026
Resolved
Lifebuoy requires marking and reflective tape IAW 46CFR185.604. Mark lifebuoy as directed with reflective tape and vessel name.
Action required: 705 - Other - as specified
Resolved 4 May 2026
Resolution: Received photographic evidence of compliance.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 30 April 2025
Resolved
Slow down water ingress in way of rudder post, either by tightening packing nut or adding to packing. Water is entering vessel at a steady stream and is excessive.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 4 June 2025
Resolution: Received photographic evidence of correction.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 30 April 2025
Resolved
In numbers not less than 2 inches high, correctly identify the number of adult lifejackets stowed in forward locker.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 4 June 2025
Resolution: Received photographic evidence of correction.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 30 April 2025
Resolved
A submersible electric bilge pump may be used as a power bilge pump, provided that: a positive shutoff valve is installed at the hull penetration. Correct prior to next drydock scheduled in Nov. 2026.
Action required: 705 - Other - as specified
Resolved 29 July 2026
Resolution: Confirmed correction of deficiency.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 14 May 2024
Resolved
The number and identification of the items must be marked on each container for life jackets. Letters and numbers must be at least 2 inches high. Number of adult lifejackets marking was missing from storage area.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2024
Resolved 7 June 2024
Resolution: Labels added; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 14 May 2024
Resolved
Placards containing instructions for the donning and use of life jackets aboard the vessel must be posted. Missing lifejacket donning instructions.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2024
Resolved 7 June 2024
Resolution: Placard added; all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 14 May 2024
Resolved
Each lifering with a floating waterlight must have a lanyard of 3-6 feet with a corrosion-resistant clip, securing the waterlight around the body of the lifering. Waterlight was not secured to the lifering.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2024
Resolved 7 June 2024
Resolution: All sat.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 14 May 2024
Resolved
Fixed gas fire extinguishing system must be inspected as required by table 176.810(b) and operators must provide satisfactory evidence of the required servicing to the marine inspector. There is no record of servicing for the fire-boy on board.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 June 2024
Resolved 7 June 2024
Resolution: Fireboy was serviced; all sat.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 18 May 2023
Resolved
A vessel that is exposed to salt water more than 3 months in a 12 month period, must undergo dry dock and internal structural examinations once every two years. Vessel was operating pass its dry dock deadline. Conducted dry dock and internal structural examinations on 18May2023. Deficiency cleared.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 18 May 2023
Resolution: Conducted hull/ISE
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 18 May 2023
Resolved
A stability letter must be posted under glass or on board in a watertight container, readily available. Stability letter was missing. Inspector provided operator with a copy of stability letter. Deficiency cleared.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 18 May 2023
Resolution: Provided copy to operator.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 17 August 2022
Resolved
Provide retro-reflective material for Ring Life Buoy. New RLB, no retro applied.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 August 2022
Resolved 7 September 2022
Resolution: Resolved
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 17 August 2022
Resolved
Prove proper operation of stern light. Current light inoperable.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 August 2022
Resolved 7 September 2022
Resolution: Resolved
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 12 May 2022
Resolved
The fixed gas fire extinguishing installation must be installed in accordance with the manufacturer's instructions. The installed Fireboy is undersized for the total enclosed volume open to the engine room.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 June 2022
Resolved 19 August 2022
Resolution: completed
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 12 May 2022
Resolved
Alterations to the machinery must not be made without the approval of the [name withheld] and fuel system was replaced without approval. Submit written specifications describing the details of the alterations.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 June 2022
Resolved 17 August 2022
Resolution: completed, replacement in kind
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 12 May 2022
Resolved
The lifeline attached to the lifebuoy must be 60 feet in length. The lifeline provided was approximately 30 feet in length.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 June 2022
Resolved 19 August 2022
Resolution: provided
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 12 May 2022
Resolved
The COI must be available for passengers to review. The COI or a copy was not on board.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 June 2022
Resolved 17 August 2022
Resolution: done
01 - Certificates & Documentation › 013 - Documents › Stability Information Booklet
Issued 12 May 2022
Resolved
The stability letter must be available for the master to review. The stability letter or a copy was not on board.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 June 2022
Resolved 17 August 2022
Resolution: completed
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 15 June 2021
Resolved
Bilge high level alarm not working. Bilge high level must have a audible and visual alarm in good working order.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 June 2021
Resolved 2 September 2021
Resolution: Bilge alarm is operational. Both audible and visual.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 15 June 2021
Resolved
Shaft packing gland excessice leaking into bilge. Greatly reduce the amount of leaking from the shasft packing gland.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 June 2021
Resolved 9 September 2021
Resolution: Shaft packing tighten and water has crawled to almost no drip.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 15 June 2021
Resolved
Fireboy pre engineered systems does not allow engine to restart after test/discharge. Fire bouy needs to operate as designed.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 June 2021
Resolution: Fireboy is fully operational.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 15 June 2021
Resolved
Fireboy doesnt have inspection tag of last service. Annual maintenance must be performed by a certified service agency.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 30 June 2021
Resolution: Fireboy has been serviced by a qualified technician.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 27 May 2020
Resolved
Replace expired first aid kit.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 June 2020
Resolved 10 June 2020
Resolution: New first aid kit provided.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 9 July 2018
Resolved
Fixed fire system would not allow the engine to start in the normal mode. Engine started in overide mode.
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Due 13 July 2018
Resolved 17 July 2018
Resolution: System tested all sat.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Remote Pulls
Issued 6 July 2017
Resolved
Install safety tab on pull handle.
Condition: Improper/Lack of Maintenance
Due 6 August 2017
Resolved 10 August 2017
Resolution: Tab installed.
Fire Fighting › Fire Bucket › Quantity
Issued 6 July 2017
Resolved
INSTALL FIRE BUCKET
Condition: Improper/Lack of Maintenance
Due 6 August 2017
Resolved 2 August 2017
Resolution: fire bucket installed.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 6 July 2017
Resolved
Install reflective tape
Condition: Placed in Improper Service
Due 6 August 2017
Resolved 2 August 2017
Resolution: Reflective tape installed.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 6 July 2017
Resolved
Replace battery in float light
Condition: Improper/Lack of Maintenance
Due 6 August 2017
Resolved 2 August 2017
Resolution: Battery light installed.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 6 July 2017
Resolved
Install RFI line on life ring 5/16
Condition: Improper Installation
Due 6 August 2017
Resolved 2 August 2017
Resolution: Line Installed.
Personnel › Certificates/Documents/Licenses › License, Master
Issued 21 July 2016
Resolved
06 of 08 mariners did not have valid MMC's. Provide valid MMC's prior to allowing them to operate vessels.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: All non-credentialed personnel have submitted packages to NMC.
Operations/Management › Drug and Alcohol Testing › EAP Training Requirements
Issued 21 July 2016
Resolved
Mariners had no/limited knowledge of post SMI drug and alcohol test procedures. Provide proof that employees have been trained on post SMI drug and alcohol test procedures.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: All non-credentialed employees have departed for the season.
Fire Fighting › Fixed Gas Fire Extinguishing System › Quantity of Gas
Issued 7 July 2016
Resolved
Renew engine space fixed firefighting system (Fire-boy).
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 July 2016
Resolution: System renewed and tested satisfactory.
Fire Fighting › Fixed Gas Fire Extinguishing System › Operating Controls
Issued 7 July 2016
Resolved
Provide tamper seal for Fire-boy manual pull T-handle.
Due 21 July 2016
Resolved 19 August 2016
Resolution: Tamper seal installed.