Records from 2013 to 2025. Most recent: inspection, 29 July 2025.
Everything above is free. The detail below — the inspection history, the deficiency record, the casualty record and the documentation record — is Professional, $39 a month. Sign in.
Inspection history · 12
29 July 2025
Annual Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 8188664
20 August 2024
Annual Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7989410
2 May 2024
Deficiency Check
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7911388
10 October 2023
Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7808258
10 May 2023
In-Service Inspection · Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7683563
30 August 2022
Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7541531
29 July 2021
COI Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7273370
13 July 2020
Annual Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 7005430
7 May 2019
Annual Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 6683057
1 May 2018
Annual Inspection · Drydock Exam
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 6408265
3 May 2017
COI Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 6104416
12 July 2016
Annual Inspection
Physical examination · Marine Safety Detachment St. Paul · USCG Heartland District (CGD-H) · Activity 5941490
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 29 July 2025
Resolved
The number and identification of the items stowed inside, and their sizes, must be marked in clearly legible letters and numbers on each container for life jackets... Letters and numbers must be at least 2 inches high... Label all PFD storage containers.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2025
Resolved 22 September 2025
Resolution: Correct signage placed on PFD storage locations.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 17 October 2023
Resolved
The number and identification of the items stowed inside, and their sizes, must be marked in clearly legible letters and numbers on each container (or space) for life jackets. The letters must be at least 2 inches high. Life jackets stowed in the forward lockers were not labeled and the labeling on the upper deck containers was faded; label spaces and containers where the lifejackets are stowed.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2023
Resolved 13 May 2024
Resolution: Label placed on stoage containers
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 17 October 2023
Resolved
Portable fire extinguishers must be located so they are clearly visible and readily accessible from the space being protected. The installation and location must be to the satisfaction of the Officer in Charge, Marine Inspections. Portable fire extinguisher in the bar area is unsecured and on the ground; mount fire extinguisher in clearly visable and readily accessible location.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2023
Resolved 13 May 2024
Resolution: Fire extinguisher mounted
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 October 2023
Resolved
The owner, charterer, master or managing operator shall instruct each crew member, upon first being employed and prior to getting underway for the first time on a particular vessel and at least every three months, as to the duties that the crew member is expected to perform in an emergency. Crew training shall be logged or otherwise documented for review by the Coast Guard. Conduct and log drills prior to FY24 operating season.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 October 2023
Resolved 26 August 2024
Resolution: Vefified training logs during 2024 annual.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 10 October 2023
Resolved
Portable watertight containers for distress flares and smoke signals shall be a bright color, and marking in legible contrasting letters at least 1/2 inches high: DISTRESS SIGNALS. Watertight containers were not properly labeled; label container.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2023
Resolved 13 May 2024
Resolution: Container labeled.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 October 2023
Resolved
Electrical equipment on a vessel must be installed and maintained to: protect passengers, crew, other persons, and the the vessel from electrical hazards, including fire, caused by or originating in electrical equipment and electrical shock. Multi-outlet adapters (power strips) are connected to other adapters (daisy-chained) in a manner that could overload the capacity of the receptacle; removed adapter.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2023
Resolved 13 May 2024
Resolution: Adaptor removed.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 10 October 2023
Resolved
Each door, hatch, or scuttle, use as a means of escape, must be capable of being opened by one person, from either side. The exterior engine room door is outfitted with a barrel slide bolt lock; remove lock or provide satisfactory justification to Officer in Charge, Marine Inspection.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2023
Resolved 13 May 2024
Resolution: Barrel side lock removed.
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 10 October 2023
Resolved
The person in command of a documented vessel must have on board that vessel the original Certificate of Documentation currently in effect for that vessel. Document was not on board vessel; provide copy of document to attending marine inspector.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2023
Resolved 13 May 2024
Resolution: Copy of COD provided to MI
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 30 August 2022
Resolved
A vessel on an rivers route must carry three hand red flare distress signals and three hand orange smoke distress signals approved in accordance with §160.037 in subchapter Q of this chapter, or other standard specified by the Commandant. MI found distress signals expired, replace with new.
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 September 2022
Resolved 12 September 2022
Resolution: Receipt/photo provided
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 30 August 2022
Resolved
A vessel must carry either a first-aid kit approved under approval series 160.041 or a kit with equivalent contents and instructions. For equivalent kits, the contents must be stowed in a suitable, watertight container that is marked “First-Aid Kit.” A first-aid kit must be easily visible and readily available to the crew. First-Aid kit contents were found outdated.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 31 August 2022
Resolution: Expired contents replaced.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 August 2022
Resolved
Electrical equipment on a vessel must be installed and maintained to minimize accidental personnel contact with energized parts. MI discovered battery covers in the E/R not installed. Rectified on the spot.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Resolved 30 August 2022
Resolution: Covers installed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 29 July 2021
Resolved
Label life buoy's appropriately.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 26 August 2021
Resolution: life rings labeled
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 29 July 2021
Resolved
overheated port main engine occurred on July 27th.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 August 2021
Resolution: Engine overheated due to coolant valve that was shut off
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 29 July 2021
Resolved
Stow bar fire extinguisher in a bracket.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 August 2021
Resolution: fire extinguisher stowed
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 7 May 2019
Resolved
Re-test each bilge alarm; when tested, the E/R alarm squawked considerably before actuating.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 11 June 2019
Resolution: received videos of alarms functioning.
09 - Working and Living Conditions › 091 - Living Conditions › Lighting (Accommodation)
Issued 7 May 2019
Resolved
Lighting fixture in the "galley" space needs to be fixed.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 11 June 2019
Resolution: Light fixed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 May 2019
Resolved
Replace the following: Outlet in the "galley" space is cracked. Outlet on the bridge is cracked.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 11 June 2019
Resolution: outlets replaced.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 7 May 2019
Resolved
blank is missing from breaker panel on main deck.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 11 June 2019
Resolution: blank installed.
Lifesaving › Lifejacket/PFD (General) › Marking
Issued 3 May 2018
Resolved
Provide lifejacket donning instructions on starboard side of main deck stowage locker.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 June 2018
Resolved 30 May 2018
Resolution: Donning instructions have been placed near stowage.
Documentation › Certificates/Documents › FCC SSL
Issued 3 May 2018
Resolved
Provide proof of FCC ship station license.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 June 2018
Resolved 30 May 2018
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Mounting Bracket
Issued 3 May 2018
Resolved
Mount fire extinguisher in the crew only space in a proper bracket.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 June 2018
Resolved 30 May 2018
Resolution: Fire extinguisher is mounted correctly.
Lifesaving › Hand Flares › Quantity
Issued 3 May 2017
Resolved
03 orange smoke flares were missing.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 June 2017
Resolved 25 May 2017
Resolution: Flares onboard
Fire Fighting › Remote Fuel Shutoff › General
Issued 3 May 2017
Resolved
Fuel shutoff valve must be marked appropriately outside the space.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 June 2017
Resolved 24 May 2017
Resolution: Shutoff valve labeled.