07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 July 2023
Resolved
In a ship in which oil fuel is used, the arrangement for the storage, distribution and utilization of the fuel oil shall be such as to ensure the safety of the ship and persons on board. Oil fuel was found leaking from the number two cylinder on the emergency diesel generator.
74SOLASII-2/33(a)
Action code: 60 a c
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 17 July 2023
Resolved 20 July 2023
Resolution: Class report received. Fuel oil injector piping fittings were tightened for all cylinders, and two-hour run test was completed to the surveyor's satisfaction with no fuel oil leaks noted.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 17 July 2023
Resolved
Every oil fuel pipe which if damaged would allow oil to escape from a storage, settling or daily service tank situated above e double bottom, shall be fitted with a cock or valve on the tank capable of being closed from a position outside the space. The quick closing remote operated valve was found unable to open from a remote position. (Ship service/day tank)
74SOLAS II-2/33(a)(v)
16 a c
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 July 2023
Resolved 20 July 2023
Resolution: valve was fully closed, the opposing valve flange blanked, and the piping disconnected.
09 - Working and Living Conditions › 092 - Working Conditions › Gangway, accommodation-ladder
Issued 17 July 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Significant wastage found port accommodation ladder pipe. (hole)
74SOLAS(20)I/11(a)
16 a c
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 July 2023
Resolved 20 July 2023
Resolution: A new flanged tube was fabricated and installed into the existing structure. Ladder was operated, and found to be satisfactory by the attending surveyor.
02 - Structural Conditions › N/A - No Subsystem › Ballast, fuel and other tanks
Issued 17 July 2023
Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Significant wastage found on the number three port ballast sounding pipe. Pipe is holed through.
74SOLAS(20)I/11(a)
17 a c
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 17 July 2023
Resolved 20 July 2023
Resolution: Upon expanded examination, Ballast Water Tank No. 4, Port, which is adjacent to vent pipe BWT No. 3, Port, was found holed. The holed pipe was cropped and renewed to the attending surveyor's satisfaction.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 July 2023
Resolved
Main and emergency switchboards shall be so arranged as to give easy access back and front without danger to attendants. The sides and backs and , where necessary, the fronts of switchboards shall be suitably guarded. Electrical panel in engine control room found missing cover over an unused spare breaker.
74SOLASII-1/27(a)(ii)
17 a c
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 17 July 2023
Resolved 20 July 2023
Resolution: A cover was fabricated and installed to the surveyor's satisfaction for the unused spare (riserva) breaker located in the Engine Control Room.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 17 July 2023
Resolved
A public address system or other effective means of communication shall be available throughout the accommodation and service spaces and control stations. No means of effective communication or alarm was observed in the remote operated vehicle control module or workshop module.
74SOLASII-2/32(a)(vi)
60 a c
Condition: Design Flaw
Action required: 60 - Rectify deficiencies prior to movement
Due 17 July 2023
Resolved 20 July 2023
Resolution: New public address loudspeaker was installed adjacent to the ROV control module and workshop module. The speaker was tested, and found to be satisfactory for the spaces.